Gebruiksaanwijzing /service van het product CH5S1 van de fabrikant Bard
Ga naar pagina of 25
Manual 2100-455A Page 1 of 25 INST ALLA TION INSTRUCTIONS W ALL MOUNTED P ACKAGE HEA T PUMPS Models: CH3S1 CH4S1 CH5S1 Manual : 2100-455A Supersedes: 2100- 455 File: V olume III T ab 17 Date: 08-18-06 Bard Manufacturing Company , Inc. Bryan, Ohio 43506 Since 1914.
Manual 2100-455A Page 2 of 25 CONTENTS Figures Figure 1 Unit Dimensions CH3S1 ...................... 5 Figure 2 Unit Dimensions CH4S1 & CH5S1 ...... 6 Figure 3 Mounting Instructions CH3S1 ............ 1 0 Figure 4 Mounting Instructions CH4S1/CH5S1 .
Manual 2100-455A Page 3 of 25 Getting Other Information and Publications These publications can help you install the air conditioner or heat pump. You can usually find these at your local library or purchase them directly from the publisher. Be sure to consult current edition of each standard.
Manual 2100-455A Page 4 of 25 W ALL MOUNT GENERAL INFORMA TION HEAT PUMP WALL MOUNT MODEL NOMENCLATURE CH 4S 1 – A 05 B P X X X X TABLE 1 ELECTRIC HEAT TABLE s l e d o M A - 1 S 3 H CB - 1 S 3 H CC .
Manual 2100-455A Page 5 of 25 FIGURE 1 UNIT DIMENSIONS 16" 16" 16" 16" 16" 31 5/8" 32 3/4" 84 11/16" 43 7/8" 42 3/16" 13 3/8" 48 1/16" 5 13/.
Manual 2100-455A Page 6 of 25 FIGURE 2 UNIT DIMENSIONS 42 3/4" 39 7/8" 1 3/8" 6 7/8" Right Side View Front View MIS-2020 A Left Side View "CH4S1 and CH5S1" Unit Dimensions Back View Door Filter Access Supply Opening Mounting (12) Wall Return Opening Top Rain Flashing Evap.
Manual 2100-455A Page 7 of 25 TABLE 2 ELECTRICAL SPECIFICATIONS 1 Maximum size of the time delay fuse or HACR type circuit breaker for protection of field wiring conductors. 2 Based on 75°C copper wire. All wiring must conform to NEC and all local codes.
Manual 2100-455A Page 8 of 25 SHIPPING DAMAGE Upon receipt of equipment, the carton should be checked for external signs of shipping damage. If damage is found, the receiving party must contact the last carrier immediately, preferably in writing, requesting inspection by the carrier’s agent.
Manual 2100-455A Page 9 of 25 INST ALLA TION INSTRUCTIONS WALL MOUNTING INFORMATION 1. Two holes for the supply and return air openings must be cut through the wall as shown in Figure 3. 2. On wood frame walls, the wall construction must be strong and rigid enough to carry the weight of the unit without transmitting any unit vibration.
Manual 2100-455A Page 10 of 25 7 0" min. 0" min. " 6 8 1 3 8 " Unit Mounting Return Opening Supply Opening Holes, 12 places (Install before unit) Bottom Wall Bracket Wall B 43".
Manual 2100-455A Page 11 of 25 FIGURE 4 MOUNTING INSTRUCTIONS $ % ' & ( .
Manual 2100-455A Page 12 of 25 FIGURE 5 ELECTRIC HEAT CLEARANCE RECOMMENDED 1" OPTIONAL CLEARANCE Duct Outside Sheeting Unit Inside Sheeting Wall Frame Supply Air Typical Building Supply Air Duct Flange of Wall MIS-2210 Side section view of supply air duct for wall mounted unit showing 0" clearance to combustible surfaces.
Manual 2100-455A Page 13 of 25 FIGURE 6 WALL MOUNTING INSTRUCTIONS FIGURE 7 WALL MOUNTING INSTRUCTIONS MIS-2024 steel siding wall Interior finished wall Return opening structural steel 2x4's, 2x6's, and/or Framing material: unit before installing.
Manual 2100-455A Page 14 of 25 FIGURE 8 COMMON WALL MOUNTING INSTALLATIONS Isolation Curb WM1CF5-X Supply Air Return Air Silencer WAPR11-X RETURN AIR Free Blow Supply Plenum WAFB51-X Outside Wall Unit (outside) Note: duct maybe in attic or below rafters as shown.
Manual 2100-455A Page 15 of 25 Nine (9) wires should be run from thermostat subbase to the 24V terminal board in the unit. A nine conductor, 18 gauge copper color-coded thermostat cable is recommended.
Manual 2100-455A Page 16 of 25 LOW VOLTAGE CONNECTIONS FOR DDC CONTROL Fan Only Energize G Cooling Mode 1st S tage Energize Y , G Cooling Mode 2nd S tage Energize Y , Y1, G Heat Pump Heating 1st S tag.
Manual 2100-455A Page 17 of 25 ST ART UP CONT’D. SAFETY PRACTICES: 1. Never mix R-410A with other refrigerants. 2. Use gloves and safety glasses, Polyol Ester oils can be irritating to the skin, and liquid refrigerant will freeze the skin. 3. Never use air and R-410A to leak check; the mixture may become flammable.
Manual 2100-455A Page 18 of 25 Verification of proper rotation direction is made by observing that suction pressure drops and discharge pressure rises when the compressor is energized.
Manual 2100-455A Page 19 of 25 DEFROST CYCLE The defrost cycle is controlled by temperature and time on the solid state heat pump control. See Figure 12. When the outdoor temperature is in the lower 40° F temperature range or colder, the outdoor coil temperature is 32° F or below.
Manual 2100-455A Page 20 of 25 TROUBLESHOOTING SOLID STATE HEAT PUMP CONTROL TROUBLESHOOTING PROCEDURE 1. Turn on AC power supply to indoor and outdoor units. 2. Turn thermostat blower switch to fan on. The indoor blower should start. (If it doesn’t, troubleshoot indoor unit and correct problem.
Manual 2100-455A Page 21 of 25 CHECKING TEMPERATURE SENSOR OUTSIDE UNIT CIRCUIT 1. Disconnect temperature sensor from board and from outdoor coil. 2. Use an ohmmeter and measure the resistance of the sensor. Also use ohmmeter to check for short or open.
Manual 2100-455A Page 22 of 25 REMOVAL OF FAN SHROUD 1. Disconnect all power to the unit. 2. Remove the screws holding both grilles, one on each side of unit, and remove grilles. 3. Remove screws holding fan shroud to condenser and bottom. Nine (9) screws.
Manual 2100-455A Page 23 of 25 TABLE 9 MAXIMUM ESP OF OPERATION d e e p S h g i H L L A5 . TABLE 7 1 REFRIGERANT CHARGE - SUBCOOLING LEVEL G N I L O O CG N I T A E H l e d o M d e t a R w o l f r i A .
Manual 2100-455A Page 24 of 25 TABLE 10 PRESSURE TABLE TABLE 11 PRESSURE TABLE G N I L O O C Y T I C A P A C H G I H L E D O M R I A N R U T E R E R U T A R E P M E T E R U S S E R P 5 7 o F 0 8 o F 5.
Manual 2100-455A Page 25 of 25 TABLE 12 PRESSURE TABLE TABLE 13 PRESSURE TABLE G N I T A E H Y T I C A P A C H G I H F E E R G E D L I O C R O O D T U O G N I R E T N E E R U T A R E P M E T R I A L E.
Een belangrijk punt na aankoop van elk apparaat Bard CH5S1 (of zelfs voordat je het koopt) is om de handleiding te lezen. Dit moeten wij doen vanwege een paar simpele redenen:
Als u nog geen Bard CH5S1 heb gekocht dan nu is een goed moment om kennis te maken met de basisgegevens van het product. Eerst kijk dan naar de eerste pagina\'s van de handleiding, die je hierboven vindt. Je moet daar de belangrijkste technische gegevens Bard CH5S1 vinden. Op dit manier kan je controleren of het apparaat aan jouw behoeften voldoet. Op de volgende pagina's van de handleiding Bard CH5S1 leer je over alle kenmerken van het product en krijg je informatie over de werking. De informatie die je over Bard CH5S1 krijgt, zal je zeker helpen om een besluit over de aankoop te nemen.
In een situatie waarin je al een beziter van Bard CH5S1 bent, maar toch heb je de instructies niet gelezen, moet je het doen voor de hierboven beschreven redenen. Je zult dan weten of je goed de alle beschikbare functies heb gebruikt, en of je fouten heb gemaakt die het leven van de Bard CH5S1 kunnen verkorten.
Maar de belangrijkste taak van de handleiding is om de gebruiker bij het oplossen van problemen te helpen met Bard CH5S1 . Bijna altijd, zal je daar het vinden Troubleshooting met de meest voorkomende storingen en defecten #MANUAl# samen met de instructies over hun opplosinge. Zelfs als je zelf niet kan om het probleem op te lossen, zal de instructie je de weg wijzen naar verdere andere procedure, bijv. door contact met de klantenservice of het dichtstbijzijnde servicecentrum.