INST ALLA TION INSTRUCTIONS W ALL MOUNTED P ACKAGE AIR CONDITIONERS MODELS WL423 WL484 WL602 Manual : 2100-400 Supersedes: File: V olume III T ab 16 Date: 01-31-02 Bard Manufacturing Company Bryan, Ohio 43506 Since 1914...Moving ahead just as planned.
Figures Figure 1 Unit Dimensions ...................................... 3 Figure 2 Fresh Air Damper Assembly ................... 6 Figure 3 Mounting Instructions ............................... 8 Figure 4 Electric Heat Clearance ......................
Manual 2100-400 Page 1 Getting Other Information and Publications These publications can help you install the air conditioner or heat pump. You can usually find these at your local library or purchase them directly from the publisher. Be sure to consult current edition of each standard.
Manual 2100-400 Page 2 W ALL MOUNT GENERAL INFORMA TION HEAT PUMP WALL MOUNT MODEL NOMENCLATURE WL 42 3 – A 10 X N X X X A NOTE: All vent options are without exhaust capability.
Manual 2100-400 Page 3 FIGURE 1 UNIT DIMENSIONS MIS-1286 l e d o M h t d i W ) W ( h t p e D ) D ( - g i e H t h ) H ( y l p p u Sn r u t e R EF G I JKL M N O P Q R S T A BCB 2 4 L W 8 4 L W 0 6 L W 5 7 0 . 2 42 3 4 . 2 25 7 8 . 4 88 8 . 98 8 . 9 28 8 .
Manual 2100-400 Page 4 Maximum size of the time delay fuse or HACR type circuit breaker for protection of field wiring conductors. Based on 75 ° C copper wire. All wiring must conform to NEC and all local codes. These “ Minimum Circuit Ampacity ” values are to be used for sizing the field power conductors.
Manual 2100-400 Page 5 SHIPPING DAMAGE Upon receipt of equipment, the carton should be checked for external signs of shipping damage. If damage is found, the receiving party must contact the last carrier immediately, preferably in writing, requesting inspection by the carrier’s agent.
Manual 2100-400 Page 6 FRESH AIR INTAKE All units are built with fresh air inlet slots punched in the service panel. If the unit is equipped with a fresh air damper assembly, the assembly is shipped already attached to the unit. The damper blade is locked in the closed position.
Manual 2100-400 Page 7 INST ALLA TION INSTRUCTIONS W ARNING Failure to provide the 1/4 inch clearance between the supply duct and a combustible surface for the first 3 feet of duct can result in fire causing damage, injury or death. WALL MOUNTING INFORMATION 1.
Manual 2100-400 Page 8 FIGURE 3 MOUNTING INSTRUCTIONS MIS-947.
Manual 2100-400 Page 9 W ARNING A minimum of 1/4 inch clearance must be maintained between the supply air duct and combustible materials. This is required for the first 3 feet of ducting. It is important to insure that the 1/4 inch minimum spacing is maintained at all points.
Manual 2100-400 Page 10 FIGURE 5 WALL MOUNTING INSTRUCTIONS FIGURE 6 WALL MOUNTING INSTRUCTIONS MIS-1051 SEE FIGURE 3 – MOUNTING INSTRUCTIONS SUPPLY AIR DUCT RETURN AIR OPENING RETURN AIR OPENING SUPPLY AIR OPENING BOTTOM MOUNTING BRACKET. MOUNT ON WALL BEFORE INSTALLING UNIT.
Manual 2100-400 Page 11 FIGURE 7 COMMON WALL MOUNTING INSTALLATIONS FREE AIR FLOW NO DUCT DUCTED SUPPLY RETURN AT UNIT FALSE WALL INSTALLATION CLOSET INSTALLATION MIS-1050.
Manual 2100-400 Page 12 WIRING – MAIN POWER Refer to the unit rating plate for wire sizing information and maximum fuse or “HACR” type circuit breaker size. Each outdoor unit is marked with a “Minimum Circuit Ampacity”. This means that the field wiring used must be sized to carry that amount of current.
Manual 2100-400 Page 13 FIGURE 8 UNIT 24V TERMINAL BOARD MIS-1373A.
Manual 2100-400 Page 14 THREE PHASE SCROLL COMPRESSOR START UP INFORMATION Scroll compressors, like several other types of compressors, will only compress in one rotational direction. Direction of rotation is not an issue with single phase compressors since they will always start and run in the proper direction.
Manual 2100-400 Page 15 COMPRESSOR CONTROL MODULE The compressor control module is standard on the WL484 and WL602 models covered by this manual and is optional on the WL423 model. The compressor control is an anti-short cycle/lockout timer with high and low pressure switch monitoring and alarm relay output.
Manual 2100-400 Page 16 REMOVAL OF FAN SHROUD 1. Disconnect all power to the unit. 2. Remove the screws holding both grilles, one on each side of unit, and remove grilles. TROUBLESHOOTING The suction line temperatures in table above are based upon 80° F dry bulb / 67° F wet bulb (50% R.
Manual 2100-400 Page 17 TABLE 8 RECOMMENDED AIRFLOW * Rated CFM and ESP on high speed tap. l e d o M d e t a R * M F C d e t a R * P S E d e d n e m m o c e R e g n a R w o l f r i A 3 2 4 L W0 0 4 10 3 .0 5 1 1 - 0 0 6 1 4 8 4 L W0 5 5 10 2 .5 8 2 1 - 0 5 7 1 2 0 6 L W0 0 7 10 3 .
Manual 2100-400 Page 18 TABLE 11 OPTIONAL ACCESSORIES WL423-A WL423-B WL423-C WL484-A WL484-B WL484-C WL602-A WL602-B WL602-C t r a P r e b m u Nn o i t p i r c s e D 5 - P O B 5 - D A F B 5 - D A F M.
Een belangrijk punt na aankoop van elk apparaat Bard WL423 (of zelfs voordat je het koopt) is om de handleiding te lezen. Dit moeten wij doen vanwege een paar simpele redenen:
Als u nog geen Bard WL423 heb gekocht dan nu is een goed moment om kennis te maken met de basisgegevens van het product. Eerst kijk dan naar de eerste pagina\'s van de handleiding, die je hierboven vindt. Je moet daar de belangrijkste technische gegevens Bard WL423 vinden. Op dit manier kan je controleren of het apparaat aan jouw behoeften voldoet. Op de volgende pagina's van de handleiding Bard WL423 leer je over alle kenmerken van het product en krijg je informatie over de werking. De informatie die je over Bard WL423 krijgt, zal je zeker helpen om een besluit over de aankoop te nemen.
In een situatie waarin je al een beziter van Bard WL423 bent, maar toch heb je de instructies niet gelezen, moet je het doen voor de hierboven beschreven redenen. Je zult dan weten of je goed de alle beschikbare functies heb gebruikt, en of je fouten heb gemaakt die het leven van de Bard WL423 kunnen verkorten.
Maar de belangrijkste taak van de handleiding is om de gebruiker bij het oplossen van problemen te helpen met Bard WL423 . Bijna altijd, zal je daar het vinden Troubleshooting met de meest voorkomende storingen en defecten #MANUAl# samen met de instructies over hun opplosinge. Zelfs als je zelf niet kan om het probleem op te lossen, zal de instructie je de weg wijzen naar verdere andere procedure, bijv. door contact met de klantenservice of het dichtstbijzijnde servicecentrum.