CORPORATE OFFICE 13131 WES T LITTLE YORK ROAD HOUSTON, TX 7704 1 PHONE: (713) 466- 0277 (800 ) 231- 1412 FACSIMILE: (713) 896 - 5226 1 TOSH I BA G9000 80/100/160/225 kVA GUIDE SPECIFICATION THREE PHAS.
Guide Specification – 3-Phase Static Uninterr uptible Power Supply 2.
Guide Specification – 3-Phase Static Uninterr uptible Power Supply 3 Table of Contents 1 SCOPE ..........................................................................................................................................................
Guide Specification – 3-Phase Static Uninterr uptible Power Supply 4 9.2 R EMOTE S TATUS A LARM P ANEL (RSAP) ............................................................................................................................... 15 10 TOSHIBA DISTRIBUTION CABNET (TDC) (OPTION) .
Guide Specification – 3-Phase Static Uninterr uptible Power Supply 5 1 SCOPE 1.1 Sy stem Th ese specifications desc ribe a high eff iciency continuous duty, three-pha se, on-line, solid-state Uninterruptible Power Supply system (UPS).
Guide Specification – 3-Phase Static Uninterr uptible Power Supply 6 2.3 Sy stem Operation: The UPS shall operate as a f ully automatic on-line sy stem i n the following modes: 2.3.1 Normal I GBT Rectifier c onverts AC input power to DC power for the inverter and for cha rging the batteries.
Guide Specification – 3-Phase Static Uninterr uptible Power Supply 7 3.2.3 Clearances for installation Ceiling L evel : 20 ” minimum from top of UPS to ceiling Front : 40 ” minimum for maintenan.
Guide Specification – 3-Phase Static Uninterr uptible Power Supply 8 Current THD : <3% THD at 60% – 100% load <6% THD at 25% – 59% load (No input harmonic filter require d) 4.1.3 Charging Function: DC Nominal Voltage : 480 V AC Ripple on DC Bus : < 0.
Guide Specification – 3-Phase Static Uninterr uptible Power Supply 9 Harmonic Voltag e Distortion : < 2% THD (100% L inear L oad) : < 5% THD (100% Non-linear L oad) Phase Displacement : 1° Ma.
Guide Specification – 3-Phase Static Uninterr uptible Power Supply 10 5.2.3 Battery Protection The converter shall be provided with monitoring and control cir cuits to protect the battery sy stem from damag e due to excessive discharg e.
Guide Specification – 3-Phase Static Uninterr uptible Power Supply 11 5.3.5 Overload Capacity : The I nverter output shall be c apable of providing an overload curre nt of 125% for 2 min. and 150% for 1 min. A messag e on the control panel shall indicate this condition.
Guide Specification – 3-Phase Static Uninterr uptible Power Supply 12 I f the by pass sourc e is bey ond the conditions stated be low, interrupted transfer sha ll be made upon detection of a f ault condition. By pass voltage greater than + 10%, -10% from the UPS rated output voltag e.
Guide Specification – 3-Phase Static Uninterr uptible Power Supply 13 5.5.4 Mimic Panel A one-line diag ram of the sy stem shall be display ed on the touch pane l display panel to provide a visual status of contactors within UPS.
Guide Specification – 3-Phase Static Uninterr uptible Power Supply 14 6 MECHANICA L DESIGN 6.1 UPS Enclosure The UPS shall be a free standing NEMA1 enclosure equipped with a leveling c hannel base. The enclosure shall include provisions for hoisting , jacking, and fo rklift handling.
Guide Specification – 3-Phase Static Uninterr uptible Power Supply 15 9.1.2 HTTP Familiarity The RemotEy e I I shall provide a HTTP interfac e for the UPS to allow easy access of the UPS information from any machine with a web browser. At any ti me, a network workstation or management sta tion shall be able to open a RemotEy e II website.
Guide Specification – 3-Phase Static Uninterr uptible Power Supply 16 10 TOSHIBA DISTRIBUTION CABN ET (TDC) (OP TION) The manufacture r can optionally provide a matching TDC for the UPS. The TDC can include a step-down, 480/208/120 V transformer in a matching NEMA1 cabinet.
Guide Specification – 3-Phase Static Uninterr uptible Power Supply 17 14 EXTENDED SER VICES (OPTION) The UPS manufacturer c an offer : Startup Service Maintenance Contrac ts (Silver, Gold, Platinum).
Een belangrijk punt na aankoop van elk apparaat Toshiba G9000 (of zelfs voordat je het koopt) is om de handleiding te lezen. Dit moeten wij doen vanwege een paar simpele redenen:
Als u nog geen Toshiba G9000 heb gekocht dan nu is een goed moment om kennis te maken met de basisgegevens van het product. Eerst kijk dan naar de eerste pagina\'s van de handleiding, die je hierboven vindt. Je moet daar de belangrijkste technische gegevens Toshiba G9000 vinden. Op dit manier kan je controleren of het apparaat aan jouw behoeften voldoet. Op de volgende pagina's van de handleiding Toshiba G9000 leer je over alle kenmerken van het product en krijg je informatie over de werking. De informatie die je over Toshiba G9000 krijgt, zal je zeker helpen om een besluit over de aankoop te nemen.
In een situatie waarin je al een beziter van Toshiba G9000 bent, maar toch heb je de instructies niet gelezen, moet je het doen voor de hierboven beschreven redenen. Je zult dan weten of je goed de alle beschikbare functies heb gebruikt, en of je fouten heb gemaakt die het leven van de Toshiba G9000 kunnen verkorten.
Maar de belangrijkste taak van de handleiding is om de gebruiker bij het oplossen van problemen te helpen met Toshiba G9000 . Bijna altijd, zal je daar het vinden Troubleshooting met de meest voorkomende storingen en defecten #MANUAl# samen met de instructies over hun opplosinge. Zelfs als je zelf niet kan om het probleem op te lossen, zal de instructie je de weg wijzen naar verdere andere procedure, bijv. door contact met de klantenservice of het dichtstbijzijnde servicecentrum.