JK Series POWER DISTRIBUTION 400A & 720A Fixed T ype Medium V oltage Motor Contr ollers.
The low voltage section is oversized and is at a convenient height. This section is isolated from the medium voltage section and includes: Thermal Overload Protection Relay Pilot Lights (door mounted).
T oshiba's JK400 series complies with EEMAC, NEMA, UL and CSA standards and is available in non-reversing and reversing full voltage, autotrans- former , reactor , multi-speed, synchronous and wound rotor configurations. Latched contactors are also available.
MEDIUM VOL T AGE CONTROLLERS JK720 Series The new JK720 Series of motor controller is the result of extensive research and development. This state-of-the-art controller was designed in Houston, T exas, and is currently being manufac- tured under ISO 9001 standards in the same manufacturing facility as T oshiba motors and drives.
T oshiba's JK720 series complies with EEMAC, NEMA, UL and CSA standards and is available in non-reversing and reversing full voltage, autotrans- former , reactor , multi-speed, synchronous and wound rotor configurations. Latched contactors are also available.
JK Series Product Specification 400A MEDIUM VOLTAGE FIXED CONTROLLER 1. Standards 1.1 Basic controller shall comply with NEMA ICS3-1993, Part 2 (ICS2-324) and UL 347 Standards.
2.4 Handling and Installation 2.4.1 Removable angles or eye bolts shall be pr ovided at the top of t he structure for lifting. 3. Pow er Bus 3.1 Horizontal power bus shall be located at the cent er rear of the cubicle, in the same location as other JK Series controllers.
4.2 Bolted Pressure Isolation Switch 4.2.1 A Toshiba type JK fixed mounted, gang-oper ated isolation switch shall be provided with each controller to isolate the medium vo ltage compartment from the power source. 4.2.2 The switch shall be directly driven by an externally operable handle mounted on the right hand flange of the cubicle.
4.3.3 Power connections from the isolation switch to the main power fuses shall be made using bus bar. Connections from the contactor through the current transformers to the outgoing load terminals shall be made using power cable furnished by others. 4.
5. Ratings 5.1 Controller shall be rated as follows: 5.1.1 Interrupting Ratings: 400 Ampere Controller: - contactor 7.0kA @ 6.9kV - fused controller 50kA RMS Sym. @ 7.2kV 200MVA @ 2.3kV 350MVA @ 4.0kV 400MVA @ 4.6kV 570MVA @ 6.6kV 5.1.2 Continuous Thermal Ratings: 400 Ampere Controller: Enclosure type Max.
JK Series Product Specification 720A MEDIUM VOLTAGE FIXED CONTROLLER 1. Standards 1.1 Basic controller shall comply with NEMA ICS3-1993, Part 2 (ICS2-324) and UL 347 Standards.
2.4.1 Removable angles or eye bolts shall be pr ovided at the top of t he structure for lifting. 2.4.2 Optional removable sill channels shall be available. 3. Pow er Bus 3.1 Horizontal power bus shall be located at the cent er rear of the cubicle, in the same location as other JK Series controllers.
4.2 Bolted Pressure Isolation Switch 4.2.1 A fixed mounted, gang-operated isolation sw itch shall be provided with each controller to isolate the medium voltage compartment from the power source. 4.2.2 The switch shall be directly driven by an externally operable handle mounted on the right hand flange of the cubicle.
4.3.3 Power connections from the isolation switch to the contactor shall be made using bus bar. Connections from the contactor through the curr ent transformers to the outgoing load terminals shall be made using power cable. 4.3.4 The contactor shall be supplied with an optional mechanical latch with provisions for manual or electrical trip.
4.5.7 An electrical interlock shall be provided to ensure the isolation switch does not open with the control power transformer under load. This interlock shall be designed such that during switch opening, the transformer secondary is disconnected prior to the opening of the switch blades.
.
.
.
.
.
.
.
Medium V oltage Motor G7 Drive *pacjKSBROCH050218* ADJUST ABLE SPEED DRIVES MOTORS CONTROLS UPS INSTRUMENT A TION PLC INDUSTRIAL DIVISION 13131 W est Little Y ork Road, Houston, T exas 77041 T el 713/466-0277 Fax 713/466-8773 US 800/231-1412 Canada 800/872-2192 Mexico 01/800/527-1204 www .
Een belangrijk punt na aankoop van elk apparaat Toshiba JK Series (of zelfs voordat je het koopt) is om de handleiding te lezen. Dit moeten wij doen vanwege een paar simpele redenen:
Als u nog geen Toshiba JK Series heb gekocht dan nu is een goed moment om kennis te maken met de basisgegevens van het product. Eerst kijk dan naar de eerste pagina\'s van de handleiding, die je hierboven vindt. Je moet daar de belangrijkste technische gegevens Toshiba JK Series vinden. Op dit manier kan je controleren of het apparaat aan jouw behoeften voldoet. Op de volgende pagina's van de handleiding Toshiba JK Series leer je over alle kenmerken van het product en krijg je informatie over de werking. De informatie die je over Toshiba JK Series krijgt, zal je zeker helpen om een besluit over de aankoop te nemen.
In een situatie waarin je al een beziter van Toshiba JK Series bent, maar toch heb je de instructies niet gelezen, moet je het doen voor de hierboven beschreven redenen. Je zult dan weten of je goed de alle beschikbare functies heb gebruikt, en of je fouten heb gemaakt die het leven van de Toshiba JK Series kunnen verkorten.
Maar de belangrijkste taak van de handleiding is om de gebruiker bij het oplossen van problemen te helpen met Toshiba JK Series . Bijna altijd, zal je daar het vinden Troubleshooting met de meest voorkomende storingen en defecten #MANUAl# samen met de instructies over hun opplosinge. Zelfs als je zelf niet kan om het probleem op te lossen, zal de instructie je de weg wijzen naar verdere andere procedure, bijv. door contact met de klantenservice of het dichtstbijzijnde servicecentrum.