Gebruiksaanwijzing /service van het product VF-MB1/S15 van de fabrikant Toshiba
Ga naar pagina of 38
E6581738 TOSVERT VF-MB1/S15 PROFIBUS-DP Option Function Manual PDP003Z NOTICE 1. Read this manual before installing or operating. Keep this instruction manual on hand of the end user, and make use of this manual in maintenance and inspection. 2. All information contained in this manual will be changed without notice.
E6581738 Contents 1. Introduc tion ................................................................................................................... ........................... 1 2. Connection Info rmation........................................
E6581738 - 1 - 1. Introduction Thank you for purchasing the PROFIBUS-D P option “PDP003Z” for the VF-MB1/S15. Before using the PROFIBUS-DP option, pleas e familiarize yourself with the product and be sure to thoroughly read the instructions and precautions contained in this manual.
E6581738 - 2 - Safety precautions On the drive and in its instruction manual , important information is contained for preventing injuries to users and damages to assets and for proper use of the device.
E6581738 - 3 - ■ General Operation Warning Disassembly prohibited ▼ Never disassemble, modify or repair. Doing so could result in electric shock, fire and injury. For repairs, call your sales agency. Prohibited ▼ Do not attach this option to any drive other than the VF- MB1/S15.
E6581738 - 4 - ■ Wiring Warning Mandatory ▼ Shut off power when installing and wiring this option. Wait at least 15 minutes and check to make su re that the charge lamp (VF- MB1/S15) is no longer lit. ▼ Electrical construction work must be done by a qualified expert.
E6581738 - 5 - Notes on use Notes ▼ Do not install the drive where the temper ature or the humidity will change rapidly. ▼ Keep a distance of 20cm or more between the drive 's power cable and the data transmission cable. Or the drive might malfunction because of noise.
E6581738 - 6 - 2. Connection Information This option allows the VF-MB1/S15 drive to be communicated with the cyclic command transmission and monitoring of the original pr ofile ("Vendor spec.", refer to Section 4) of our company other than application profile "Pro file for Variable Speed Drives PROFIdrive (3.
E6581738 - 7 - 2.2. Status indicator The PDP003Z has two LEDs, ST (status) and DX (data exchange) to indicate the statuses of PROFIBUS-DP and the PDP003Z itself. ST (Status): Red LED LED Meanings Off No diagnostics present Flashes 8 Hz (Blinking 4 times/1sec.
E6581738 - 8 - 2.3. VF-MB1/S15 Communication parameters In a network, VF-MB1/S15 (PDP003Z) serves as a PROFIBUS slave device. PDP003Z configuration is set by the following parameters. Parameter Function Adjustment range Default setting c150 PDP003Z Station address 2 to 126 The station address "126" cannot exchange data.
E6581738 - 9 - 3. Profile 3.1. Telegram Telegram of PDP003Z is set up by the configurator. The figures below show the Telegrams and configurations that the PDP003Z supports .
E6581738 - 10 - 3.2. STW Control Word Data PDP003Z supports only speed control mode. Bit Value Name Note 1 ON “Switched on” condition 0 0 OFF Normal stop. 1 No Coast Stop All "Coast Stop (OFF2)" commands are withdraw n 1 0 Coast Stop (OFF 2) Coast stop.
E6581738 - 11 - 3.3. ZSW Status Word Data Bit Valure Name Note 1 Ready To Switch-on Power supply is switched on 0 0 Not Ready To Switch-on - 1 Ready To Operate Refer to control word, bit 1. 1 0 Not Ready To Operate - 1 Operation Enabled Drive follows setpoint.
E6581738 - 12 - 3.3.1. Tolerance Range (ZSW Bit 8) If the setpoint is changed: 1. ZSW Bit 8 is set 0 2. Calculate the tolerance. 3. Start the timer which will ti me-out based on parameter Tmax. PDP003Z checks that the timer (Tmax) has not timed-out and if the actual value is within the tolerance.
E6581738 - 13 - 3.4. State Machine STW: Control Word ZSW: Status Word : State : Condition Notes STW Bit 10, 12 = 1 or cmod = 4 is needed for above control. If cmod is set to Local (0, 1, 2 or 3), set 1 to STW Bit10 and 12 first after turning on the power supply of VF-MB1/S15.
E6581738 - 14 - 3.4.1. Examples of driving by the State Machine When using the PROFIdrive profile, the frequenc y reference is set to HSW. The setting value “0x0000” - ”0x4000” is equivalent to ”0” - ”Base frequency (parameter fh )”.
E6581738 - 15 - 3.5. Access to the PROFIBUS parameter In the cyclic PROFIBUS-DP communication, t he parameter data is transferred via T ele gra m 100, 101.
E6581738 - 16 - 3.6. PROFIBUS parameter (PNU) PNU R/W data type Note 915 R Array [6] Unsigned16 PNU 915, IND 0 = the drive parameter c001 PNU 915, IND 1 = the drive parameter c002 PNU 915, IND 2 =.
E6581738 - 17 - 3.6.1. Examples of reading the PROFIdrive parameter 3.6.1.1. Example 1. Reading t he PNU 922 (Telegram) AK = 1 (Request parameter value) SPM = 0 PNU = 922 (0x039A) PKE 0 0 0 1 0 0 .
E6581738 - 18 - 3.7. Access to VF-MB1/S15 parameter When access to VF-MB1/S15 parameter, set “1” to the PNU. The communication number of the drive parameter is set to the subindex IND. Refer to the drive instruction manual about the communication number and unit.
E6581738 - 19 - 3.7.1.3. Example 3. Reading the stat us monitor parameter ( fe02 (The operation frequency)) AK = 6 (Request parameter value (array)) SPM = 0 PNU = 1 IND = 0xFE02( fe02 communicatio.
E6581738 - 20 - 4. Vendor Spec. Profile Cyclic command transmission (the value of the parameter c001 - c006 ) and monitoring (the value of the parameter c021 - c026 ) are possible for PDP003Z by the original profile Select the ”Telegram 100”, ”Telegram 101” or ”Telegram 102” as the profile on the configuration.
E6581738 - 21 - 4.1. How to use The purposes are adjustment by real time command transmission, and the monitor of an operation state by using cyclic communication of PROFIBUS. Example 1: Command transmitting When you want to set "0xC400" to parameter fa06 , set “1 ( fa06 )” to parameter c001 .
E6581738 - 22 - 4.2. The overview of the VF-MB1/S15 parameter Refer to a communication functional description (E6581726/E6581913) for details. 4.2.
E6581738 - 23 - 4.2.2. fa23 (Communication command 2) bit Function 0 1 Note 0 (Reserved) - - - 1 Electric power quantity reset OFF Reset Electric power quantity ( fe76 , fe77 ) reset 2 (Reserved) .
E6581738 - 24 - 4.2.3. fa07 (frequency reference from internal option) Frequency reference is set up by 0. 01Hz unit and the hexadecimal number. For example, when "Frequency reference" is set up to 80Hz, since the minimum unit is 0.01Hz, 80 / 0.
E6581738 - 25 - 4.2.6. fd01 (Inverter operating status 1 (real time)) bit Function 0 1 Note 0 Failure FL No output Under in progress - 1 Failure Not tripped Tripped Trip status includes rtry and the trip retention status are also regarded as tripped statuses.
E6581738 - 26 - 4.2.8. fd03 (Output current (real time)) The output current is read into 0.01% of units and by the hexadecimal number. For example, when the output current of the rated current 4.8A driv e is 50% (2.4A), 0x1388 (hexadecimal number) is read out.
E6581738 - 27 - 4.2.12. fc91 (Alarm code) bit Function 0 1 Remarks (Code displaye d on the panel) 0 Over-current alarm Normal Alarming c flicking 1 Inverter over load alarm Normal Alarming l flick.
E6581738 - 28 - 4.2.14. fd07 (Output TB Status) bit TB Name Function (Parameter) 0 1 0 RY -R C Output terminal function selection 1A ( f130 ) OFF ON 1 OUT Output TB Function select 2A ( f131 ) OFF ON 2 FL Output TB Function select 3 ( f132 ) OFF ON 3 - 15 (Undefined) - - - Note: The bit described "Undefined" is unstabl e.
E6581738 - 29 - 5. Diagnostic When the communication loss occurs, PDP003Z returns the diagnosis telegram including the following information. Byte 1: Station Status 1 Byte 2: Station Status 2 Byte.
E6581738 - 30 - 6. DP-V1 function DP-V1 acyclic communication is mainly us ed to read/write the parameter. VF-MB1/S15 parameter and the PROFIBUS parameter can be read/written using PDP003Z. The following setting is necessary in the configuration to communicate DP-V1.
E6581738 - 31 - 6.1. Example1. Read the PROFIdrive parameter 6.1.1. Write Request data table (Read PNU 964 (0x03C4) IND 4) Field Description Value Header DU0 Function number 0x5F Header DU1 Slot n.
E6581738 - 32 - 6.2. Example 2. Change the PROFIdrive parameter 6.2.1. Write Request data table (Change, set 0 to PNU 927 (0x039F)) Field Description Value Header (DU0) Function number 0x5F Header.
E6581738 - 33 - 6.3. Example 3. Read the VF-MB1/S15 parameter When access to VF-MB1/S15 parameter, set “1000” to the PNU. 6.3.1. Write Request data table (Read fd04 (Input voltage)) Field Desc.
E6581738 - 34 - 6.4. Example 4. Change the VF-MB1/S15 parameter When access to VF-MB1/S15 parameter, set “1000” to the PNU. * This procedure changes the value of VF-MB1/S15 EEPROM.
E6581738 - 35 - 7. PROFIBUS Local/Remote Operation The example below shows how to configur e the VF-MB1 for local/remote operation. <Terminal function> F terminal ............ RUN command R terminal ............ Local (Terminal in this example) / PROFIBUS s witching VIA terminal .
E6581738 - 36 - 9. Appendix Function number 0x5E: Read Request 0x5F: Write Request 0x5E: Positive response for Read request 0x5F: Positive response for Write request 0xDE: Negative response for Re.
Een belangrijk punt na aankoop van elk apparaat Toshiba VF-MB1/S15 (of zelfs voordat je het koopt) is om de handleiding te lezen. Dit moeten wij doen vanwege een paar simpele redenen:
Als u nog geen Toshiba VF-MB1/S15 heb gekocht dan nu is een goed moment om kennis te maken met de basisgegevens van het product. Eerst kijk dan naar de eerste pagina\'s van de handleiding, die je hierboven vindt. Je moet daar de belangrijkste technische gegevens Toshiba VF-MB1/S15 vinden. Op dit manier kan je controleren of het apparaat aan jouw behoeften voldoet. Op de volgende pagina's van de handleiding Toshiba VF-MB1/S15 leer je over alle kenmerken van het product en krijg je informatie over de werking. De informatie die je over Toshiba VF-MB1/S15 krijgt, zal je zeker helpen om een besluit over de aankoop te nemen.
In een situatie waarin je al een beziter van Toshiba VF-MB1/S15 bent, maar toch heb je de instructies niet gelezen, moet je het doen voor de hierboven beschreven redenen. Je zult dan weten of je goed de alle beschikbare functies heb gebruikt, en of je fouten heb gemaakt die het leven van de Toshiba VF-MB1/S15 kunnen verkorten.
Maar de belangrijkste taak van de handleiding is om de gebruiker bij het oplossen van problemen te helpen met Toshiba VF-MB1/S15 . Bijna altijd, zal je daar het vinden Troubleshooting met de meest voorkomende storingen en defecten #MANUAl# samen met de instructies over hun opplosinge. Zelfs als je zelf niet kan om het probleem op te lossen, zal de instructie je de weg wijzen naar verdere andere procedure, bijv. door contact met de klantenservice of het dichtstbijzijnde servicecentrum.