Ins talla ti on/ Op er a t ion Maint enan c e V ar i T r ane ™ Pne umati c Con tr ols V A V -S V X0 2 B-EN March 2002.
V A V -SVX02B-EN Thermost at Selec tion and Location In general, both one- and two-pipe thermost ats have a gain of 2.5 psi per degree F ahrenheit, unless special thermosta ts are used that provide a different g ain.
3 V A V -SVX02B-EN Thermostat Specif icat ions TP970 S eries Pneumatic T -stats Maximum Safe Air Pressure: 25psi (172 kPa) Maximum S afe Air T emperature: 150°F (66°C) Throttling Range: 2–1 0°F (1–5°C) Gain: 2.5 psi/ °F Adjustable Ope ra t ion Pneumatic thermost ats modulate out put air pressure in respons e to room air temperature.
V A V -SVX02B-EN Inst alla tion and Oper a t ion The reversing relay is a proportional, non-bleeding device for use in pneu- matic control systems where a propor - tional signal from a controlling device must be reversed (see Figure 5). The most common use of the reversing relay is to c hange the action of a pneumatic thermostat.
5 V A V -SVX02B-EN Re v er sing Rela y Calibrat ion By using the “bias” adjustment on the relay , t he factory-set 8.0 – 9.0 “cross- over” can be c hanged. T o recalibrate, the relay should be connected as illustrated in F igure 8. F igure 8 – Rec a libra ting Reve rsing Re lay If the new desired “cross-over” pressure is 1 1 .
V A V -SVX02B-EN Model 30 1 1 The model 30 1 1 Pneumatic V olume Regulator (PVR) is capable of operating with normally-open or normally-closed air valves and can operate with either direct-acting (DA) or reverse-acting (RA) thermostats. F igure 9 – Accepta ble Installa tion Positions Ins ta lla tion 1 .
7 V A V -SVX02B-EN Use the following procedure to set-up the PVR: 1 . Select damper action (NO or NC). Loosen damper selection switc h screw and align to either the NO or NC pointer with damper pointer and tighten screw. 2 . Now determine the type of thermostat that will be used.
V A V -SVX02B-EN Calibration P r oced ur es Calibr a ti on P roc e dure (Steps 1– 4 apply to all ther mos t a t m odels) 1 . Be sure the PVR is installed correctly and that all connections are hooked up to the proper ports. See Figure 9 for unit appl ication.
V A V -SVX02B-EN 9 Spe cifica tions (30 1 1) Differential Pressure Range: 0 to 1 .0 in. wg Minimum Set point Range: 0 to 1 .0" H 2 O Maximum Set point Range: minimum to 1 .0 in. w g Operating Static Range: 0.25 – 6.0 in. wg Sp e cif ic ations (30 1 1) Normal Supply Air Pressure: 20.
V A V -SVX02B-EN 10 Model 350 1 The model 350 1 Pneumatic V olume Regulator (PVR) is capable of operating with normally-open or normally-closed air valves and can operate with either direct-acting (DA) or reverse-acting (RA) thermostats. Adjusting the Reset Span (350 1) The reset span is factory-set at 5 psi.
V A V -SVX02B-EN 11 Calibration P r ocedures Calibr ation Pr oce dure (Steps 1– 4 apply to all ther mostat models) 1 . Be sure the PVR is installed correctly and that all connections are hooked up to the proper ports. 2 . Remove the caps on the tees, whic h are connected to the lines to the flow sensor .
V A V -SVX02B-EN 12 Spec if ica t ions (350 1) Differential Pressure Range: 0 to 1 .0 in. wg Minimum Setpoint Range: 0 to 1 .0" H 2 O Maximum Setpoint Range: minimum to 1 .0 in. w g Maximum Setpoint Range: 6.0 in. wg Normal Supply Air Pressure: 20.
V A V -SVX02B-EN 13 MCP -3631—Rotary Pneumatic D amper Ac tuat or Desc ription: Rotary actuators mounts to a standard ½" diameter shaf t by a loc king collar and bushing.
V A V -SVX02B-EN 14 Constant V ol ume Dual-Duct Calibration (30 1 1) This calibration procedure is used when a constant volume of air must be maintained through a unit. On a dual- duct unit, a constant-volume disc harge sensor is used to measure the air leaving the unit.
V A V -SVX02B-EN 15 Thermostat Range: 3 – 8 psi Heating V alve = 5 psi range Thermostat Range: 8 –13 psi Cooling V alve = 5 psi range Approximately 1 0 0 0 cfm di vided by 5 psi = 200 cfm/1b* *Due.
T rane An American Standard Company www.trane.com For more information contact your local district office or e-mail us at comfort@trane.com Liter ature Order Number V AV - S V X02B - EN Fil e Number S.
Een belangrijk punt na aankoop van elk apparaat Trane VAV-SVX02B-EN (of zelfs voordat je het koopt) is om de handleiding te lezen. Dit moeten wij doen vanwege een paar simpele redenen:
Als u nog geen Trane VAV-SVX02B-EN heb gekocht dan nu is een goed moment om kennis te maken met de basisgegevens van het product. Eerst kijk dan naar de eerste pagina\'s van de handleiding, die je hierboven vindt. Je moet daar de belangrijkste technische gegevens Trane VAV-SVX02B-EN vinden. Op dit manier kan je controleren of het apparaat aan jouw behoeften voldoet. Op de volgende pagina's van de handleiding Trane VAV-SVX02B-EN leer je over alle kenmerken van het product en krijg je informatie over de werking. De informatie die je over Trane VAV-SVX02B-EN krijgt, zal je zeker helpen om een besluit over de aankoop te nemen.
In een situatie waarin je al een beziter van Trane VAV-SVX02B-EN bent, maar toch heb je de instructies niet gelezen, moet je het doen voor de hierboven beschreven redenen. Je zult dan weten of je goed de alle beschikbare functies heb gebruikt, en of je fouten heb gemaakt die het leven van de Trane VAV-SVX02B-EN kunnen verkorten.
Maar de belangrijkste taak van de handleiding is om de gebruiker bij het oplossen van problemen te helpen met Trane VAV-SVX02B-EN . Bijna altijd, zal je daar het vinden Troubleshooting met de meest voorkomende storingen en defecten #MANUAl# samen met de instructies over hun opplosinge. Zelfs als je zelf niet kan om het probleem op te lossen, zal de instructie je de weg wijzen naar verdere andere procedure, bijv. door contact met de klantenservice of het dichtstbijzijnde servicecentrum.