IMPORTANT — This Document is customer property and is to remain with this unit. Please return to service information pack upon completion of work. ALL phases of this installation must comply with NA.
Page 2 TYPICAL ROOFTOP INSTALLATION WITH FULL PERIMETER CURBS (WCY024-060G Models) GENERAL INFORMA TION IMPORTANT: Read this entire manual before beginning instal- lation procedures. SAFETY NOTICE. THIS INFORMATION IS INTENDED FOR USE BY INDIVIDUALS POSSESSING ADEQUATE BACK- GROUNDS OF ELECTRICAL AND MECHANICAL EXPERI- ENCE.
Page 3 ROOF INSULA TION ROOF DECK FIELD SUPPLIED RIGID INSULA TION SUPPL Y AIR DUCT RETURN AIR DUCT ROOF MOUNTING CURB FIELD SUPPLIED CANT STRIP FIELD SUPPLIE D SUPPORTS A T EACH END OF CURB ROOFING SEE NOTE 1 SEE NOTE 2 CONVERTING HORIZONTAL TO DOWNFLOW TYPICAL ROOFTOP INSTALLATION WITH BAYCURB030A (WCY024-060G Models) NOTE SUPPLY OPENING 1.
Page 4 DIMENSIONAL D A T A 4 MOD EL CORNER WEIGHT(LBS) UNIT WEI G HT AB C D E F G H J KL M N P W1 W2 W3 W4 WCY 024G 79 74 74 104 331 56-1/2 36 29-3/16 18-9/16 11-1/1 6 6-9/16 6-13/16 17 21 25-3/8 17 -.
Page 5 DIMENSIONAL D A T A 5 From Dwg. 21D664 MODEL A B C D WCY024G WCY030G 56-1 /2 36 2 9-3/16 12-15 /1 6 WCO36G WCY042G 64 36 29-3/1 6 14- 1/2 WCY048G WCY060G 65-1/8 45 33-3/8 14 -13/1 6 RECOMM ENDED SER VI CE CLEARANC E BA CK * 6.0" LEFT SIDE 30.
Page 6 REQUIRED CLEARANCE FOR UNIT INSTALLATION AND ROOF PENETRATION HOLE SIZE REQUIRED LOCA TIONS AND RECOMMEND A TIONS These units are designed for outdoor installation. For proper instal- lation, the following recommendations must be considered. NOTE: Unit shipped for horizontal installation.
Page 7 INST ALLA TION IMPORTANT!: DO NOT LIFT THE UNIT WITHOUT TEST- LIFTING FOR BALANCE AND RIGGING.DO NOT LIFT THE UNIT IN WINDY CONDITIONS OR ABOVE PERSONNEL. DO NOT LIFT THE UNIT BY ATTACHING A CLEVIS, HOOKS, PINS OR BOLTS TO THE UNIT CASING, CASING HARD- WARE, ANGLES, TABS OR FLANGES.
Page 8 8 7 NOTE: The inner perimeter of the Drip Lip on all units should be flush with the outer perimeter of the curb on the two sides shown here. See Figure 2 for the location of the unit overhang on the WCY036-060G Models with BAYCURB030A.
Page 9 TYPICAL ROOFTOP APPLICATION WITH FRAME (WCY024-060G MODELS) INST ALLA TION ROOFTOP -- UNITS For roof top applications using a field fabricated frame and ducts, use the following procedure: 1. The frame must be located and secured by bolting or welding to the roof.
Page 10 TYPICAL GROUND LEVEL APPLICATION (WCY024-060G MODELS) INST ALLA TION GROUND LEVEL -- HORIZONTAL UNITS For ground level installations, the unit should be positioned on a pad the size of the unit or larger. The unit must be level on the pad. The pad must not come in contact with the structure (See Figure 11.
Page 11 DUCT ATTACHMENT METHODS 3 / 4 " PVC OR COPPER TUBING AND FITTINGS 1-1/2" MIN. TYPICAL CONDENSATE DRAIN PIPING A 3/4-inch female NPT condensate drain connection is pro- vided on the evaporator access panel end of the unit. See Figure 4.
Page 12 ELECTRICAL CONNECTIONS Electrical wiring and grounding must be installed in accordance with local codes or, in the absence of local codes, with the National Electrical Code ANSI/NFPA 70, Latest Revision. ELECTRICAL POWER It is important that proper electrical power be available for the unit.
Page 13 WCY-G FIELD WIRING DIAGRAM Thermostat System Switch until power has been applied long enough to evaporate any liquid R-22 in the compressor. It is recommended that the sump heater be energized for eight (8) hours prior to starting.
Page 14 ST AR T - UP To start the unit in the cooling mode, set the thermostat system switch to COOL and move the thermostat COOL indicator to a setting below room temperature. The condenser (outdoor) fan motor compressor and evaporator (indoor) fan motor will operate automatically.
Page 15 SEQUENCE OF OPERA TION GENERAL Operation of the unit heating and cooling cycles is automatic for HEAT and COOL functions. (The optional automatic changeover thermostat, when in the AUTO position, automatically changes to heat or cool with sufficient room temperature change.
Page 16 FLASH RA TE INDICA TIONS: 1 — Flash/Second = Normal operation. 2 — Flashes/Second = F ault A (Low ∆ T) i.e.: Inoperativ e compressor , loss of charge, open ambient sensor , shor ted coil sensor . 3 — Flashes/Second = F ault B (20 defrosts ter minated on time) F ault C (High ∆ T) i.
Page 17 DEMAND DEFR OST CONTROL CHECK OUT SYMPTOMS CHECKS YES/NO A CTIONS 1. LED off . 1. 24V R-B & Y -B at board, with unit running? N Repair low v oltage wiring. Y Complete Check #2. 2.Shor t FRC_DFT pin to TEST_COMMON pin. Is defrost cycle initiated? N Replace defrost control.
Page 18 ROUTINE MAINTENANCE BY OWNER You can do some of the periodic maintenance functions for your WCY-G unit yourself; this includes replacing the dispos- able or cleaning the permanent air filters, cleaning the unit cabinet, clearing the condenser coil, and conducting a general unit inspection on a regular basis.
Page 19 LIMITED WARRANTY HIGH EFFICIENCY HEAT PUMP WCZ, WCY AND WCX Models Less Than 20 Tons for Residential Use* (Parts Only) This limited w ar ranty is extended by American Standard Inc.
Page 20 Technical Literature - Printed in U.S.A. LIMITED WARRANTY HIGH EFFICIENCY HEAT PUMP WCZ, WCY, WCX, WCC, WCD, WCH, WCM AND WSC Models Less Than 20 Tons for Commercial Use* (Parts Only) This warr anty is extended by American Standard Inc.
Een belangrijk punt na aankoop van elk apparaat Trane WCY036G1 (of zelfs voordat je het koopt) is om de handleiding te lezen. Dit moeten wij doen vanwege een paar simpele redenen:
Als u nog geen Trane WCY036G1 heb gekocht dan nu is een goed moment om kennis te maken met de basisgegevens van het product. Eerst kijk dan naar de eerste pagina\'s van de handleiding, die je hierboven vindt. Je moet daar de belangrijkste technische gegevens Trane WCY036G1 vinden. Op dit manier kan je controleren of het apparaat aan jouw behoeften voldoet. Op de volgende pagina's van de handleiding Trane WCY036G1 leer je over alle kenmerken van het product en krijg je informatie over de werking. De informatie die je over Trane WCY036G1 krijgt, zal je zeker helpen om een besluit over de aankoop te nemen.
In een situatie waarin je al een beziter van Trane WCY036G1 bent, maar toch heb je de instructies niet gelezen, moet je het doen voor de hierboven beschreven redenen. Je zult dan weten of je goed de alle beschikbare functies heb gebruikt, en of je fouten heb gemaakt die het leven van de Trane WCY036G1 kunnen verkorten.
Maar de belangrijkste taak van de handleiding is om de gebruiker bij het oplossen van problemen te helpen met Trane WCY036G1 . Bijna altijd, zal je daar het vinden Troubleshooting met de meest voorkomende storingen en defecten #MANUAl# samen met de instructies over hun opplosinge. Zelfs als je zelf niet kan om het probleem op te lossen, zal de instructie je de weg wijzen naar verdere andere procedure, bijv. door contact met de klantenservice of het dichtstbijzijnde servicecentrum.