Owner’ s Man ual 1111 W. 35th Street • Chicago, IL 60609 USA Customer Support: (773) 869-1234 • Application Services: (773) 869-1236 www .tripplite.
2 Impor tant Safety W arnings SA VE THESE INSTR UCTIONS. This manual contains important instructions and w arnings that should be followed during the installation and maintenance of all T ripp Lite SmartOnline Rackmount UPS Systems and their batteries.
3 Mounting 1 Single Unit Installation 1 2 3 A B C B E D F 4 G Connect the two segments of each shelf (A) using the included scre ws and nuts (B). Leav e the screws slightly loose so that the shelv es can be adjusted in the next step.
4 Mounting continued Connect the shelved sections from two UPSRMRII kits (A) to the unshelv ed sections (B) using the included scre ws and nuts (C). Note: T wo unshelv ed sections will be left ov er . Leav e the screws slightly loose so that the shelv es can be adjusted in th e next step.
Mount the shelved sections (A) of your UPSRMRII kit on the back side of your rack. Mount them in the lowest a v ailable space of your rack with with the screws, nuts and washers provided (B). Note that the support ledges should f ace inward. Attach mounting ears (C) to the front mounting holes of your equipment (D) using the screws pro vided (E).
6 Features Familiarize yourself with the location and function of the front and rear panel features before installing and operating your UPS. UPS Front P anel Controls The UPS Front Panel Controls can be rotated in its mounting to match your to wer or rackmount installation.
7 Features continued UPS Rear P anel EPO ACC. RS-232 DRY CONT ACT AC INPUT AC OUTPUT BREAKER AC INPUT BREAKER EXTERNAL BA TTER Y INPUT 240VDC CA UTION: DO NOT DISCONNECT UNDER LOAD GL 1 L 2 L2 L1 G GL 1 L 2 L2 L1 G AC OUTPUT CU S U L Input: 200/208/220/230/240V~, 50/60Hz 29.
8 Features continued UPS Rear P anel 1. Output T erminal Block: Use these terminals to connect your UPS to your equipment or to the transformer’ s UPS Connector .
9 Hard wire y our utility power sour ce to your UPS’ s input. Remov e the top of the box covering the UPS’ s power terminals. P ass one end of a power cable through the UPS’ s cov er box’ s right knockout, then connect it to the UPS’ s input terminals.
10 N O R M A L B Y P A S S Hard wire y our isolation transformer’ s UPS connector to y our UPS’ s input and output. Remov e the tops of the boxes cov ering the UPS’ s and transformer’ s input and output terminals.
11 Connection continued Connect external battery pac k(s) to your UPS Y our UPS has no internal batteries and must be connected to at least one external battery pack to operate. Complete installation and mounting instructions for your battery pack(s) appear in the battery pack(s)’ s owner’ s manual.
12 T urn input to the UPS ON If the UPS is connected to a transformer , turn the transformer’ s UPS and Load Breakers ON. T urn the UPS’ s Input Circuit Breaker ON. Press the UPS’ s ON button until you hear a beep to begin in verter operation. If your AC input is not pro viding power normally , you may “cold start” your UPS from battery .
13 DIAGNOSTIC MODE AC/DC OK DIAGNOSTIC MODE TESTING INVERTER ON BA TTER Y MODE LOAD = XXX% X.XXKW Operation When you turn the UPS ON, it will enter Diagnostic Mode and perform a brief self-test lasting about 15 seconds. The results of the self-test are shown on the LCD screen in the sequence belo w .
14 Operation continued During normal operation, the first line of your LCD Display sho ws which operating mode your UPS is in: Online, Economy , On Battery , or Bypass. Online mode: The UPS pro vides A C po wer while utility power is a vailable and switches to On Battery mode instantly (zero transfer time) if AC po wer is interrupted.
15 Operation continued While in Bypass Mode, the UPS monitors its input voltage and passes that input po wer along to connected equipment. The UPS will not provide battery backup in Bypass Mode.
16 Service/W arranty and Insurance Y our SmartOnline UPS is cov ered by the 2-year limited warranty period described below . A variety of service contracts is also a vailable from T ripp Lite, including start-up service contracts and 3- to 5-year SafeSure on-site service contracts.
17 Specifications Specifications are for UPS, Isolation T ransformer , and one battery pack. Model SU6000RT3U SU10KRT3U Input UPS Input V oltage 156V~276V Single Phase 156V~276V Single Phase T ransformer Input V oltage 200/208/220/230/240V 200/208/220/230/240V Input F requency 50/60 Hz ± 3 Hz 50/60 Hz ± 3 Hz Input Current 22.
Een belangrijk punt na aankoop van elk apparaat Tripp Lite SU6000RT3UPM (of zelfs voordat je het koopt) is om de handleiding te lezen. Dit moeten wij doen vanwege een paar simpele redenen:
Als u nog geen Tripp Lite SU6000RT3UPM heb gekocht dan nu is een goed moment om kennis te maken met de basisgegevens van het product. Eerst kijk dan naar de eerste pagina\'s van de handleiding, die je hierboven vindt. Je moet daar de belangrijkste technische gegevens Tripp Lite SU6000RT3UPM vinden. Op dit manier kan je controleren of het apparaat aan jouw behoeften voldoet. Op de volgende pagina's van de handleiding Tripp Lite SU6000RT3UPM leer je over alle kenmerken van het product en krijg je informatie over de werking. De informatie die je over Tripp Lite SU6000RT3UPM krijgt, zal je zeker helpen om een besluit over de aankoop te nemen.
In een situatie waarin je al een beziter van Tripp Lite SU6000RT3UPM bent, maar toch heb je de instructies niet gelezen, moet je het doen voor de hierboven beschreven redenen. Je zult dan weten of je goed de alle beschikbare functies heb gebruikt, en of je fouten heb gemaakt die het leven van de Tripp Lite SU6000RT3UPM kunnen verkorten.
Maar de belangrijkste taak van de handleiding is om de gebruiker bij het oplossen van problemen te helpen met Tripp Lite SU6000RT3UPM . Bijna altijd, zal je daar het vinden Troubleshooting met de meest voorkomende storingen en defecten #MANUAl# samen met de instructies over hun opplosinge. Zelfs als je zelf niet kan om het probleem op te lossen, zal de instructie je de weg wijzen naar verdere andere procedure, bijv. door contact met de klantenservice of het dichtstbijzijnde servicecentrum.