Gebruiksaanwijzing /service van het product 36CDVRRN van de fabrikant Vermont Casting
Ga naar pagina of 40
Installation Instructions and Homeowner ’ s Manual 20010175 6/06 Rev . 2 Builder Direct V ent Models: 36CDVRRN (Rear V ent) 36CDVTRN (T op V ent) DO NOT ST ORE OR USE GASOLINE OR OTHER FLAMMABLE V APORS AND LIQUIDS IN THE VICINITY OF THIS OR ANY OTHER APPLIANCE.
2 CDV Series Direct Vent Gas Fireplace 20010175 PLEASE READ THE INST ALLA TION & OPERA TING INSTRUCTIONS BEFORE USING APPLIANCE. Thank you and congratulations on your purchase of a CFM Corporation fireplace. IMPORT ANT : Read all instructions and warnings carefully before starting installation.
3 CDV Series Direct Vent Gas Fireplace 20010175 This gas appliance should be installed by a qualified installer in accordance with local building codes and with current CSA-B149.1 Installation codes for Gas Burning Appliances and Equipment. For USA Installations follow local codes and/or the current National Fuel Gas Code.
4 CDV Series Direct Vent Gas Fireplace 20010175 O F X - Rough Opening Width Rough Opening Height Rough Opening Depth U U V T W G I H J E A Y B K L Q Gas Line Access Gas Line Access Low V oltage Electr.
5 CDV Series Direct Vent Gas Fireplace 20010175 O F X - Rough Opening Width Rough Opening Height Rough Opening Depth U U V T W G J E A Y B K L Q Gas Line Access Gas Line Access Low V oltage Electrical Access Electrical Access D N Low V oltage Access P R S C M 10 CDVT specs 1/06 H Fireplace Dimensions - T op V ent Fig.
6 CDV Series Direct Vent Gas Fireplace 20010175 T op of Unit to Ceiling ............................... 36” (914 mm) Front of Unit to Combustibles .................. 36” (914 mm) Appliance T op .....................................................
7 CDV Series Direct Vent Gas Fireplace 20010175 Noncombustible materials such as brick or tile may be extended over the edges of the face of the fireplace. DO NOT cover any vent or grille panels. If a T rim Kit is going to be installed on the fireplace, the brick or tile will have to be installed flush with the edges of the fireplace.
8 CDV Series Direct Vent Gas Fireplace 20010175 Installation 1. Carefully unwrap the remote wire that is attached to the valve. There are two 1/2” (13 mm) knockouts, one on each side of the outer casing. 2. Remove the knockout desired and insert the plastic snap bushing on the remote wire in the 1/2” hole.
9 CDV Series Direct Vent Gas Fireplace 20010175 The electrical junction box has been fitted standard on this model to allow for the easy connection of an op- tional fan kit. T o connect the electric box to the house electrical sup - ply follow the steps below .
10 CDV Series Direct Vent Gas Fireplace 20010175 V V V V V V V X X X D E B B B C B M B A J K F L VENT TERMINA TION AIR SUPPL Y INLET AREA WHERE TERMINAL IS NOT PERMITTED H I .
1 1 CDV Series Direct Vent Gas Fireplace 20010175 Outside Corner Inside Corner T ermination Clearances T ermination clearances for buildings with combustible and noncombustible exteriors.
12 CDV Series Direct Vent Gas Fireplace 20010175 The vent chart should be read in conjunction with the following vent installation instructions to determine the relationship of the vertical and horizontal dimensions of the vent system. 1. Determine the height of the center of the horizontal vent pipe exiting through the outer wall.
13 CDV Series Direct Vent Gas Fireplace 20010175 T op View Straight V enting Fig. 12 Rear vent applications. 13" (330 mm) Max. FP1598 Rear W all Installation T wist Lock Pipe STEP 1 Locate vent opening on the wall.
14 CDV Series Direct Vent Gas Fireplace 20010175 Rear W all V ent Installations - 45° Flex V ent Pipe NOTE: Under no circumstances can ridged pipe or a rigid 45° elbow be used.
15 CDV Series Direct Vent Gas Fireplace 20010175 Screw Collar Screws FP1605 Fig. 19 Secure collar in place, slide termination into collar . Flex V ent Rear W all V ent Application * Exterior Outside W all 20” - 32” (508 - 813 mm) From Rear of Unit * 1.
16 CDV Series Direct Vent Gas Fireplace 20010175 V584-201 Horizontal Run 2/99 djt 10 ft. (3048 mm) 7 ft. 6 in. (2286 mm) 7 ft. (2134 mm) CFM147 Fig. 23 Maximum vent run with elbows. 90° Elbow = 3 ft. A + B = 17 ft. (Max.) 1 2 3 4 1 + 2 + 3 + 4 = 270 o CFM132 Insert Rear V ent Sidewall 2/26/01 sta CFM132 Fig.
17 CDV Series Direct Vent Gas Fireplace 20010175 STEP 2 Slide venting component on collar of fireplace. Secure component to fireplace by running a screw (self-tap - ping) through tab & into outer casing. (Fig. 26) STEP 3 Measure the horizontal length requirement including a 2” (51 mm) overlap, i.
18 CDV Series Direct Vent Gas Fireplace 20010175 Below Grade Installations When it is not possible to meet the required vent ter- minal clearances of 12” (305 mm) above grade level a snorkel vent kit #7TDVSNORK is required. It allows installation depth of down to 7” (178 mm) below grade level.
19 CDV Series Direct Vent Gas Fireplace 20010175 Example: Maximum horizontal length 0 x 45° elbows = 10’ (3 m) 1 x 45° elbows = 8 ¹⁄₂ ’ (2.6 m) 2 x 45° elbows = 7’ (2.1 m) 3. A minimum of an 8’ vertical rise. 4. T wo sets of 45° elbows offsets within these vertical installations.
20 CDV Series Direct Vent Gas Fireplace 20010175 FP1022 T ypical Straight Up Installation 1/26/00 djt 50’ (15 m) Storm Collar Roof Flash- ing V ent T ermination Roof 2’ Min. Roof Support Attic Insulation Shield Attic Insulation Joists Joists FP1022 Fig.
21 CDV Series Direct Vent Gas Fireplace 20010175 FP1012 T op vent max run 1/25/00 djt 20' (6m) 7.5' (2.3m) Pipe Straps Every 3’ (914mm) Firestop/Zero Clearance Sleeve Pipe Straps Every 3’ (914mm) FP1012 Fig. 39 Support straps for horizontal runs.
22 CDV Series Direct Vent Gas Fireplace 20010175 1 2 3 4 Example: Elbow 1 = 90° Elbow 2 = 45° Elbow 3 = 45° Elbow 4 = 90° T otal angular variation = 270° 1 + 2 + 3 + 4 = 270° FP1239 Fig. 42 Maximum number of elbow degrees. STEP 1 Locate vent opening on the wall.
23 CDV Series Direct Vent Gas Fireplace 20010175 STEP 5 Use appropriate length of pipe sections - telescopic or fixed - and install the horizontal vent sections. The sec- tions which go through the wall are packaged with the starter kit, and can be cut to suit if necessary .
24 CDV Series Direct Vent Gas Fireplace 20010175 BG402a T op V ent Below grade installation 1/26/00 djt Firestop 7” Pipe 7TDVSNORK (Snorkel) 4” (102mm) Clearance Min.
25 CDV Series Direct Vent Gas Fireplace 20010175 1 2 3 4 Max. 8' (2.4m) FP1245 through the roof 90 & 45 degree 12/02 1 + 2 + 3 + 4 = 270° FP1245 Fig. 51 T ypical offset application. V ertical Through-the-Roof Installation 1. Locate your fireplace.
26 CDV Series Direct Vent Gas Fireplace 20010175 If there is a room above ceiling level, firestop spacer must be installed on both the bottom and the top side of the ceiling joists. If an attic is above ceiling level a 7DV AIS (Attic Insulation Shield) must be installed.
27 CDV Series Direct Vent Gas Fireplace 20010175 V enting Components 584G V enting Components Firestop spacer 2/25/99 djt 584H V enting components attic insulation shield 2/25/99 djt 584I vent compone.
28 CDV Series Direct Vent Gas Fireplace 20010175 Only glass approved by CFM Corporation should be used on this fireplace. The top louvre panel is removed by lifting the panel vertically and pulling it away from the appliance. (Fig. 56) The lower access door is removed in the same manner .
29 CDV Series Direct Vent Gas Fireplace 20010175 Logs The 36CDV logs are shipped in place. If a log is bro- ken, refer to the replacement parts list for a replace- ment.
30 CDV Series Direct Vent Gas Fireplace 20010175 3. Open control access panel. 4. Push in gas control knob slightly and turn clock- wise to “OFF”. Do not force. 5. Close control access panel. 1. STOP! Read the safety information above. 2. T urn off all electrical power to the fireplace.
31 CDV Series Direct Vent Gas Fireplace 20010175 Lighting and Operating Instructions For Fireplaces equipped with SIT822 Gas V alve (EN or EP) A. This fireplace is equipped with an ignition device which automatically lights the pilot. DO NOT try to light the pilot by hand.
32 CDV Series Direct Vent Gas Fireplace 20010175 W ARNING: BEFORE DOING ANY GAS CONTROL SERVICE WORK, REMOVE GLASS FRONT . SYMPTOM POSSIBLE CAUSES CORRECTIVE ACTION 1. Spark ignitor will not light A. Defective or misaligned Using a match, light pilot.
33 CDV Series Direct Vent Gas Fireplace 20010175 The conversion of this appliance from one gas to another must be carried out by an authorized service provider . 1. Disconnect power to the unit and shut off the gas sup - ply . 2. Remove window frame assembly .
34 CDV Series Direct Vent Gas Fireplace 20010175 Burner and Burner Compartment It is important to keep the burner and the burner compartment clean. At least once per year the logs and lava rock/ember material should be removed and the burner compartment vacuumed and wiped out.
35 CDV Series Direct Vent Gas Fireplace 20010175 CFM Corporation reserves the right to make changes in design, materials, specifications, prices and discontinue colors and products at any time, without notice. CDV 16 14a,b 13 22 2 6a,b 7 10 1 1 12 15 17 19 21 20 23 24 25 3 8 18 26 1a 1b 1c Ref.
36 CDV Series Direct Vent Gas Fireplace 20010175 CDV (continued) 15. Flexible Gas Line w/ON/Off Shut-Of f V alve 20002500 16. Fan Assy (FK12 Option) ZA1 1 10 17. Electrical Cord (6 ft.) 51865 18. Door Assy 20010207 19. Glass w/Gasket 10010206 20. Gasket Glass 10000992 21.
37 CDV Series Direct Vent Gas Fireplace 20010175 FK12 This auxiliary fan system increases the efficiency of the circulation of the heating air . The FK12 Fan Assembly is a fixed speed fan system and does not allow for variable speed control. Specifications 1 15 V olts / 60 Hz / 56 W atts.
38 CDV Series Direct Vent Gas Fireplace 20010175.
39 CDV Series Direct Vent Gas Fireplace 20010175 BASIC W ARRANTY CFM Corporation (hereinafter referred to collectively as the Company) warrants that your new V ermont Castings or Majestic Gas Fireplac.
2695 Meadowvale Blvd. • Mississauga, Ontario, Canada L5N 8A3 800-668-5323 • www .cfmcorp.com CFM Corporation Efficiency Ratings Model EnerGuide Ratings Steady State (%) D.O.E. Fireplace Efficiency (%) Fan-OFF Fan-ON (AFUE%) 36CDVRRN 66.9 76 76.5 63 36CDVRRP 66.
Een belangrijk punt na aankoop van elk apparaat Vermont Casting 36CDVRRN (of zelfs voordat je het koopt) is om de handleiding te lezen. Dit moeten wij doen vanwege een paar simpele redenen:
Als u nog geen Vermont Casting 36CDVRRN heb gekocht dan nu is een goed moment om kennis te maken met de basisgegevens van het product. Eerst kijk dan naar de eerste pagina\'s van de handleiding, die je hierboven vindt. Je moet daar de belangrijkste technische gegevens Vermont Casting 36CDVRRN vinden. Op dit manier kan je controleren of het apparaat aan jouw behoeften voldoet. Op de volgende pagina's van de handleiding Vermont Casting 36CDVRRN leer je over alle kenmerken van het product en krijg je informatie over de werking. De informatie die je over Vermont Casting 36CDVRRN krijgt, zal je zeker helpen om een besluit over de aankoop te nemen.
In een situatie waarin je al een beziter van Vermont Casting 36CDVRRN bent, maar toch heb je de instructies niet gelezen, moet je het doen voor de hierboven beschreven redenen. Je zult dan weten of je goed de alle beschikbare functies heb gebruikt, en of je fouten heb gemaakt die het leven van de Vermont Casting 36CDVRRN kunnen verkorten.
Maar de belangrijkste taak van de handleiding is om de gebruiker bij het oplossen van problemen te helpen met Vermont Casting 36CDVRRN . Bijna altijd, zal je daar het vinden Troubleshooting met de meest voorkomende storingen en defecten #MANUAl# samen met de instructies over hun opplosinge. Zelfs als je zelf niet kan om het probleem op te lossen, zal de instructie je de weg wijzen naar verdere andere procedure, bijv. door contact met de klantenservice of het dichtstbijzijnde servicecentrum.