TECHNICAL GUIDE SPLIT -SYSTEM A IR CONDITIONERS 13 SEER – R-22 MODELS: H*RD018 THRU 060 (1.5 THRU 5 NOMINAL TONS, 1 PHASE) H*RD036 THRU 060 (2.5 THRU 5 NOMINAL TONS, 3 PHASE) Due to continuous produc t impr ovement, specifications are subject to change without notice.
254892-YTG-C-0606 2 Unitary Products Group All dimensions are in inches. They a re subject to change without notice. Ce rtif ied dimensio ns will be provide d upon request.
254892-YTG-C-0606 Unitary Products Group 3 Additional R-22 Charge / Orifice Size for V arious Ma tched Systems - 1 Phase Outdoor Unit H2RD018S06 H2RD024S06 H2RD030S06 H2RD036S06 H2RD042S06 H2RD048S06 .
254892-YTG-C-0606 4 Unitary Products Group H C 1 8 A 3 X 0 2 B + 1 ––––– H C 3 0 A 3 X – 2 A + 0 0 –––– HC36B3X – – 0 0 – – – H C 4 2 C 3 X ––––0 0 – H C 6 0 C .
254892-YTG-C-0606 Unitary Products Group 5 PROCEDURES: 1. U nit factory charge listed on the unit nameplate includes refr igerant for the condenser , the smallest evaporator and for 15 feet of inter- connecting line tubing. 2. Verify the TXV and additional charge required for specific evaporator coil in the system using the above table.
254892-YTG-C-0606 6 Unitary Products Group All dimensions are in inches. They a re subject to change without notice. Ce rtif ied dimensio ns will be provide d upon request.
254892-YTG-C-0606 Unitary Products Group 7 Additional R-22 Charge / Orifice Size for V arious Ma tched Systems - 3 Phase Outdoor Unit H1RD030S(25,46) H1RD036S(25,46) H1RD042S(25,46) H1RD048S(25, 46) H.
254892-YTG-C-0606 8 Unitary Products Group PROCEDURES: 1. U nit factory charge listed on the unit nameplate include s refr iger ant for the condenser , the smallest evaporator and for 15 feet of inter- connecting line tubing. 2. Verify the TXV and additional charge required for specific evaporator coil in the system using the above table.
254892-YTG-C-0606 Unitary Products Group 9 COOLING CAP ACITY - With Air Handler Coils UNIT MODEL AIR HANDLER COIL MODEL 1 COOLING MODEL ELECTRIC HEA T KW 2 W RA TED CFM NET MBH SEER EER TOT AL SENS. 1 & 3 PH 13 SEER AC WITH MA H2RD018S06 MA08B 2,5,8 17 FC/MC18B 600 17.
254892-YTG-C-0606 10 Unitary Products Group — = Not applicable. 1 PH 13 SEER AC WITH A V / SV - V ARIABLE SPEED H2RD018S06 A V24 2,5,8,10,15 17 – 600 18.0 1 1.7 14.00 1 1.50 H2RD024S06 A V24 2,5,8,10,15 17 – 800 23.2 16.5 14.00 1 1.50 H2RD030S06 A V36 5,8,10,15,18 21 – 1000 30.
254892-YTG-C-0606 Unitary Products Group 11 COOLING CAP ACITY - Up flow , Downflow & Horizont al Furnaces and Coils UNIT MODEL F URNACE** COIL MODEL COOLING CFM RANGE (MIN.-MAX.) W RA TED CFM NET MBH SEER 1 EER TOT AL SENS. H2RD018S06 450 750 14,17 FC/MC/PC/UC18 600 17.
254892-YTG-C-0606 12 Unitary Products Group H2RD042S06 1200 1600 17,21 FC/MC/PC/UC42 1400 40.5 29.6 13.00 1 1.00 21,24 FC/MC/PC/UC48 1400 41.0 30.2 13.00 1 1.00 17 G*F A042S17 1400 40.5 29.6 13.00 1 1.00 21 G*F A048S21 1400 41.0 29.6 13.00 1 1.00 21 G*FD042H21 1400 40.
254892-YTG-C-0606 Unitary Products Group 13 COOLING CAP ACITY - With V ariable Speed Furnaces UNIT MODEL V ARIABLE SPEED FURNACE MODEL COIL MODEL 1 W COOLING RA TED CFM NET MBH SEER EER T OTAL SENS. 1 PH 13 SEER AC WITH V ARIABLE SPEED FURNACES 2 H2RD018S06 PV8*A12 FC/MC/PC18A 14 600 17.
254892-YTG-C-0606 14 Unitary Products Group H2RD036S06 PV8*A12 FC/MC/PC36A 14 1200 35.0 25.4 13.00 1 1.00 PV8*B16 FC/MC/PC36B 17 1200 35.2 25.6 13.75 1 1.00 PV8*C16 FC/MC/PC36C 21 1200 35.2 25.6 14.00 1 1.50 PV8*C20 FC/MC/PC36C 21 1200 35.2 25.6 14.00 1 1.
254892-YTG-C-0606 Unitary Products Group 15 H2RD048S06 PV8*C16 FC/MC/PC48C 21 1500 46.5 34.2 13.00 1 1.00 PV8*C20 FC/MC/PC48C 21 1600 47.0 35.2 13.00 1 1.00 P(C,V)9*C16 FC/MC/PC48C 21 1600 47.0 35.2 13.00 1 1.00 P(C,V)9*C20 FC/MC/PC48C 21 1600 47.0 35.
254892-YTG-C-0606 16 Unitary Products Group ACCESSORIES Refer to Price Manual for specific model numbers. HARD ST ART KIT - Provides increased starting torque for areas with low voltage. COMPRESSOR BLANKET - Designed to furth er reduce the normal compressor operating sound.
254892-YTG-C-0606 Unitary Products Group 17 Multipliers for determining the performance with other indoor sections . NOTE: For dry bulb temperatures dif ferent than t hose liste d (between 73-87 F), s.
254892-YTG-C-0606 18 Unitary Products Group Multipliers for determining the p erfo rman ce with other indoor sections. NOTE: For dry bulb temperatures dif ferent than those liste d (bet ween 73-87 F),.
254892-YTG-C-0606 Unitary Products Group 19 Multipliers for determining the performance with other indoor sections . NOTE: For dry bulb temperatures dif ferent than t hose liste d (between 73-87 F), s.
254892-YTG-C-0606 20 Unitary Products Group Multipliers for determining the p erfo rman ce with other indoor sections. NOTE: For dry bulb temperatures dif ferent than those liste d (bet ween 73-87 F),.
254892-YTG-C-0606 Unitary Products Group 21 Multipliers for determining the performance with other indoor sections . NOTE: For dry bulb temperatures dif ferent than t hose liste d (between 73-87 F), s.
254892-YTG-C-0606 22 Unitary Products Group Multipliers for determining the p erfo rman ce with other indoor sections. NOTE: For dry bulb temperatures dif ferent than those liste d (bet ween 73-87 F),.
254892-YTG-C-0606 Unitary Products Group 23 Multipliers for determining the performance with other indoor sections . NOTE: For dry bulb temperatures dif ferent than t hose liste d (between 73-87 F), s.
Subject to change without notice. Printe d in U .S.A. 254892-YTG-C-0606 Copyright © by York International Corp. 2006. All right s reserved. Supersedes: 254892 / 036-21339-002 Rev.
Een belangrijk punt na aankoop van elk apparaat York H*RD036 THRU 060 (of zelfs voordat je het koopt) is om de handleiding te lezen. Dit moeten wij doen vanwege een paar simpele redenen:
Als u nog geen York H*RD036 THRU 060 heb gekocht dan nu is een goed moment om kennis te maken met de basisgegevens van het product. Eerst kijk dan naar de eerste pagina\'s van de handleiding, die je hierboven vindt. Je moet daar de belangrijkste technische gegevens York H*RD036 THRU 060 vinden. Op dit manier kan je controleren of het apparaat aan jouw behoeften voldoet. Op de volgende pagina's van de handleiding York H*RD036 THRU 060 leer je over alle kenmerken van het product en krijg je informatie over de werking. De informatie die je over York H*RD036 THRU 060 krijgt, zal je zeker helpen om een besluit over de aankoop te nemen.
In een situatie waarin je al een beziter van York H*RD036 THRU 060 bent, maar toch heb je de instructies niet gelezen, moet je het doen voor de hierboven beschreven redenen. Je zult dan weten of je goed de alle beschikbare functies heb gebruikt, en of je fouten heb gemaakt die het leven van de York H*RD036 THRU 060 kunnen verkorten.
Maar de belangrijkste taak van de handleiding is om de gebruiker bij het oplossen van problemen te helpen met York H*RD036 THRU 060 . Bijna altijd, zal je daar het vinden Troubleshooting met de meest voorkomende storingen en defecten #MANUAl# samen met de instructies over hun opplosinge. Zelfs als je zelf niet kan om het probleem op te lossen, zal de instructie je de weg wijzen naar verdere andere procedure, bijv. door contact met de klantenservice of het dichtstbijzijnde servicecentrum.