Gebruiksaanwijzing /service van het product H1CE150 van de fabrikant York
Ga naar pagina of 16
GENERAL These condensing units are designed for outdoor installation on a roof or at ground level. Every unit is completely piped and wired at the factory and is shipped ready for immediate installa- tion.
035-15407-002-B-0404 2 Unitary Products Group General ................................................................................ 1 Reference ............................................................................ 1 Inspection ..............
LIMIT ATIONS These units must be installed in accordance with all national and local safety codes. If no local codes apply , installation must conform with the appropriate national codes. See T able 1 for Unit Application Data. Units are designed to meet National Safety Code Standards.
CLEARANCES All units require certain minimum clearances for proper opera- tion and service. Refer to Figure 4 for these clearances. WARNING: Do not permit overhanging structures or shrubs to obstruct condenser air discharge. Additional height may be required for snow clearance if winter operation is expected.
035-15407-002-B-0404 Unitary Products Group 5 Model HCE V oltage Code Compressor Condenser Fan Motor Unit Ampacity (Amps) Max. Fuse Size 1 (Amps) Power Supply RLA LRA Power Supply HP Qty . FLA 090 25 208/230-3-60 25.6 190 208/230-1-60 3/4 1 3.03 35.1 60 46 460-3-60 12.
035-15407-002-B-0404 6 Unitary Products Group FIG. 5 - UNIT DIMENSIONS AND CLEARANCES A I R O U T A I R I N 4- 5/ 8 ( 118) 2 5 - 3 / 4 ( 6 5 5 ) 1 0 - 1 / 8 ( 2 5 8 ) 2 - 1 / 2 ( 6 . 4 ) 4 - 1 / 2 ( 115) G U A G E L I N E A C C E S S 1 - 1 / 8 " ( 2 8 .
REFRIGERANT PIPING GENERAL GUIDELINES Many service problems can be avoided by taking adequate precautions to provide an internally clean and dry system and by using procedures and materials that conform with estab- lished standards. Use hard drawn copper tubing where no appreciable amount of bending around pipes or other obstructions is necessary .
035-15407-002-B-0404 8 Unitary Products Group NOTE: Add the operating charge of the condensing unit, the evaporator coil and the refrigerant lines to determine the total refrigerant charge of the system. 1 Charges are based on 40 ° F suction temperature and a 105 ° F liquid temperature.
EXTENDING THE SERVICE PORTS (Refer to Fig 7.) 1. Loosen the screws securing the service ports in shipping position. 2. Push the service ports through the corner post.
10. After the disc has been removed, burnish the external sur - faces and clean the internal surfaces as outlined above. The suction piping can now be brazed to the suction connection on the evaporator coil while maintaining a minimum flow of dry nitrogen.
035-15407-002-B-0404 Unitary Products Group 11 FIG. 7 - EXTENDING THE SERVICE PORTS.
035-15407-002-B-0404 12 Unitary Products Group FIG. 8 - CHARGING CURVE HCE090 FIG. 9 - CHARGING CURVE HCE120.
035-15407-002-B-0404 Unitary Products Group 13 FIG. 10 - CHARGING CURVE HCE150.
UNIT OPERATION - 7-1/2, 10 & 12-1/2 TON When the external control calls for cooling at terminal Y1: 1. The system controller (SC) is energized. The system con - troller starts the compressors and enables the condenser fans by energizing contactor 1M (and 2M on the 12-1/2 ton, 208/230 volt models).
If the unit continues to be shut down by one of its safety con - trols, service should be called to determine the cause of the problem. Repeatedly resetting the lockout circuit may damage the unit. The following accessories are available to provide low am - bient operation to 0 ° F.
Unitary Products Group 5005 Y ork Drive, Norman, Oklahoma 73069 Subject to change without notice. Printed in U.S.A Copyright © 2004 by Y ork International Corporation.
Een belangrijk punt na aankoop van elk apparaat York H1CE150 (of zelfs voordat je het koopt) is om de handleiding te lezen. Dit moeten wij doen vanwege een paar simpele redenen:
Als u nog geen York H1CE150 heb gekocht dan nu is een goed moment om kennis te maken met de basisgegevens van het product. Eerst kijk dan naar de eerste pagina\'s van de handleiding, die je hierboven vindt. Je moet daar de belangrijkste technische gegevens York H1CE150 vinden. Op dit manier kan je controleren of het apparaat aan jouw behoeften voldoet. Op de volgende pagina's van de handleiding York H1CE150 leer je over alle kenmerken van het product en krijg je informatie over de werking. De informatie die je over York H1CE150 krijgt, zal je zeker helpen om een besluit over de aankoop te nemen.
In een situatie waarin je al een beziter van York H1CE150 bent, maar toch heb je de instructies niet gelezen, moet je het doen voor de hierboven beschreven redenen. Je zult dan weten of je goed de alle beschikbare functies heb gebruikt, en of je fouten heb gemaakt die het leven van de York H1CE150 kunnen verkorten.
Maar de belangrijkste taak van de handleiding is om de gebruiker bij het oplossen van problemen te helpen met York H1CE150 . Bijna altijd, zal je daar het vinden Troubleshooting met de meest voorkomende storingen en defecten #MANUAl# samen met de instructies over hun opplosinge. Zelfs als je zelf niet kan om het probleem op te lossen, zal de instructie je de weg wijzen naar verdere andere procedure, bijv. door contact met de klantenservice of het dichtstbijzijnde servicecentrum.