TECHNICAL GUIDE AFFINITY SPLIT -SYSTEM HEA T PUMPS 18 SEER – R-410A MODELS: YZH024 THRU 060 (2 THRU 5 NOMINAL TONS) Due to continuous pr oduct improvement, spec ifications are subject to change without notice. Visit us on the web at www .york.com Additional rati ng information can be foun d at www .
2 Unitary Products Group 345094-YTG-D-0108 All dimensions are in inches. They are subject to change without notice. Certified dimensions wil l be provided upon request.
Unitary Products Group 3 345094-YTG-D-0108 PROCEDURES: 1. Unit factory charge listed on the unit nameplate includes refri gerant for the condenser , the smallest evaporator and 15 feet of intercon- necting line tubing. 2. V erify the TXV and additional charge requ ired for specific evaporator coil in th e system using the above table.
4 Unitary Products Group 345094-YTG-D-0108 COOLING CAP ACITY - With A ir Handler Coils UNIT MODEL AIR HANDLER COIL 1 MODEL COOLING MODEL W ST AGE RA TED CFM NET MBH SEER EER TOT AL SENSIBLE 18 SEER HP WITH MV - V ARIABLE SPEED YZH0241 1 MV12B 17 FC/MC43B 1 645 18.
Unitary Products Group 5 345094-YTG-D-0108 COOLING CAP ACITY - With V a riable Speed Furnaces UNIT MODEL V ARIABLE SPEED FURNACE MODEL COIL MODEL 1 W COOLING ST AGE RA TED CFM NET MBH SEER EER TOT AL SENSIBLE YZH0241 1 P(C,V)9*B12 FC/MC/PC43B 17 1 560 18.
6 Unitary Products Group 345094-YTG-D-0108 YZH0481 1 P(C,V)8*C16 FC/MC/PC48C 21 1 880 33.0 23.4 16.3O 13.30 2 1500 46.0 34.6 1 1.70 P(C,V)8*C20 FC/MC/PC48C 21 1 1030 33.0 25.0 16.4O 13.40 2 1610 46.5 35.4 1 1.80 P(C,V)9*C16 FC/MC/PC48C 21 1 1090 34.0 26.
Unitary Products Group 7 345094-YTG-D-0108 ** Refer to Quick Selection Chart for specific furnace match-up. HEA TING CAP ACITY - With Air Handler UNIT MODEL AIR HANDLER MODEL COIL 1 MODEL W HEA TING ST AGE RA TED CFM NET MBH HSPF COP @ 47 47 OD 17 O D 18 SEER HP WITH MV - V ARIABLE SPEED YZH0241 1 MV12B FC/MC43B 17 1 645 19.
8 Unitary Products Group 345094-YTG-D-0108 HEA TING CAP ACITY - With V a riable Speed F urnaces UNIT MODEL V ARIABLE SPEED FURNACE MODEL COIL MODEL 1 W HEA TING ST AGE RA TED CFM NET MBH HSPF COP @ 47 47 OD 17 OD YZH0241 1 P(C,V)9*B12 FC/MC/PC43B 17 1 560 19.
Unitary Products Group 9 345094-YTG-D-0108 YZH0361 1 P(C,V)8*C20 FC/MC62D 24 1 780 26.4 - - 4.00 2 1200 36.0 26.2 9.55 4 .20 2 780 36.0 23.8 9.35 3.20 P(C,V)9*C20 FC/MC62D 24 1 790 26.4 - - 4.00 2 1 195 36.0 26.0 9.55 4.20 2 790 36.0 24.0 9.35 3.40 P(C,V)9*D20 FC/MC62D 24 1 775 26.
10 Unitary Products Group 345094-YTG-D-0108 YZH0481 1 P(C,V)9*D20 FC/MC/PC60D 24 1 985 36.0 - - 3.80 2 1560 48.0 32.6 9.8 4. 00 2 985 39.0 25.6 9.5 3. 20 P(C,V)8*C20 FC/MC62D 24 1 1030 36.0 - - 3.80 2 1610 48.0 32.8 9.8 4. 00 2 1030 38.5 25.2 9.5 3. 20 P(C,V)9*C20 FC/MC62D 24 1 1010 36.
Unitary Products Group 11 345094-YTG-D-0108 ACCESSORIES* TXV Kits - 1 TVM9 series thermal expansion valves precisely meter refrigerant for optimu m performance. Bonnet Sensor (2SB1370012 4) - The bonnet sensor is used to sense plenum temperature, and is optional with a gas or oil back-up heat source.
12 Unitary Products Group 345094-YTG-D-0108 Multipliers for determining th e performance with other indoor sec tions . NOTE: For dry bulb temperatures dif f erent than those listed (bet ween 73-87 F),.
Unitary Products Group 13 345094-YTG-D-0108 Multipliers for determining the performance with ot her indoor sections. NOTE: For dry bulb temperatures dif ferent than those listed (bet ween 73-87 F), se.
14 Unitary Products Group 345094-YTG-D-0108 Multipliers for determining th e performance with other indoor sec tions . NOTE: For dry bulb temperatures dif f erent than those listed (bet ween 73-87 F),.
Unitary Products Group 15 345094-YTG-D-0108 Multipliers for determining the performance with ot her indoor sections. NOTE: For dry bulb temperatures dif ferent than those listed (bet ween 73-87 F), se.
16 Unitary Products Group 345094-YTG-D-0108 Multipliers for determining th e performance with other indoor sec tions . NOTE: For dry bulb temperatures dif f erent than those listed (bet ween 73-87 F),.
Unitary Products Group 17 345094-YTG-D-0108 Multipliers for determining the performance with ot her indoor sections. NOTE: For dry bulb temperatures dif ferent than those listed (bet ween 73-87 F), se.
18 Unitary Products Group 345094-YTG-D-0108 Multipliers for determining th e performance with other indoor sec tions . NOTE: For dry bulb temperatures dif f erent than those listed (bet ween 73-87 F),.
Unitary Products Group 19 345094-YTG-D-0108 Multipliers for determining the performance with ot her indoor sections. NOTE: For dry bulb temperatures dif ferent than those listed (bet ween 73-87 F), se.
20 Unitary Products Group 345094-YTG-D-0108 Multipliers for determining the perfo rman ce with other indoor section. NOTE: KW RA TING IS FOR OUT DOOR AND INDOOR UNITS. LOW CFM HEA TING PERFORMA NCE DA T A - LOW CFM 1-ST AGE OPERA TION OUTDOOR UNIT MODEL NO.
Unitary Products Group 21 345094-YTG-D-0108 Multipliers for de termining the performa nce with other i ndoor section. NOTE: KW RA TING IS FOR OU TDOOR AND INDOOR UNITS. HIGH CFM HEA TIN G PERFOR MA NCE DA T A - HIGH CFM 2-ST AGE OPERA TION OUTDOOR UNIT MODEL NO.
22 Unitary Products Group 345094-YTG-D-0108 Multipliers for determining th e performance with other indoor sec tions . NOTE: KW RA TING IS FOR OUT DOOR AND INDOOR UNITS. LOW CFM HEA TING PERFORMA NCE DA T A - LOW CFM 1-ST AGE OPERA TION OUTDOOR UNIT MODEL NO.
Unitary Products Group 23 345094-YTG-D-0108 Multipliers for de termining the performa nce with other i ndoor sections. NOTE: KW RA TING IS FOR OU TDOOR AND INDOOR UNITS. HIGH CFM HEA TIN G PERFOR MA NCE DA T A - HIGH CFM 2-ST AGE OPERA TION OUTDOOR UNIT MODEL NO.
24 Unitary Products Group 345094-YTG-D-0108 Multipliers for determining the perfo rman ce with other indoor sections. NOTE: KW RA TING IS FOR OUT DOOR AND INDOOR UNITS. LOW CFM HEA TING PERFORMA NCE DA T A - LOW CFM 1-ST AGE OPERA TION OUTDOOR UNIT MODEL NO.
Unitary Products Group 25 345094-YTG-D-0108 Multipliers for de termining the performa nce with other i ndoor sections. NOTE: KW RA TING IS FOR OU TDOOR AND INDOOR UNITS. HIGH CFM HEA TIN G PERFOR MA NCE DA T A - HIGH CFM 2-ST AGE OPERA TION OUTDOOR UNIT MODEL NO.
26 Unitary Products Group 345094-YTG-D-0108 Multipliers for determining the perfo rman ce with other indoor sections. NOTE: KW RA TING IS FOR OUT DOOR AND INDOOR UNITS. LOW CFM HEA TING PERFORMA NCE DA T A - LOW CFM 1-ST AGE OPERA TION OUTDOOR UNIT MODEL NO.
Unitary Products Group 27 345094-YTG-D-0108 Multipliers for de termining the performa nce with other i ndoor sections. NOTE: KW RA TING IS FOR OU TDOOR AND INDOOR UNITS. HIGH CFM HEA TIN G PERFOR MA NCE DA T A - HIGH CFM 2-ST AGE OPERA TION OUTDOOR UNIT MODEL NO.
Subject to change without notice. Printe d in U.S.A. 345094-YTG-D-0108 Copyright © by Unitary Products Gr oup 2008. All ri ghts reserved. Supersedes: 345094-YTG-C-1007 Unitary 5005 Norman Product s Y.
Een belangrijk punt na aankoop van elk apparaat York YZH024 THRU 060 (of zelfs voordat je het koopt) is om de handleiding te lezen. Dit moeten wij doen vanwege een paar simpele redenen:
Als u nog geen York YZH024 THRU 060 heb gekocht dan nu is een goed moment om kennis te maken met de basisgegevens van het product. Eerst kijk dan naar de eerste pagina\'s van de handleiding, die je hierboven vindt. Je moet daar de belangrijkste technische gegevens York YZH024 THRU 060 vinden. Op dit manier kan je controleren of het apparaat aan jouw behoeften voldoet. Op de volgende pagina's van de handleiding York YZH024 THRU 060 leer je over alle kenmerken van het product en krijg je informatie over de werking. De informatie die je over York YZH024 THRU 060 krijgt, zal je zeker helpen om een besluit over de aankoop te nemen.
In een situatie waarin je al een beziter van York YZH024 THRU 060 bent, maar toch heb je de instructies niet gelezen, moet je het doen voor de hierboven beschreven redenen. Je zult dan weten of je goed de alle beschikbare functies heb gebruikt, en of je fouten heb gemaakt die het leven van de York YZH024 THRU 060 kunnen verkorten.
Maar de belangrijkste taak van de handleiding is om de gebruiker bij het oplossen van problemen te helpen met York YZH024 THRU 060 . Bijna altijd, zal je daar het vinden Troubleshooting met de meest voorkomende storingen en defecten #MANUAl# samen met de instructies over hun opplosinge. Zelfs als je zelf niet kan om het probleem op te lossen, zal de instructie je de weg wijzen naar verdere andere procedure, bijv. door contact met de klantenservice of het dichtstbijzijnde servicecentrum.