Form 2143 Date: 4/3/03 Repl: 2/1/99 BR Y AN STEAM LLC Inst allation and Operating Service Manual BOILER FEED SYSTEM 0.
INSTALLATION AND OPERAT ION SERVICE MANUAL BOILER FEED SYSTEM Bryan Steam LLC 783 North Chili Avenue * Peru, IN 46970 Phone 765.473.6651 • Fax 765.473.
MODEL IDENTIFICATION & DESIGNATION Boiler F eed System A – H - FS – 15 – 12 – 50 – D A = LINING BLANK – NO LINING A – APEXIOR LINING B – GALVANIZED LINING H = TANK POSITION H – H.
T a ble of Contents SECTION 1 – INSTALLATION INSTRUCTIONS 1.1 FOUNDAT ION ......................................................................................................... 1 1.2 CLE ARANCE ....................................................
BOILER FEED SYSTEM DATE: 4/3/03 REP:2/1/99 1 Sectio n 1 Installa tion Instr uctions – Boiler F eed System Note: Please read the entire instruction manual before attempting installation. Insurance and local or state regulatory codes may contain additional or more stringent requirements than those contained in this manual.
BOILER FEED SYSTEM DATE: 4/3/03 REP:2/1/99 2 feed system near its permanent location. Before in stallation, take inventory of items that were shipped loose so they will not be misplaced. 1.4 BOILER FEED SY STEM CONNECTIONS 1.4.1 GENERAL Maintain clearances as shown on the dimensional drawing for servicing and as referenced in N.
BOILER FEED SYSTEM DATE: 4/3/03 REP:2/1/99 3 1.4.5 OVERFLOW CONNECTION The overflow connection should be piped to an approved drain for gravity flow of any water that may reach that level in the tank. The purpose of the overflow connection is to keep the tank from being flooded in case a high level condition occurs in the unit.
BOILER FEED SYSTEM DATE: 4/3/03 REP:2/1/99 4 1.5.2 MAKE UP FILL VALVE A self-contained mechanical float type make up water control is proved to accept incoming water up to a differential pressure of 70 psi (see manufacturer’s date for exact pressures).
BOILER FEED SYSTEM DATE: 4/3/03 REP:2/1/99 5 1.6 PR OCEDURE T O BE FOLL O WED BEFORE PLA CING BOILER FEED SY STEM IN OPERA TION 1.6.1 CLEANING THE FEED SYSTEM After installation is complete, the feed system should be checked for debris. Any debris found in the tank, pump, or strainers should be removed before start-up.
BOILER FEED SYSTEM DATE: 4/3/03 REP:2/1/99 6 Sectio n 2 ST AR T -UP AND OPERA TION – BOILER FEED SY STEM WARNING: IMPROPER SERVICING AND START-UP OF THIS EQUIPMENT MAY CREATE A POTENTIAL HAZARD TO EQUIPMENT AND TO OPERATORS OR PERSONS IN THE BUILDING.
BOILER FEED SYSTEM DATE: 4/3/03 REP:2/1/99 7 2.1.2 ATMOSPHERIC TANK DESIGN This tank was designed to be used only in atmospheric conditions. To avoid potential hazards, this tank should never be pressurized. Safety precautions should be taken to make sure the tank is never pressurized.
BOILER FEED SYSTEM DATE: 4/3/03 REP:2/1/99 8 2.2 OPERA TING INSTRUCTIONS CAUTION: Check all electrical terminals and piping connections for tightness before start-up.
BOILER FEED SYSTEM DATE: 4/3/03 REP:2/1/99 9 Sectio n 3 CARE AND MAINTENANCE BOILER FEED SY STEMS 3.1 REQUIRED PRECA UTIONS DURING TEMPORAR Y USE 3.1.1 GENERAL A boiler system is often utilized in new construction to assist in curing of building components or to provide temporary heat or for other purposes.
BOILER FEED SYSTEM DATE: 4/3/03 REP:2/1/99 10 6. Considerations of warranty should the boiler system be used for temporary heat without adherence to the recommended start-up and operating procedures outlined in the instruction manuals.
BOILER FEED SYSTEM DATE: 4/3/03 REP:2/1/99 11 FILTRATION For some old systems, there is a reluctance to clean the piping because of the possibility of leaks occurring in badly corroded lines. Should the customer refuse cleaning, it is necessary to install filtration equipment.
BOILER FEED SYSTEM DATE: 4/3/03 REP:2/1/99 12 3.6 SUGGESTED MAINTENANCE SCHEDULE DAILY Make visual inspection of gauges, monitors, and indicators and record readings in boiler system log. Make visual check of instrument and equipment settings against factory recommended specifications.
BOILER FEED SYSTEM DATE: 4/3/03 REP:2/1/99 13 Idle boilers are vulnerable to attack when air contacts untreated wet metal surfaces. To prevent corrosion, the metal must be protected by either keeping the surfaces completely dry or by excluding air from the system.
Een belangrijk punt na aankoop van elk apparaat Bryan Boilers AH-FS151250D (of zelfs voordat je het koopt) is om de handleiding te lezen. Dit moeten wij doen vanwege een paar simpele redenen:
Als u nog geen Bryan Boilers AH-FS151250D heb gekocht dan nu is een goed moment om kennis te maken met de basisgegevens van het product. Eerst kijk dan naar de eerste pagina\'s van de handleiding, die je hierboven vindt. Je moet daar de belangrijkste technische gegevens Bryan Boilers AH-FS151250D vinden. Op dit manier kan je controleren of het apparaat aan jouw behoeften voldoet. Op de volgende pagina's van de handleiding Bryan Boilers AH-FS151250D leer je over alle kenmerken van het product en krijg je informatie over de werking. De informatie die je over Bryan Boilers AH-FS151250D krijgt, zal je zeker helpen om een besluit over de aankoop te nemen.
In een situatie waarin je al een beziter van Bryan Boilers AH-FS151250D bent, maar toch heb je de instructies niet gelezen, moet je het doen voor de hierboven beschreven redenen. Je zult dan weten of je goed de alle beschikbare functies heb gebruikt, en of je fouten heb gemaakt die het leven van de Bryan Boilers AH-FS151250D kunnen verkorten.
Maar de belangrijkste taak van de handleiding is om de gebruiker bij het oplossen van problemen te helpen met Bryan Boilers AH-FS151250D . Bijna altijd, zal je daar het vinden Troubleshooting met de meest voorkomende storingen en defecten #MANUAl# samen met de instructies over hun opplosinge. Zelfs als je zelf niet kan om het probleem op te lossen, zal de instructie je de weg wijzen naar verdere andere procedure, bijv. door contact met de klantenservice of het dichtstbijzijnde servicecentrum.