Gebruiksaanwijzing /service van het product 4-WAY MULTIPOISE 359AAV van de fabrikant Bryant
Ga naar pagina of 44
1 359AA V DIRECT OR NON - - DIRECT VENT 4- -W A Y M U L TI P O I S E CONDENSING GAS FURNACE Installation Instructions SPECIAL VENTING REQUIREMENTS FOR INST ALLA TIONS IN CANADA Installation in Canada must confor m to the requirements of CSA B149 code.
2 Required Notice for Massachusetts Installations IMPOR T ANT The Commonwealth of Massachusetts r equires compliance with regulation 248 CMR as follows: 5.08: Modifications to NFP A- - 54, Chapter 10 2) Revise 10.8.3 by adding the follo wing additional requirements: a.
3 NOTE : Read the entire instruction manual before starting the installation. NOTE : Please retain these instructions with the furnace after installation for future reference. SAFETY CONSIDERA TIONS FURNACE RELIABILITY HAZARD Failure to follow this warning could result in personal injury , death or property damage.
4 SAFE INST ALLA TION REQUIREMENTS FIRE, EXPLOSION, AND ASPHYXIA TION HAZARD Failure to follow this warning could result in personal injury or death. Improper adjustment, alteration, service, maintenance or installation could cause persona l injury , death and/or property damage.
5 Frozen W ater Pipe Hazard W A TER DAMAGE T O PROPERT Y HAZARD Failure to follow this caution m ay result in property damage. Do not leave your home unattended for long periods during freezing weather without turning off water supply and draining water pipes or otherwise protecting against the risk of frozen pipes and resultant damage.
6 V ent Pipes MUST be supported Horizontally and V er tically *8 ″ (203.2mm) Min. 20 ′ (6.1m) Max. in same atmospheric zone *8 ″ (203.2mm) Min. 20 ′ (6.1m) Max. in same atmospheric zone Coupling on ends of exhaust pipe. T otal pipe & c oupling out- side structure = 8 ″ (203.
7 Furnace Installation Considerations The installation of the furnace for a given application will dictate the position of the furnace, the airflow , ductwork connections, vent and combustion air piping.
8 AIR INT AKE VENT H G E F TOP AIR INT AKE (KO) (AL TERNA TE) LEFT SIDE VENT 7 2 1 / 4 6 11 / 16 1 1 / 4 ELECTRICAL 4 13 / 16 1 1 / 16 1 11 / 16 17 5 / 16 24 1 / 16 19 13 / 16 28 3 / 4 29 7 / 8 TRAP (.
9 Minimum One Inlet an d One Outlet Air Sup ply is Required M a yb ei na n yC o m b i n a t i o nS h o w n Inlet Air Opening Must be Within1 2 in. (304.
10 d. V ertical duct openings or openings directly communic- ating with the outdoors require 1 squar e inch of free area per 4,000 BTUH (5.5 cm 2 /kW) for combined in- put of all gas appliances in the space ( see Ta b l e 1 ) . 3. When one permanent outdoor opening is used, the opening requires: a.
11 T able 2 – Minimum Space V olume for 100% Combustion and V entilation Air fr om Indoors - - Ft 3 (M 3 ) Other Than Fan - - - Assisted T otal (1,000 Btuh) Fa n - - - assisted T otal (1,000’s Btuh) ACH 30 40 50 50 75 100 125 0.60 1,050 (29.7) 1,400 (39.
12 good judgement of the installer . Manufacturer does NOT take responsibility for modifications made to existing equipment. CARBON MONOXIDE POISONING HAZARD Failure to follow the steps outlined below.
13 Applicable ASTM Standards for V ent Mate rials Materials Sch. 40 Pipe SDR Pipe Cell Core Pipe Fittings Primer Solvent Cement ABS D1527 __ F628 D2468 & D2661 --- --- D2235 PVC D1785 D2241 F891 D2466 & D2665 F656 D2564 CPVC F441 F442 --- --- F438 --- --- F493 ABS to PVC --- --- --- --- --- --- --- --- --- --- D3138 NOTE : 1.
14 T able 3 – Pipe Diameter T able PIPE DIAMETER T ABLE 359AA V MODEL 60,000 BTUH F urnaces 10 ′ (3.0 M) & (3) 90 ° elbows with 1.5 ″ (13 mm) PVC pipe 40 ′ ( 1 2 . 1M )&( 5 )9 0 ° elbows with 2 ″ (51 mm) PVC pipe or 70 ′ ( 2 1 . 3M )&( 5 )9 0 ° elbows with 3 ″ (76 mm) PVC pipe 80,000 BTUH F urnace 40 ′ ( 1 2 .
15 12 inches (30 cm) for appliean ces >10,000 Btuh(3 kW) and < 100,000 Btuh(30kW), 36 inches (91cm) for appliances > 100,000 Btuh(30kW) A06675 Fig.
16 Fig. 8 - - Other than Dir ect V ent T ermination Clearance 359AAV.
17 Condensate Drain T rap This furnace removes both sensible and latent heat from the products of combustion. Removal of the latent heat results in condensation of the water vapor . The condensate is removed from the furnace through the drains i n the plastic transition and the vent fitting.
18 INLET EXHAUST IN ON OFF V E N T AIR FLOW Street Elbow 1 / 2 ″ CPVC (Loose parts bag ) Casing Grommet Black Rubbe r 5 / 8 ″ ID (Loose parts bag ) Drain T ee Drain Conn ector Black PVC 3 / 4 ″ .
19 INLET EXHAUST IN ON OFF V E N T Casing Grommet Black Rubbe r 5 / 8 ″ ID (Loose parts bag ) Drain Conn ector Black PVC 3 / 4 ″ PVC X 1 / 2 ″ CPVC (Loose parts bag ) Drain Line Vent T ee 3 / 4 .
20 EXHAUST AIR FLOW INLET IN ON OFF V E N T Casing Grommet Black Rubbe r 5 / 8 ″ CPVC (Loose parts b ag) Drain Conn ector Black PVC 3 / 4 ″ PVC X 1 / 2 ″ CPVC (Loose parts bag ) Drain Line V ent.
21 Elbow T ube Black Rubber 1 / 2 ″ ″ ID (13 mm) & Clamps (Loose Parts Bag) AIR FLOW OFF ON AIR FLOW 25 - - 24 - - 69 Single Pressure Switch Detail Dual Pressure Switch T ee Trap White PVC (lo.
22 AIR FLOW OFF ON Drain Connector Black PVC 3 / 4 ″ CPVC (Loose parts bag) T rap Connection “Clamp ears” Pointed OUT Preassemble & insert into furnace Single Pressure Switch Detail Dual Pre.
23 T rap Connection “Clamp ears” Pointed OUT Preassemble & insert into furnace AIR FLOW IN ON OFF V E N T Relief T ube Black Rubber 3 / 16 ″ ID Plastic Caps Y ellow o r black Ve n t D r a i .
24 AIR FLOW IN ON OFF V E N T Relief T ube Black Rub ber 3 / 16 ″ ID 2 5 -- 2 4 -- 8 8 Single Pressure Switch Detail Dual Pressure Switch T ee T rap White PVC (loose parts ba g) WA R N I NG Move Cap.
25 Cut Here Drain T ube Corrugate d 5 / 8 ″ ″ ID & Clamps Cut at straight section Leave room fo r clamp IN ON OFF V E N T Relief T ube Rub ber T ube 3 / 16 ″ ID T rap Connection “Clamp ear.
26 IN ON OFF V E N T AIR FLOW Coupling & Clamps (Optional) Drain T ube Corrugate d, 5 / 8 ″ ID & Clamps Cut at straight section Relief T ube Black R ubber 3 / 16 ″ ID Single Pressure Switc.
27 before operation. V erify all condensate drain connections are securely clamped. A coupling and clamps (in loose part bag) may be installed as shown for future servicing of the vent system.
28 Rubber Coupling &C l a m p s 90 ° Elbow Combustion Blower V ent Fitting &C l a m p s V ent Extension Pipe (Side Panel Exit) V ent Pipe (T op Panel Exit) V ent Pipe Rotate downward 5 ° to 10 ° NOTE: Built- - in channel will be angled 5 ° to 10 ° also.
29 EXHAUST INLET GRADE LEVEL SNOW LEVEL OR 8” (203.2mm)* MIN. 20’ (6.1m) MA X *18 in. (457.2mm) Minimum for cold climates [sustained 0 _ F (- 17 _ C) and below for 24 o r more consecutive hours] 8” (203.2mm) MIN. 12 ” (304.8mm) MIN. A07716 Fig.
30 V ertical T ermination 1. Fig. 24 shows the pr oper installation and clearances for vertical vent termination. Th e vertical roof termination should be sealed with a plumbing roof boot or equivalent flashing.
31 CONCENTRIC TERMINA TION V ent T ermination Clearances CARBON MONOXIDE POISONING, FIRE AND EXPLOSION HAZARD Failure to follow t his warning could result in personal injury , death, or property damage. Inlet and outlet pipes may NOT be vented directly above each other (standard vent terminals).
32 B PVC Intake/Combustion Air B PVC V ent /Exhaust D A 1 1 / 2 ″ C Model A* B C D** KGAVT0801CVT 38 7 / 8 3 4 1 / 2 21 1 / 8 KGAVT0701CVT 33 3 / 8 2 3 1 / 2 16 5 / 8 * = Dimension will change accordingly as dimension D is lengthened or shortened.
33 1 ″ (25.4mm) max. Maintain 12 ″ (304.8mm) clearance above highest anticipated snow level or grade whichever is greater . Combustion Air V ent 25- - 22 - - 02 12 ″ (304.8mm) min. Roof Overhang A07736 Fig. 34 - - Concentric V e nt and Combustion- - Air Side T ermina tion 9.
34 7. Install a manual shut- - of f v alve external to furnace casing and tighten all joints securely . 8. If local codes allow the use of flexible gas appliance con- nectors, always use a new listed connector . Do not use a connector which has previously ser v iced an- other gas appliance.
35 O N O F F O N O F F O N O F F Use elbows and 3 ″ pipe nipple to connect valve to piping when using right side gas pipe entry . * Union may be installed inside the cabinet when necessary because of clearances. Drip Leg and Union, Union* should be outs ide the cabinet.
36 T able 6 – Natural Gas Manifold Pr essure (i n wc) 20,000 BTU per B urner* MEAN ELEVA TION FEET ABOVE SEA LEVEL Ft. (M) HEA TING VALU E BTU/CU . FT . 0 to 2000 2001 to 3000† 3001 to 4000 4001 to 5000 5001 to 6000 6001 to 7000 7001 to 8000 (0 to 610) (610.
37 your local gas supplier , then refer to T able 6 for required pressure change and/or orifice change for high altitudes . 3. For operation with Propane gas, gas orifices MUST be changed and manifold pressure MUST be maintained as per T able 7 . Orifices can be or dered through our distribut- or .
38 5. Move J- - Box to alternate location and attach using two self tapping screws from bag. 6. Apply two hole plugs from bag at left J - - Box location. Thermostat Thermostat location has an important effect on the operation o f the unit. Follow instructions incl uded with thermostat for correct mounting and wiring.
39 Installation NOTE : Design and install the air distribution system to comply with Air Conditioning Contractors of America manuals and/or NFP A pamphlets 90A and 90B or other approved methods that conform to local codes and good tr ade practices. 1.
40 A07729 Fig. 42 - - Side Mounted Filter Rack Filter Installation using Optional Filter Rack When installing or removing a bottom mounted filter , slide the two side filter clips to the back of the furnace BEFORE installing or removing. This will allow the filter to clear the front raised edge of the furnace.
41 Gas Supply Pressure Gas supply pressure should be within minimum and maximum values listed on rating plate ( minimum and maximum p ressures, refer to T able 5). P ressu res are usually set by gas suppliers. Manifold Gas Pressure Adjustment NOTE : Make adjustment to manifold pressure with burners operating.
42 will lower the temperature rise. A lower blower speed will increase the temperature rise. Changing Blower Speed ELECTRICAL SHOCK HAZARD Failure to follow this warning could result in personal injury or death. T urn OFF power to furnace before changing speed taps.
43 See “User ’s Information Manu al” and the “Service Manual”. SEQUENCE OF OPERA TION & DIAGNOSTICS Following is the normal operating sequence: Cooling (Y) Request: 24V AC signals applied to Y & G terminals of FCB (furnace control board) S Cool motor speed is ener gized after 5 second Cool Fan On Delay time.
44 Blower Off Delay Jumper FUSE Diagnos tic Light 24 V AC HUM 11 5 V A C HUM A07733 Fig. 49 - - Control Board Control Board Diagnostic Codes OFF = 24VAC or 115V AC is off, fuse is open Heartbeat = Normal operat ion or no previous Diagnostic Code ON SOLID = Soft Lockout - - - Furnace Control Error (1 hr .
Een belangrijk punt na aankoop van elk apparaat Bryant 4-WAY MULTIPOISE 359AAV (of zelfs voordat je het koopt) is om de handleiding te lezen. Dit moeten wij doen vanwege een paar simpele redenen:
Als u nog geen Bryant 4-WAY MULTIPOISE 359AAV heb gekocht dan nu is een goed moment om kennis te maken met de basisgegevens van het product. Eerst kijk dan naar de eerste pagina\'s van de handleiding, die je hierboven vindt. Je moet daar de belangrijkste technische gegevens Bryant 4-WAY MULTIPOISE 359AAV vinden. Op dit manier kan je controleren of het apparaat aan jouw behoeften voldoet. Op de volgende pagina's van de handleiding Bryant 4-WAY MULTIPOISE 359AAV leer je over alle kenmerken van het product en krijg je informatie over de werking. De informatie die je over Bryant 4-WAY MULTIPOISE 359AAV krijgt, zal je zeker helpen om een besluit over de aankoop te nemen.
In een situatie waarin je al een beziter van Bryant 4-WAY MULTIPOISE 359AAV bent, maar toch heb je de instructies niet gelezen, moet je het doen voor de hierboven beschreven redenen. Je zult dan weten of je goed de alle beschikbare functies heb gebruikt, en of je fouten heb gemaakt die het leven van de Bryant 4-WAY MULTIPOISE 359AAV kunnen verkorten.
Maar de belangrijkste taak van de handleiding is om de gebruiker bij het oplossen van problemen te helpen met Bryant 4-WAY MULTIPOISE 359AAV . Bijna altijd, zal je daar het vinden Troubleshooting met de meest voorkomende storingen en defecten #MANUAl# samen met de instructies over hun opplosinge. Zelfs als je zelf niet kan om het probleem op te lossen, zal de instructie je de weg wijzen naar verdere andere procedure, bijv. door contact met de klantenservice of het dichtstbijzijnde servicecentrum.