IMPORT ANT — READ BEFORE INST ALLING 1. Read and become familiar with these installation in- structions before installing this unit. 2. Be sure the installation conforms to all applicable local and national codes. 3. These instructions contain important information for the proper maintenance and repair of this equipment.
UNIT 575A UNIT W/ ALUMINUM-FIN COIL UNIT W/ COPPER-FIN COIL WEIGHT (WITH ALUMINUM-FIN COIL) WEIGHT (WITH COPPER-FIN COIL) Std Unit Corner W Corner X Corner Y Corner Z Std Unit Corner W Corner X Corner Y Corner Z Dim. A Dim. B Dim. A Dim. B Lb Kg Lb Kg Lb Kg Lb Kg Lb Kg Lb Kg Lb Kg Lb Kg Lb Kg Lb Kg 090 1 8 -8 9 [508.
T able 1 — Physical Data UNIT 575A 090 OPERA TING WEIGHT (lb) Aluminum Coils (Standard) 540 Copper Coils (Optional) 608 RIGGING WEIGHT (lb) Aluminum Coils (Standard) 590 Copper Coils (Optional) 658 REFRIGERANT* R-22 COMPRESSOR Reciprocating, Semi-Hermetic Quantity .
III. COMPLETE REFRIGERANT PIPING CONNECTIONS Suction connection is sweat with plastic cap; liquid connec- tion is sweat with plastic cap. Refer to T able 2 for the proper line sizes. Follow standard piping practices. T able 2 — Refrigerant Piping Sizes LINEAR LENGTH OF PIPING — ft UNIT 575A 0-25 25-50 50-75 75-100 Line Size (in.
LEGEND NEC — National Electrical Code TXV — Thermostatic Expansion V alve *Accessory item. †Field supplied. NOTES: 1. All piping must follow standard refrigerant piping techniques. 2. All wiring must comply with the applicable local and national codes.
IV . MAKE ELECTRICAL CONNECTIONS W ARNING: Unit cabinet must have an uninterrupted, unbroken electrical ground to minimize the possibility of personal injury if an electrical fault should occur .
T able 4 — Electrical Data UNIT 575A NOMINAL VOL T AGE (V -Ph-Hz) VOL T AGE RANGE COMPRESSOR OFM POWER SUPPL Y MINIMUM DISCONNECT Min Max RLA LRA FLA MCA MAX FUSE OR HACR BRKR AMPS FLA LRA 090 208/230-3-60 187 254 31.5 160 3.1 42.5 50 45 177 460-3-60 414 508 15.
C. Field Control Wiring Install an approved accessory thermostat assembly accord- ing to installation instructions included with the accessory . Locate thermostat assembly on a solid wall in the condi- tioned space to sense average temperature in accordance with thermostat installation instructions.
B. Oil Charging Allow unit to run for about 20 minutes. Stop unit and check compressor oil level. Add oil only if necessary to bring oil into view in sight glass. See T able 1 for oil charge. Use only ap- proved compressor oil as follows: Suniso 3GS and WF32-150 Do not reuse drained oil or use any oil that has been exposed to atmosphere.
C. Defrost Defrost board (DB) is a time and temperature control, which includes a field-selectable time period between checks for frost (30, 50, and 90 minutes). Electronic timer and defrost cycle start only when contactor is energized and defrost thermo- stat (DFT) is closed (below 28 F).
SERVICE CAUTION: When servicing unit, shut of f all electri- cal power to unit to avoid shock hazard or injury from rotating parts. I. CLEANING Inspect unit interior at the beginning of each cooling season and as operating conditions require. A. Outdoor Coil Inspect coil monthly .
II. LUBRICA TION A. Compressors Compressor has its own oil supply . Loss of oil due to a leak in the system should be the only reason for adding oil after the system has been in operation. See Start-Up, Oil Charging section. B. Fan Motor Bearings Fan motor bearings are permanently lubricated.
TROUBLESHOOTING CHART , HEA TING CYCLE LEGEND N.C. — Normally Closed —13—.
TROUBLESHOOTING CHART , COOLING CYCLE LEGEND TXV — Thermostatic Expansion V alve Copyright 1995 Carrier Corporation CA TALOG NO. BDP-3357-502.
ST ART -UP CHECKLIST I. PRELIMINAR Y INFORMA TION OUTDOOR: MODEL NO. INDOOR: MODEL NO. SERIAL NO. SERIAL NO. ADDITIONAL ACCESSORIES B. Pre-Start-Up OUTDOOR UNIT IS THERE ANY SHIPPING DAMAGE? (Y/N) IF SO, WHERE: WILL THIS DAMAGE PREVENT UNIT ST ART -UP? (Y/N) CHECK POWER SUPPL Y .
C. Start-Up CHECK INDOOR-F AN SPEED AND RECORD. CHECK OUTDOOR-F AN SPEED AND RECORD. AFTER A T LEAST 15 MINUTES RUNNING TIME, RECORD THE FOLLOWING MEASUREMENTS: COOLING HEA TING OIL PRESSURE SUCTION P.
Een belangrijk punt na aankoop van elk apparaat Bryant 575A (of zelfs voordat je het koopt) is om de handleiding te lezen. Dit moeten wij doen vanwege een paar simpele redenen:
Als u nog geen Bryant 575A heb gekocht dan nu is een goed moment om kennis te maken met de basisgegevens van het product. Eerst kijk dan naar de eerste pagina\'s van de handleiding, die je hierboven vindt. Je moet daar de belangrijkste technische gegevens Bryant 575A vinden. Op dit manier kan je controleren of het apparaat aan jouw behoeften voldoet. Op de volgende pagina's van de handleiding Bryant 575A leer je over alle kenmerken van het product en krijg je informatie over de werking. De informatie die je over Bryant 575A krijgt, zal je zeker helpen om een besluit over de aankoop te nemen.
In een situatie waarin je al een beziter van Bryant 575A bent, maar toch heb je de instructies niet gelezen, moet je het doen voor de hierboven beschreven redenen. Je zult dan weten of je goed de alle beschikbare functies heb gebruikt, en of je fouten heb gemaakt die het leven van de Bryant 575A kunnen verkorten.
Maar de belangrijkste taak van de handleiding is om de gebruiker bij het oplossen van problemen te helpen met Bryant 575A . Bijna altijd, zal je daar het vinden Troubleshooting met de meest voorkomende storingen en defecten #MANUAl# samen met de instructies over hun opplosinge. Zelfs als je zelf niet kan om het probleem op te lossen, zal de instructie je de weg wijzen naar verdere andere procedure, bijv. door contact met de klantenservice of het dichtstbijzijnde servicecentrum.