Gebruiksaanwijzing /service van het product 619CNF van de fabrikant Bryant
Ga naar pagina of 24
Cancels: II 619C-24-3 II 619C-24-4 4/15/06 CONTENTS Page SAFETY CONSIDERA TIONS . . . . . . . . . . . . . . . . . . . . . . . . . 1 INST ALLA TION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-17 I. Step 1 — Complete Pre-Installation Checks .
—2— T able 1 — System Matches *Units must be field reconfigured f or 1 1 / 2 ton (18,000 Btuh) operation. See Bef ore Installation section on page 3 for details. NO T E: Numbers in ( ) indicate quantities when there is more than one fan coil unit in the system.
—3— T able 3A — Physical Data, Unde r Ceiling Cooling Onl y Units *Field reconfigured to 18,000 Btuh (1 1 / 2 tons). See Before Installation section on this page for details . †The valv e connect ion size is 7 / 8 inch. The recommended line size is 1 1 / 8 inch.
—4— T able 3B — Physical Data, Under Ceiling Heat Pump Units *Field reconfigured to 18,000 Btuh (1 1 / 2 tons). See Before Installation section on page 3 for details. †The valv e connect ion size is 7 / 8 inch. The recommended line size is 1 1 / 8 inch.
—5— Fig. 3 — Base Unit Dimensions UNIT SIZE WEIGHT (lb) A B E F G Cooling Only Heat Pump ft-in. mm ft-in. mm ft-in. mm ft-in. mm ft-in. mm 024 108 110 4- 2 15 / 16 1294 3-10 1169 4- 1 5 / 8 1260.
—6— 5. Run refrigerant piping as directly as possible and avoid any unnecessary turns or ben ds . 6. Condensate piping can be dir ected through the inside wall to an approved drain or straight o utside. NO TE: The piping hole for condensate line must slope at a minimum pitch of 1 / 4 in.
—7— F . T o Install Thermostat: If there is at least 3 / 8 in. of space between the back of indoor unit and wall: 1. Route thermostat wires (fi eld-supplied) through slot in right side or rear panel of indoor unit (F ig. 3). 2. Route wires over refr igerant and drain piping as shown in Fig .
—8— 3. Insulate and caulk wall openings to reduce air infil- tration and refrigerant pipe vibrations on structure. 4. Evacuate piping, if necessary . If either refrigerant piping or the indoor coil is exposed to atmospheric conditions , it must be ev acua ted to 1000 microns to eliminate contamination and moisture in the system.
—9— HEX-HEAD BOLT MOUNTING SLOT Fig. 10 — Mounting Ha nging Brackets Fig. 11 — Hangin g Fan Co il Unit *F actor y-supplied. Fig. 12 — Routing Wires Over Piping NO TE: T eflon Seal must face to ward the outdoor heat pump unit.
—10— VI. STEP 6 — MAKE ELECTRICAL CONNECTIONS Be sure field wiring complies with local building codes and NEC , and unit voltage is within limits shown in T ab le 5. Contact local power company for correction of improper line voltage. NO TE: Use copper wire only betw een disconnect switch(es) and unit.
—11— Fig. 14 — Component Location (T ypical Ceiling-Suspended System) LEGEND *Standard. †Accessory item. **Field supplied. ††Insulate for heat pump application. NO T ES: 1. All piping must f ollow standard refr igerant piping techniques. 2.
—12— VII. STEP 7 — INST ALL THERMOST A T These systems use a 3-speed thermostat. The thermostat monitors the system operatio n and controls the operating mode. T o change settings or re fer to the thermostat Operat- ing Instructions. Mount thermostat to a wall in the occupied space using 2 field-supplied screws .
—13— LEGEND ASM — Air Sweep Motor ASR — Air Sw ee p Rela y EQUIP GND — Equipment Ground FL — Fuse Link FPT — F reeze Protection Ther mostat HP — Heat Pump HR — Heater Relay HTR — Heater HTT — Heater T emp.
—14— AUTO COOL HEA T COOL HEA T AUTO FLA T THERMOST A T (FLA TST A T) COOLING ONL Y HEA T & COOL (53DFS250-FS-BR Y) SLIMLINE THERMOST A T HEA T PUMP COOLING ONL Y HEA T & COO L (53DFS250-SL-BR Y) 5-1-1 PROGRAMMABLE THERMOST A T COOLING ONL Y HEA T & COOL (53DFST2-NP-BR Y) Fig.
—15— VIII. STEP 8 — MAKE CONNECTIONS BETWEEN INDOOR AND OUTDOOR UNITS The thermostat is wired betw een the indoor and outdoor units to make the s ystem complete. A. Check AccuRater Metering Device The correct Ac cuRater (bypass type) refrigerant con t rol is required for system capacity optimization.
—16— 5 38 A 619CNF ,CNQ 5 38 A 619CNF ,CNQ Fig. 20 — Cooling System Wiring Diagram a40-1636.
—17— 619CNQ 5 38 B 5 38 B 619CNQ Fig. 21 — Heat Pump Wiring Diagram a40-1637.
—18— ST ART -UP Make the following checks and complete the Start-Up Check- list on page CL-1 before sy stem start-up. Also refer to the condensing unit Installation, St art-Up and Service Instructions for system start-up instructions and refrigerant charging methods .
—19— The DFB logic checks the 10-m inute defrost timer and the DFT . If the DFT opens in less than 10 minutes , the DFB switches the unit back to norm al heating operation. If the DFT remains closed, the DFB switches the unit back to heating operation after 10 minu tes.
—20— III. CLEAN INDOOR UNIT BOTT OM P ANEL If the bottom panel of the unit becomes dirty or smudged, wipe the outside of the panel wi th a soft dry cloth.
—21— T able 7 — T roubleshooting *If fuse blo ws or circuit breaker trips again after firs t star t attempt, DO NOT attempt to start system again.
Copy right 2006 Bryant Heating & Cooling Systems Printed in U.S .A. CA T ALOG NO . 02-619C0001-II SER VICE TRAINING P ackaged Service Training programs are an excellent wa y to in crease your know.
CL-1 ST ART -UP CHECKLIST I. PRELIMINAR Y INFORMA TION OUTDOOR UNIT : MODEL NO. ___________________ INDOOR UNIT : MODEL NO . _____________________ SERIAL NO .
Copy right 2006 Bryant Heating & Cooling Systems Printed in U .S.A. CL-2 6-06A CA T ALOG NO. 02-619C00 01-II CUT ALONG DO TTED LINE CUT ALONG DOTTED LINE ST ART -UP CHECKLIST (c ont) IV .
Een belangrijk punt na aankoop van elk apparaat Bryant 619CNF (of zelfs voordat je het koopt) is om de handleiding te lezen. Dit moeten wij doen vanwege een paar simpele redenen:
Als u nog geen Bryant 619CNF heb gekocht dan nu is een goed moment om kennis te maken met de basisgegevens van het product. Eerst kijk dan naar de eerste pagina\'s van de handleiding, die je hierboven vindt. Je moet daar de belangrijkste technische gegevens Bryant 619CNF vinden. Op dit manier kan je controleren of het apparaat aan jouw behoeften voldoet. Op de volgende pagina's van de handleiding Bryant 619CNF leer je over alle kenmerken van het product en krijg je informatie over de werking. De informatie die je over Bryant 619CNF krijgt, zal je zeker helpen om een besluit over de aankoop te nemen.
In een situatie waarin je al een beziter van Bryant 619CNF bent, maar toch heb je de instructies niet gelezen, moet je het doen voor de hierboven beschreven redenen. Je zult dan weten of je goed de alle beschikbare functies heb gebruikt, en of je fouten heb gemaakt die het leven van de Bryant 619CNF kunnen verkorten.
Maar de belangrijkste taak van de handleiding is om de gebruiker bij het oplossen van problemen te helpen met Bryant 619CNF . Bijna altijd, zal je daar het vinden Troubleshooting met de meest voorkomende storingen en defecten #MANUAl# samen met de instructies over hun opplosinge. Zelfs als je zelf niet kan om het probleem op te lossen, zal de instructie je de weg wijzen naar verdere andere procedure, bijv. door contact met de klantenservice of het dichtstbijzijnde servicecentrum.