Form No. PDS 698B.24.1 TWO-SPEED PURON® PLUS™ ELECTRIC HEAT PUMP 698B (60 HZ) Sizes 024, 036, 048, and 060 • T W O - S P E E D • ™ Model 698B Heat Pumps incor porate innov ativ e 2-speed com- pressor technology with Puron ® , the refrigerant of the future, to provide quiet, ef fi cient cooling perf ormance.
— 2 — DIMENSIONS A01063 DIMENSIONS (IN.) SOUND PO WER (dBA) *Sound lev els are equivalent at high and low speeds. UNIT SIZE SERIES A B C D E F G H K L M N MINIMUM MOUNTING P AD DIMENSIONS 024 A 33.
— 3 — RECOMMENDED TUBE DIAMETERS NO TE: Maximum long-line tube length of 50 ft liquid and v apor line sets indicated abov e must be f ollowed on all applications . Over 50 ft or 20 ft vertical differential, refer to Application Guideline and Service Manual — Air Conditioners and Heat Pumps Using Puron ® Refrigerant.
— 4 — SPECIFICA TIONS * P ermissible limits of the voltage r ange at which the unit will operate satisf actorily . Oper ation outside these limits ma y result in unit failure . † If wire is applied at ambient greater than 30 ° C (86 ° F), consult T able 310-16 of the NEC (ANSI/NFP A 70).
— 5 — OPTIONAL EQUIPMENT DESCRIPTION AND USA GE (Listed Alphabetically) 1. Coastal Filter A mesh screen inser ted under the top cov er and inside the base pan to protect the condenser coil from salt damage without restricting air fl ow . SUGGESTED USE:In geographic areas where salt damage could occur .
— 6 — COMBINA TION RA TINGS UNIT SIZE SERIES INDOOR UNIT Cooling ‡ Heating HPSF High-T emp Low-T emp CFM** TC* SEER EER TC* Cop TC* Cop High Lo w High Low High Lo w High Low High Low High Low 024-A FV4ANF002* 735 440 24,000 12,000 14.0 11.0 21,000 10,600 3.
— 7 — UNIT SIZE SERIES INDOOR UNIT Cooling ‡ Heating HPSF High-T emp Low-T emp CFM** TC* SEER EER TC* Cop TC* Cop High Low High Low High Low High Low High Low High Low 036-A FK4CNF001 1100 660 33,600 17,200 14.0 10.7 32,600 15,400 3.12 3.50 18,500 7300 2.
— 8 — UNIT SIZE SERIES INDOOR UNIT Cooling ‡ Heating HPSF High-T emp Low-T emp CFM** TC* SEER EER TC* Cop TC* Cop High Low High Low High Low High Low High Low High Low 036-A CK5A/CK5BA048 1100 700 34,800 17,600 15.0 11.6 32,400 15,800 3.32 3.66 18,400 7300 2.
— 9 — UNIT SIZE SERIES INDOOR UNIT Cooling ‡ Heating HPSF High-T emp Low-T emp CFM** TC* SEER EER TC* Cop TC* Cop High Low High Low High Low High Low High Low High Low 036-A CC5A/CD5AB042 1200 800 34,600 17,600 14.5 11.2 32,800 15,800 3.20 3.58 18,700 7500 2.
— 10 — UNIT SIZE SERIES INDOOR UNIT Cooling ‡ Heating HPSF High-T emp Low-T emp CFM** TC* SEER EER TC* Cop TC* Cop High Low High Low High Low High Low High Low High Low 048-A CK5A/CK5BN060 1470 910 45,500 24,000 14.5 11.0 42,500 24,000 3.06 3.62 27,800 14,000 2.
— 11 — * Ratings are net values re fl ecting the eff ects of circulating fan heat. Supplemental electric heat is not included. Ratings are based on: Cooling Standard: 80 ° F (27 ° C) db 67 ° F (19 ° C) wb indoor entering air temperature and 95 ° F (35 ° C) db air entering outdoor unit.
— 12 — 698BNX BALANCE POINT WORKSHEET BUILDING H EAT LO SS, 1000 BTU / HR UN I T I NTEGRATED HEATING C APACITY, 1000 BTU/HR P rinte d in U .S.A . OUTDOOR TEMPERATURE, ° F -10 0 10 20 30 40 50 60 70 80 2.9 5.9 8.8 11.7 14.7 17.6 20.5 70 60 50 40 30 20 10 KW BASED ON INDOOR ENT.
— 13 — DET AILED COOLING CAP A CITIES* See notes on page 27. EV APORA TOR AIR CONDENSER ENTERING AIR TEMPERA TURES ° F 75 85 95 105 115 125 CFM EWB Capacity MBtuh † T otal System KW** Capacity .
— 14 — DET AILED COOLING CAP A CITIES* continued See notes on page 27. EV APORA TOR AIR CONDENSER ENTERING AIR TEMPERA TURES ° F 75 85 95 105 115 125 CFM EWB Capacity MBtuh † T otal System KW**.
— 15 — DET AILED COOLING CAP A CITIES* continued See notes on page 27. EV APORA TOR AIR CONDENSER ENTERING AIR TEMPERA TURES ° F 75 85 95 105 115 125 CFM EWB Capacity MBtuh † T otal System KW**.
— 16 — DET AILED COOLING CAP A CITIES* continued See notes on page 27. EV APORA TOR AIR CONDENSER ENTERING AIR TEMPERA TURES ° F 75 85 95 105 115 125 CFM EWB Capacity MBtuh † T otal System KW**.
— 17 — DET AILED COOLING CAP A CITIES* continued See notes on page 27. EV APORA TOR AIR CONDENSER ENTERING AIR TEMPERA TURES ° F 75 85 95 105 115 125 CFM EWB Capacity MBtuh † T otal System KW**.
— 18 — DET AILED COOLING CAP A CITIES* continued See notes on page 27. EV APORA TOR AIR CONDENSER ENTERING AIR TEMPERA TURES ° F 75 85 95 105 115 125 CFM EWB Capacity MBtuh † T otal System KW**.
— 19 — DET AILED COOLING CAP A CITIES* continued See notes on page 27. EV APORA TOR AIR CONDENSER ENTERING AIR TEMPERA TURES ° F 75 85 95 105 115 125 CFM EWB Capacity MBtuh † T otal System KW**.
— 20 — DET AILED COOLING CAP A CITIES* continued See notes on page 27. EV APORA TOR AIR CONDENSER ENTERING AIR TEMPERA TURES ° F 75 85 95 105 115 125 CFM EWB Capacity MBtuh † T otal System KW**.
— 21 — DET AILED COOLING CAP A CITIES* continued See notes on page 27. EV APORA TOR AIR CONDENSER ENTERING AIR TEMPERA TURES ° F 75 85 95 105 115 125 CFM EWB Capacity MBtuh † T otal System KW**.
— 22 — DET AILED COOLING CAP A CITIES* continued See notes on page 27. EV APORA TOR AIR CONDENSER ENTERING AIR TEMPERA TURES ° F 75 85 95 105 115 125 CFM EWB Capacity MBtuh † T otal System KW**.
— 23 — DET AILED COOLING CAP A CITIES* continued See notes on page 27. EV APORA TOR AIR CONDENSER ENTERING AIR TEMPERA TURES ° F 75 85 95 105 115 125 CFM EWB Capacity MBtuh † T otal System KW**.
— 24 — DET AILED COOLING CAP A CITIES* continued See notes on page 27. EV APORA TOR AIR CONDENSER ENTERING AIR TEMPERA TURES ° F 75 85 95 105 115 125 CFM EWB Capacity MBtuh † T otal System KW**.
— 25 — DET AILED COOLING CAP A CITIES* continued See notes on page 27. EV APORA TOR AIR CONDENSER ENTERING AIR TEMPERA TURES ° F 75 85 95 105 115 125 CFM EWB Capacity MBtuh † T otal System KW**.
— 26 — DET AILED COOLING CAP A CITIES* continued See notes on page 27. EV APORA TOR AIR CONDENSER ENTERING AIR TEMPERA TURES ° F 75 85 95 105 115 125 CFM EWB Capacity MBtuh † T otal System KW**.
— 27 — DET AILED COOLING CAP A CITIES* continued * Detailed cooling capacities are based on indoor and outdoor unit at the same ele vation per ARI standard 210/240-94. If additional tubing length is used and/or indoor unit is located abov e outdoor unit, a slight v ariation in capacity may occur .
— 28 — HEA T PUMP HEA TING PERFORMANCE See notes on page 41. INDOOR AIR OUTDOOR COIL ENTERING AIR TEMPERA TURES ° F – 3 7 17 27 37 47 57 67 EDB CFM Capacity MBtuh † T otal Pwr Capacity MBtuh .
— 29 — HEA T PUMP HEA TING PERFORMANCE continued See notes on page 41. INDOOR AIR OUTDOOR COIL ENTERING AIR TEMPERA TURES ° F 17 27 37 47 57 67 EDB CFM Capacity MBtuh † T otal Pwr Capacity MBtu.
— 30 — HEA T PUMP HEA TING PERFORMANCE continued See notes on page 41. INDOOR AIR OUTDOOR COIL ENTERING AIR TEMPERA TURES ° F – 3 7 17 27 37 47 57 67 EDB CFM Capacity MBtuh † T otal Pwr Capac.
— 31 — HEA T PUMP HEA TING PERFORMANCE continued See notes on page 41. INDOOR AIR OUTDOOR COIL ENTERING AIR TEMPERA TURES ° F – 3 7 17 27 37 47 57 67 EDB CFM Capacity MBtuh † T otal Pwr Capac.
— 32 — HEA T PUMP HEA TING PERFORMANCE continued See notes on page 41. INDOOR AIR OUTDOOR COIL ENTERING AIR TEMPERA TURES ° F – 3 7 17 27 37 47 57 67 EDB CFM Capacity MBtuh † T otal Pwr Capac.
— 33 — HEA T PUMP HEA TING PERFORMANCE continued See notes on page 41. INDOOR AIR OUTDOOR COIL ENTERING AIR TEMPERA TURES ° F 17 27 37 47 57 67 EDB CFM Capacity MBtuh † T otal Pwr Capacity MBtu.
— 34 — HEA T PUMP HEA TING PERFORMANCE continued See notes on page 41. INDOOR AIR OUTDOOR COIL ENTERING AIR TEMPERA TURES ° F 17 27 37 47 57 67 EDB CFM Capacity MBtuh † T otal Pwr Capacity MBtu.
— 35 — HEA T PUMP HEA TING PERFORMANCE continued See notes on page 41. INDOOR AIR OUTDOOR COIL ENTERING AIR TEMPERA TURES ° F 17 27 37 47 57 67 EDB CFM Capacity MBtuh † T otal Pwr Capacity MBtu.
— 36 — HEA T PUMP HEA TING PERFORMANCE continued See notes on page 41. INDOOR AIR OUTDOOR COIL ENTERING AIR TEMPERA TURES ° F – 3 7 17 27 37 47 57 67 EDB CFM Capacity MBtuh † T otal Pwr Capac.
— 37 — HEA T PUMP HEA TING PERFORMANCE continued See notes on page 41. INDOOR AIR OUTDOOR COIL ENTERING AIR TEMPERA TURES ° F – 3 7 17 27 37 47 57 67 EDB CFM Capacity MBtuh † T otal Pwr Capac.
— 38 — HEA T PUMP HEA TING PERFORMANCE continued See notes on page 41. INDOOR AIR OUTDOOR COIL ENTERING AIR TEMPERA TURES ° F 17 27 37 47 57 67 EDB CFM Capacity MBtuh † T otal Pwr Capacity MBtu.
— 39 — HEA T PUMP HEA TING PERFORMANCE continued See notes on page 41. INDOOR AIR OUTDOOR COIL ENTERING AIR TEMPERA TURES ° F 17 27 37 47 57 67 EDB CFM Capacity MBtuh † T otal Pwr Capacity MBtu.
— 40 — HEA T PUMP HEA TING PERFORMANCE continued See notes on page 41. INDOOR AIR OUTDOOR COIL ENTERING AIR TEMPERA TURES ° F – 3 7 17 27 37 47 57 67 EDB CFM Capacity MBtuh † T otal Pwr Capac.
— 41 — HEA T PUMP HEA TING PERFORMANCE continued * The Btuh heating capacity values sho wn are net “ integrated ” values from which the defrost eff ect has been subtracted. The Btuh heating from supplement heaters should be added to those v alues to obtain total system capacity .
— 42 —.
— 43 —.
— 44 — SPECIFICATIONS SUBJECT TO CHANGE WITHOUT NOTICE UNIT MUST BE INSTALLED IN ACCORDANCE WITH INSTALLATION INSTRUCTIONS Cancels: New © 2001 Bryant Heating & Cooling Systems, 7310 W. Morris St. Indpls., IN 46231 PRINTED IN U.S.A. Catalog No.
Een belangrijk punt na aankoop van elk apparaat Bryant 698B (of zelfs voordat je het koopt) is om de handleiding te lezen. Dit moeten wij doen vanwege een paar simpele redenen:
Als u nog geen Bryant 698B heb gekocht dan nu is een goed moment om kennis te maken met de basisgegevens van het product. Eerst kijk dan naar de eerste pagina\'s van de handleiding, die je hierboven vindt. Je moet daar de belangrijkste technische gegevens Bryant 698B vinden. Op dit manier kan je controleren of het apparaat aan jouw behoeften voldoet. Op de volgende pagina's van de handleiding Bryant 698B leer je over alle kenmerken van het product en krijg je informatie over de werking. De informatie die je over Bryant 698B krijgt, zal je zeker helpen om een besluit over de aankoop te nemen.
In een situatie waarin je al een beziter van Bryant 698B bent, maar toch heb je de instructies niet gelezen, moet je het doen voor de hierboven beschreven redenen. Je zult dan weten of je goed de alle beschikbare functies heb gebruikt, en of je fouten heb gemaakt die het leven van de Bryant 698B kunnen verkorten.
Maar de belangrijkste taak van de handleiding is om de gebruiker bij het oplossen van problemen te helpen met Bryant 698B . Bijna altijd, zal je daar het vinden Troubleshooting met de meest voorkomende storingen en defecten #MANUAl# samen met de instructies over hun opplosinge. Zelfs als je zelf niet kan om het probleem op te lossen, zal de instructie je de weg wijzen naar verdere andere procedure, bijv. door contact met de klantenservice of het dichtstbijzijnde servicecentrum.