GENERA C POWER SYSTEMS, INC. R R Owner’s Manual Air-cooled, Prepackaged Automatic Standby Generators Models: ASPAS1BBA007 (6 kW NG, 7 kW LP) ASPAS1BBA012 (12 kW NG, 12 kW LP) ASPAS1BBA015 (13 kW NG, 15 kW LP) DEADL Y EXHAUST FUMES.
Bryant I NTRODUCTION Thank you for purchasing this model of the Bryant product line. This model is a compact, high performance, air-cooled, engine-driven generator designed to automatically supply electrical power to operate critical loads during a utility power failure.
T able of Cont ents Bryant Air-cooled 7 kW , 1 2 kW and 1 5 kW Generators Bryant 1 Introduction ........................Inside Front Cover Read This Manual Thoroughly ..............................IFC Contents .........................................
2 Bryant Study these SAFETY RULES carefully before installing, operating or servicing this equipment. Become familiar with this Owner’s Manual and with the unit. The generator can operate safely, efficiently and reliably only if it is properly installed, operated and maintained.
Bryant 3 ELE CTR ICAL HA Z AR DS • All generators covered by this manual produce dangerous electrical voltages and can cause fatal electrical shock. Utility power delivers extremely high and dangerous voltages to the transfer switch as does the standby generator when it is in operation.
Only qualified electricians or contractors should attempt such installations, which must comply strictly with applicable codes, standards and regulations.
Section 1 — General Information Bryant Air-cooled 7 kW , 1 2 kW and 1 5 kW Generators Bryant 5 1.4 TH E GEN ER A T OR Exhaus t En c lo su r e O i l Di p stic k D a t a D ecal C ontro l Pa n el F uel.
6 Bryant Section 1 — General Information Bryant Air-cooled 7 kW , 1 2 kW and 1 5 kW Generators 1.5 SP E CI F ICA TIONS 1.5.1 GEN ERA T OR Model ASPAS1BBA007 ASPAS1BBA012 ASPAS1BBA015 Rated Max. Continuous Power Capacity (Watts*) 6,000 NG/7,000 LP 12,000 NG/12,000 LP 13,000 NG/15,000 LP Rated Voltage 120/240 120/240 120/240 Rated Max.
Bryant 7 Should the primary fuel need to be changed to LP gas, the fuel system needs to be reconfigured. See Section 1.9 for instructions on reconfiguration of the fuel system. Recommended fuels should have a Btu content of at least 1,000 Btus per cubic foot for natural gas; or at least 2,520 Btus per cubic foot for LP gas.
1.1 0 B A TTER Y I NS T ALLA TION Fill the battery with the proper electrolyte fluid if necessary and have the battery fully charged before installing it. Before installing and connecting the battery, complete the following steps: 1. Set the generator's AUTO/OFF/MANUAL switch to OFF.
Bryant 9 Servicing of the battery is to be performed or supervised by personnel knowledgeable of batteries and the required precautions. Keep unauthorized personnel away from batteries.
10 Bryant 2.3 AUT OMA TIC TR ANSF ER OP ER A TION To select automatic operation, do the following: 1. Make sure the transfer switch main contacts are set to their UTILITY position, i.
Bryant 11 2.5 MAN U AL TR ANSF ER OP ER A TION 2.5.1 TRANSF ER T O GEN ER A T OR POWER S OURCE To start the generator and activate the transfer switch manually, proceed as follows: 1. Set the generator’s AUTO/OFF/MANUAL switch to OFF. 2. Set the generator’s main circuit breaker to its OFF (or open) position.
12 Bryant NOTE: The exerciser will only work in the AUTO mode and will not work unless this procedure is performed. The exerciser will need to be reset every time the 12-volt battery is disconnected and then reconnected. The exerciser WILL NOT work if dip switch 2 on the controller printed cir cuit board (Remote Not Auto) is ON.
Bryant 13 Section 3 — Maintenance Bryant Air-cooled 7 kW , 1 2 kW and 1 5 kW Generators Figure 3.1 – Generator Control Panel 3.2 CH E CKI NG TH E ENGI N E OI L LEVEL For oil capacities, see “Specifications,” Section 1.5. For engine oil recommendations, see Section 3.
14 Bryant Section 3 — Maintenance Bryant Air-cooled 7 kW , 1 2 kW and 1 5 kW Generators Figure 3.4 – Oil Drain Hose and Filter 3.4 CHANGI NG TH E OI L F I L TER Change the engine oil filter as follows: 1. With the oil drained, remove the old oil filter by turning it counterclockwise.
Bryant 15 Figure 3.7 – Setting the Spark Plug Gap 3.7 B A TTER Y MAI NTENANCE The battery should be inspected per the “Service Schedule,” Section 4.1. The following procedure should be followed for inspection: 1. Inspect the battery posts and cables for tightness and corrosion.
16 Bryant Figure 3.8 – Cooling V ent Locations The exhaust from this pr oduct gets extremely hot and remains hot after shutdown. High grass, weeds, brush, leaves, etc. must remain clear of the exhaust. Such materials may ignite and burn from the heat of the exhaust system.
Bryant 17 Section 4 — Service Bryant Air-cooled 7 kW , 1 2 kW and 1 5 kW Generators 4.1 SERVICE S CH EDU LE A TTENTION: It is recommended that all service work be performed by the nearest Bryant Dealer .
18 Bryant Section 5 — T roubleshooting Bryant Air-cooled 7 kW , 1 2 kW and 1 5 kW Generators 5.1 TROU B LE SHOO TI NG GU I DE P ROB LEM CAUSE C OR R E CTION The engine will not crank. 1. Fuse blown. 1. Replace 15A fuse in generator control panel. 2.
Bryant 19 BRYANT "TWO YEAR" LIMITED WARRANTY FOR "PREPACKAGED EMERGENCY AUTOMATIC STANDBY GENERATORS" For a period of two years from the date of original sale, Bryant warrants that its generator will be free from defects in material and workmanship for the items and period set forth below.
20 Bryant CALI FOR N IA EM ISSION C ONTROL W AR RANT Y ST A TEM ENT Y OUR W AR R ANTY R IGHTS AND OB LIGA TIONS The California Air Resources Board (CARB) and Generac Power Systems, Inc. (Generac) are pleased to explain the Emission Control System Warranty on your new engine.
Bryant 21 EM IS SION CONTROL S Y S TEM W ARR ANT Y Emission Control System Warranty (ECS Warranty) for 1995 and later model year engines: (a) Applicability: This warranty shall apply to 1995 and later model year engines.
PART NO. 0F6906 CATALOG NO. OM18-5 REV. * (6/01/05) PRINTED IN U.S.A..
Een belangrijk punt na aankoop van elk apparaat Bryant ASPAS1BBA007 (of zelfs voordat je het koopt) is om de handleiding te lezen. Dit moeten wij doen vanwege een paar simpele redenen:
Als u nog geen Bryant ASPAS1BBA007 heb gekocht dan nu is een goed moment om kennis te maken met de basisgegevens van het product. Eerst kijk dan naar de eerste pagina\'s van de handleiding, die je hierboven vindt. Je moet daar de belangrijkste technische gegevens Bryant ASPAS1BBA007 vinden. Op dit manier kan je controleren of het apparaat aan jouw behoeften voldoet. Op de volgende pagina's van de handleiding Bryant ASPAS1BBA007 leer je over alle kenmerken van het product en krijg je informatie over de werking. De informatie die je over Bryant ASPAS1BBA007 krijgt, zal je zeker helpen om een besluit over de aankoop te nemen.
In een situatie waarin je al een beziter van Bryant ASPAS1BBA007 bent, maar toch heb je de instructies niet gelezen, moet je het doen voor de hierboven beschreven redenen. Je zult dan weten of je goed de alle beschikbare functies heb gebruikt, en of je fouten heb gemaakt die het leven van de Bryant ASPAS1BBA007 kunnen verkorten.
Maar de belangrijkste taak van de handleiding is om de gebruiker bij het oplossen van problemen te helpen met Bryant ASPAS1BBA007 . Bijna altijd, zal je daar het vinden Troubleshooting met de meest voorkomende storingen en defecten #MANUAl# samen met de instructies over hun opplosinge. Zelfs als je zelf niet kan om het probleem op te lossen, zal de instructie je de weg wijzen naar verdere andere procedure, bijv. door contact met de klantenservice of het dichtstbijzijnde servicecentrum.