Form No. PDS 561C.18.6 ELECTRIC AIR CONDITIONER 561C (60 Hz) Sizes 018 thru 060 Model 561C Energy-Efficient Air Conditioners incor porate inno- vativ e technology to provide reliab le summer cooling perfor- mance. Built into these units are the f eatures most desired by homeowners toda y including SEER ratings of up to 11.
—2— DIMENSIONS—561C A97017 AIR IN NOTES: 1. Allow 30 in. clearance to service side of unit, 48 in. above unit, 6 in. on one side, 12 in. on remaining side, and 24 in. between units for proper airflow. 2. Minimum outdoor operating ambient in cooling mode is 55 ° F, max.
—3— CHECK-FLO-RA TER® PIST ON CHART * Piston listed is f or any approv ed coil non-capillar y tube combination. Piston is shipped with outdoor unit and must be installed in an appro ved indoor coil. RECOMMENDED TUBE DIAMETERS * For tube sets betw een 50 and 175 ft, consult Residential Split System Long-Line Application Guideline.
—4— SPECIFICA TIONS See notes on page 7. UNIT SIZE-SERIES 561C018-A, D 561C024-A, D 561C030-A, D 561C030-A Operating W eight (Lb) 113/115 115/117 124/133 124 ELECTRICAL Unit V olts—Hertz—Phase 208-230—60—1 208/230—60—3 Operating V oltage Range* 197—253 187—253 Compressor— Rated Load Amps 9.
—5— SPECIFICA TIONS Continued See notes on page 7. UNIT SIZE-SERIES 561C036-A, B, E 561C036-B, D 561C036-B 561C042-A, B 561C042-B, C 561C042-B Operating W eight (Lb) 129/138/138 129/133 133 138/14.
—6— SPECIFICA TIONS Continued See notes on page 7. UNIT SIZE-SERIES 561C048-A, B 561C048-B, C 561C060-A, B 561C060-B, E Operating W eight (Lb) 192/198 233/218 ELECTRICAL Unit V olts—Hertz—Phas.
—7— * P er missible limits of the v oltage range at which unit will operate satisf actor ily . Oper ation outside these limits may result in unit f ailure. † If wire is applied at ambient greater than 30°C (86°F), consult T able 310-16 of the NEC (ANSI/NFP A 70).
—8— A CCESSOR Y DESCRIPTION AND USA GE (Listed Alphabetically) Continued 9. High-Pressure Switch Auto reset SPST s witch activated by refrigerant pressure on high side of refrigerant circuit. Cycles compressor off if refrigerant pressure rises to 400 ± 10 psig and resets at 298 ± 20 psig.
—9— COMBINA TION RA TINGS See notes on page 14. UNIT SIZE-SERIES INDOOR MODEL T OT . CAP . BTUH F ACT ORY- SUPPLIED ENHANCE- MENT ST AND ARD RA TING BR Y ANT GAS FURNA CE OR A CCESSOR Y TDR† A CCESSOR Y TXV‡ EERA 018-A, D CC5A/CD5AA018* 17,200 NONE — 10.
—10— COMBINA TION RA TINGS Continued See notes on page 14. UNIT SIZE-SERIES INDOOR MODEL T OT . CAP . BTUH F ACT ORY- SUPPLIED ENHANCE- MENT ST AND ARD RA TING BR Y ANT GAS FURNA CE OR A CCESSOR Y TDR† A CCESSOR Y TXV‡ EERA 030-A, D CD5A/CD5AA030* 28,000 NONE 10.
—11— COMBINA TION RA TINGS Continued See notes on page 14. UNIT SIZE-SERIES INDOOR MODEL T OT . CAP . BTUH F ACT ORY- SUPPLIED ENHANCE- MENT ST AND ARD RA TING BR Y ANT GAS FURNA CE OR A CCESSOR Y TDR† A CCESSOR Y TXV‡ EERA 036-A, B, D , E CK3BA036 33,800 NONE 10.
—12— COMBINA TION RA TINGS Continued See notes on page 14. UNIT SIZE-SERIES INDOOR MODEL T OT . CAP . BTUH F ACT ORY- SUPPLIED ENHANCE- MENT ST AND ARD RA TING BR Y ANT GAS FURNA CE OR A CCESSOR Y TDR† A CCESSOR Y TXV‡ EERA 036-A, B, D , E CK5A/CK5BA042 33,400 TDR 10.
—13— COMBINA TION RA TINGS Continued See notes on page 14. UNIT SIZE-SERIES INDOOR MODEL T OT . CAP . BTUH F ACT ORY- SUPPLIED ENHANCE- MENT ST AND ARD RA TING BR Y ANT GAS FURNA CE OR A CCESSOR Y TDR† A CCESSOR Y TXV‡ EERA 042-A, B, C COILS + 355MA V060100 V ARIABLE-SPEED FURNACE CC5A/CD5AA042 40,000 TDR 10.
—14— COMBINA TION RA TINGS Continued * T ested Combination. † In most cases, only 1 method should be used to achie v e TDR function. Using more than 1 method in a system ma y cause degradation in performance. Use either the accessory Time-Dela y Relay KAA TD0101TDR or a furnace equipped with TDR.
—15— DET AILED COOLING CAP A CITIES* See notes on page 24. EV APORA TOR AIR CONDENSER ENTERING AIR TEMPERA TURES °F 75 85 95 105 115 125 CFM EWB Capacity MBtuh† T otal Sys KW** Capacity MBtuh.
—16— DET AILED COOLING CAP A CITIES* Continued See notes on page 24. EV APORA TOR AIR CONDENSER ENTERING AIR TEMPERA TURES °F 75 85 95 105 115 125 CFM EWB Capacity MBtuh† T otal Sys KW** Capaci.
—17— DET AILED COOLING CAP A CITIES* Continued See notes on page 24. EV APORA TOR AIR CONDENSER ENTERING AIR TEMPERA TURES °F 75 85 95 105 115 125 CFM EWB Capacity MBtuh† T otal Sys KW** Capaci.
—18— DET AILED COOLING CAP A CITIES* Continued See notes on page 24. EV APORA TOR AIR CONDENSER ENTERING AIR TEMPERA TURES °F 75 85 95 105 115 125 CFM EWB Capacity MBtuh† T otal Sys KW** Capaci.
—19— DET AILED COOLING CAP A CITIES* Continued See notes on page 24. EV APORA TOR AIR CONDENSER ENTERING AIR TEMPERA TURES °F 75 85 95 105 115 125 CFM EWB Capacity MBtuh† T otal Sys KW** Capaci.
—20— DET AILED COOLING CAP A CITIES* Continued See notes on page 24. EV APORA TOR AIR CONDENSER ENTERING AIR TEMPERA TURES °F 75 85 95 105 115 125 CFM EWB Capacity MBtuh† T otal Sys KW** Capaci.
—21— DET AILED COOLING CAP A CITIES* Continued See notes on page 24. EV APORA TOR AIR CONDENSER ENTERING AIR TEMPERA TURES °F 75 85 95 105 115 125 CFM EWB Capacity MBtuh† T otal Sys KW** Capaci.
—22— DETAILED COOLING CAPACITIES* Continued See notes on page 24. EV APORA TOR AIR CONDENSER ENTERING AIR TEMPERA TURES °F 75 85 95 105 115 125 CFM EWB Capacity MBtuh† T otal Sys KW** Capacity .
—23— DET AILED COOLING CAP A CITIES* Continued See notes on page 24. EV APORA TOR AIR CONDENSER ENTERING AIR TEMPERA TURES °F 75 85 95 105 115 125 CFM EWB Capacity MBtuh† T otal Sys KW** Capaci.
—24— DET AILED COOLING CAP A CITIES* Continued * Detailed cooling capacities are based on indoor and outdoor unit at the same ele vation per ARI standard 210/240-94. If additional tubing length and/or indoor unit is located abov e outdoor unit, a slight variation in capacity ma y occur .
—25— CONDENSER ONL Y RA TINGS* See notes on page 26. SST °F CONDENSER ENTERING AIR TEMPERA TURES °F 55 65 75 85 95 105 115 125 561C018-A, D 30 TCG 17.6 16.2 14.7 13.4 12.0 10.7 9.52 8.35 KW 1.37 1.49 1.58 1.66 1.73 1.77 1.80 1.82 SDT 75.6 86.1 96.
—26— CONDENSER ONL Y RA TINGS* Continued * ARI listing applies only to systems shown in Ratings and P erformance table . KW — T otal Po wer (Kw) SDT — Saturated T emperature Leaving Compressor.
—27— SYSTEM DESIGN 1. Intended for outdoor installation with free air inlet and outlet. Outdoor fan external static pressure av ailable is less than 0.01-in. wc. 2. Minimum outdoor operating air temperature without lo w-ambient operation accessor y is 55°F (12.
—2 8— SPECIFICATIONS SUBJECT TO CHANGE WITHOUT NOTICE UNIT MUST BE INSTALLED IN ACCORDANCE WITH INSTALLATION INSTRUCTIONS Cancels PDS 561C.18.5 © 1999 Bryant Heating & Cooling Systems, 7310 W. Morris St., Indpls., IN 46231 PRINTED IN U.S.A. Catalog No.
Een belangrijk punt na aankoop van elk apparaat Bryant ELECTRIC AIR CONDITIONER 561C (of zelfs voordat je het koopt) is om de handleiding te lezen. Dit moeten wij doen vanwege een paar simpele redenen:
Als u nog geen Bryant ELECTRIC AIR CONDITIONER 561C heb gekocht dan nu is een goed moment om kennis te maken met de basisgegevens van het product. Eerst kijk dan naar de eerste pagina\'s van de handleiding, die je hierboven vindt. Je moet daar de belangrijkste technische gegevens Bryant ELECTRIC AIR CONDITIONER 561C vinden. Op dit manier kan je controleren of het apparaat aan jouw behoeften voldoet. Op de volgende pagina's van de handleiding Bryant ELECTRIC AIR CONDITIONER 561C leer je over alle kenmerken van het product en krijg je informatie over de werking. De informatie die je over Bryant ELECTRIC AIR CONDITIONER 561C krijgt, zal je zeker helpen om een besluit over de aankoop te nemen.
In een situatie waarin je al een beziter van Bryant ELECTRIC AIR CONDITIONER 561C bent, maar toch heb je de instructies niet gelezen, moet je het doen voor de hierboven beschreven redenen. Je zult dan weten of je goed de alle beschikbare functies heb gebruikt, en of je fouten heb gemaakt die het leven van de Bryant ELECTRIC AIR CONDITIONER 561C kunnen verkorten.
Maar de belangrijkste taak van de handleiding is om de gebruiker bij het oplossen van problemen te helpen met Bryant ELECTRIC AIR CONDITIONER 561C . Bijna altijd, zal je daar het vinden Troubleshooting met de meest voorkomende storingen en defecten #MANUAl# samen met de instructies over hun opplosinge. Zelfs als je zelf niet kan om het probleem op te lossen, zal de instructie je de weg wijzen naar verdere andere procedure, bijv. door contact met de klantenservice of het dichtstbijzijnde servicecentrum.