Gebruiksaanwijzing /service van het product 09BY006-024 van de fabrikant Carrier
Ga naar pagina of 20
Installation, Start-Up and Service Instructions CONTENTS Page SAFETY CONSIDERA TIONS .................1 GENERAL ..................................1 INST ALLA TION ............................ 1-12 Step 1 − Complete Pre-Installation Checks ..1 Step 2 − Rig and Place Unit .
Fig. 1 — 09BY Unit (008-014 Shown) 2.
LEGEND Refrigerant Connection Field-Supplied Refrigerant Piping *Field-Supplied Floor Stand (Height to Match W all Opening). Fig. 2 — Mounting Applications 09BY DISCHARGE DUCT INLET DUCT TO OUTSIDE .
09BY DIMENSIONS (English) DIMENSION 006 (Ft-in.) 008 (Ft-in.) 012 (Ft-in.) 014 (Ft-in.) 016,024 (Ft-in.) A 2-1 1 1 ⁄ 2 3- 6 13 ⁄ 16 3- 6 13 ⁄ 16 3- 6 13 ⁄ 16 5- 0 B 1- 7 11 ⁄ 16 1-1 1 5 ⁄ .
NOTES: 1. Operational clearances are 0 in. on all sides of the unit. 2. Service clearances are 0 in. (minimum) on the top, rear , and front of the unit. A minimum of 3 ft service clearance is required on the unit right side, an da3f t clearance is recommended on the left side (2 ft is the minimum).
T able 1 — Condenser Unit Application UNIT 50BZ 09BY 006 008 012 014 016 024 006 S 008 S 012 OS 014 OS 016 OS 024 OS LEGEND S— Standard O— Optional NOTE: Contact your local representative for use with reciprocating air-cooled chillers and other compressor-bearing unit combinations.
Step 2 — Rig and Place Unit RIGGING — The 09BY units are mounted on skids. Leave the unit on the skid until it is in the final position. While on the skid, the unit can be rolled, dragged or forklifted; do not apply for ce to the unit.
Step 3 — Install Accessory Low-Ambient Kit or Inlet Filter Kit (If Required) — If the unit will be op- erated with inlet air to the condenser below 50 F , a low- ambient damper may be required. The low-ambient kit con- trols head pressure by discharge dampers on the condenser fan.
LIQUID LIFT — Amount of liquid lift available before re- frigerant flashing occurs depends on amount of liquid sub- cooling in the system. All 09BY condensers have positive subcooling when ap- plied with optimum charge.
CHECK V AL VE — When the 09BY condenser is installed with the condenser located above the compressor evapora- tor , it is recommended that a field-supplied check valve be installed on the hot gas discharge line. This prevents refrig- erant which condenses in the discharge line during the of f cycle from draining back into the compressor .
3. A high-density fiberglass (2 lb minimum density) or semi- rigid foamed insulation such as Styrofoam™ will be re- quired inside the ducts to prevent air erosion. The insu- lation must be firmly secured in the discharge duct near the blower discharge to withstand the high air velocity .
Determine maximum deviation from average voltage: (AB) 243 – 23 9=4v (BC) 239 – 23 6=3v (AC) 239 – 23 8=1v Maximum deviation is then 4 v . T o determine the percentage of voltage imbalance: 4 % V oltage Imbalance = 100 x 239 = 1.7% This amount of phase imbalance is satisfactory since it is below the allowable maximum of 2%.
ST ART -UP To prevent personal injury, be sure wire fan guards are secured in place over each fan discharge (or that fans are ducted) before starting the unit.
T able 5 — Condenser Fan Performance UNIT 09BY AIRFLOW (Cfm) EXTERNAL ST A TIC PRESSURE (in. wg) 0.0 0.2 0.4 0.6 0.8 1.0 Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp 006 2000 676 0.26 905 0.51 1085 0.80 1230 1.08 1348 1.34 1449 1.60 2500 845 0.51 1039 0.
TO CHANGE F AN WHEEL — If a fan wheel should fail, it may be replaced as follows: 1. Remove belts from fan pulley . 2. Loosen locking collars on the fan bearings and set screws on the fan wheels. 3. Remove the shaft through the access panel on either side of the unit.
TROUBLESHOOTING See T able 6 for problems and possible solutions. T a b l e6—T roubleshooting PROBLEM POTENTIAL CAUSE SOLUTION Unit is tripping on high-pressure switch or high discharge pressure is noted. 1. Fan belts are slipping or broken. 2. Fan is not delivering adequate air for condenser .
.
Copyright 1996 Carrier Corporation Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations. Book 2 4 Ta b 4 a 4 a PC 1 1 1 Catalog No. 530-969 Printed in U.S.A.
ST ART -UP CHECKLIST A. Preliminary Information COMPRESSOR BEARING UNIT : MODEL NO. SERIAL NO. 09BY UNIT : MODEL NO. SERIAL NO. FIELD-INST ALLED ACCESSORIES B. Pre-Start-Up CONDENSING UNIT IS THERE ANY SHIPPING DAMAGE? (Y/N) IF SO, WHERE: WILL THIS DAMAGE PREVENT UNIT ST ART -UP? (Y/N) CHECK POWER SUPPL Y .
CHECK VOL T AGE IMBALANCE IS CONDENSER MOTOR WIRED FOR CORRECT VOL T AGE? (Y/N) LINE-TO-LINE VOL TS: AB VA C VB C V (AB + AC + BC)/3 = A VERAGE VOL T AGE = V MAXIMUM DEVIA TION FROM A VERAGE VOL T AGE.
Een belangrijk punt na aankoop van elk apparaat Carrier 09BY006-024 (of zelfs voordat je het koopt) is om de handleiding te lezen. Dit moeten wij doen vanwege een paar simpele redenen:
Als u nog geen Carrier 09BY006-024 heb gekocht dan nu is een goed moment om kennis te maken met de basisgegevens van het product. Eerst kijk dan naar de eerste pagina\'s van de handleiding, die je hierboven vindt. Je moet daar de belangrijkste technische gegevens Carrier 09BY006-024 vinden. Op dit manier kan je controleren of het apparaat aan jouw behoeften voldoet. Op de volgende pagina's van de handleiding Carrier 09BY006-024 leer je over alle kenmerken van het product en krijg je informatie over de werking. De informatie die je over Carrier 09BY006-024 krijgt, zal je zeker helpen om een besluit over de aankoop te nemen.
In een situatie waarin je al een beziter van Carrier 09BY006-024 bent, maar toch heb je de instructies niet gelezen, moet je het doen voor de hierboven beschreven redenen. Je zult dan weten of je goed de alle beschikbare functies heb gebruikt, en of je fouten heb gemaakt die het leven van de Carrier 09BY006-024 kunnen verkorten.
Maar de belangrijkste taak van de handleiding is om de gebruiker bij het oplossen van problemen te helpen met Carrier 09BY006-024 . Bijna altijd, zal je daar het vinden Troubleshooting met de meest voorkomende storingen en defecten #MANUAl# samen met de instructies over hun opplosinge. Zelfs als je zelf niet kan om het probleem op te lossen, zal de instructie je de weg wijzen naar verdere andere procedure, bijv. door contact met de klantenservice of het dichtstbijzijnde servicecentrum.