58PAV, 58RAV Induced-Combustion Furnaces Service and Maintenance Instructions For Sizes 045-155, Series 131 NOTE: Read the entire instruction manual before performing any service or maintenance. This symbol → indicates a change since the last issue.
The ability to properly perform maintenance on this equip- ment requires certain expertise, mechanical skills, tools, and equipment. If you do not possess these, do not attempt to perform any maintenance on this equipment other than those procedures recommended in the User’s Manual.
Never operate unit without a filter or with filter access door removed. A failure to follow this warning could result in fire, personal injury, or death. 1. Downflow/Horizontal Each furnace requires 2 filters which are installed in the return-air duct.
9. Loosen setscrew holding blower wheel on motor shaft. 10. Remove bolts holding motor mount to blower housing and slide motor and mount out of housing. Disconnect ground wire attached to blower housing before removing motor. 11. Lubricate motor (when oil ports are provided).
8. Clean cells using field-provided small wire brush, steel spring cable, reversible electric drill, and vacuum cleaner. a. Assemble wire brush and steel spring cable. (1.) Use 48 in. of 1/4-in. diameter high-grade steel spring cable (commonly known as drain clean-out or Roto- Rooter cable).
ELECTRICAL CONTROLS AND WIRING There may be more than 1 electrical supply to the unit. Check accessories and cooling unit for additional electrical supplies. The electrical ground and polarity for 115-v wiring must be maintained properly. Refer to Fig.
Fig. 10—Heating and Cooling Application Wiring Diagram A78461 115-VOLT FIELD- SUPPLIED FUSED DISCONNECT AUXILIARY J-BOX CONTROL BOX 24-VOLT TERMINAL BLOCK TWO-WIRE HEATING-.
→ Fig. 12—Unit Wiring Diagram A94074 PCB BLO WER OFF DELAY SELE C TION C HART 90 SEC 135 SEC 180 SEC 225 SEC GVR HI/LO R E LAY SEC-1 SEC-2 PL 1 3 2 1 6 5 4 987 LED TEST/TWIN BLOW ER OFF D E LAY G .
Fig. 13—Service Label A93297 - Stuck gas valve relay on control or miswire to gas valve circuit. - Stuck-open gas valve or leaky gas valve. - Obstructed pressure tubing.- Defective pressure switch (stuck closed).
Close door switch and go to start. Is circuit breaker closed? Is red LED status light on? Is red LED status light blinking rapidly without a pause? Is door switch closed? Is there 115v going to switch? Replace control board.
11 NO PREVIOUS FAULT - Faults are erased after 48 hrs or whenever power (115V or 24V) is interrupted. Run system through a heating or cooling cycle to recheck system.
Copyright 1994 CARRIER Corp. • 7310 W. Morris St. • Indianapolis, IN 46231 58pr9sm Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations. Book 1 4 Tab 6a 8a PC 101 Catalog No.
Een belangrijk punt na aankoop van elk apparaat Carrier 58PAV (of zelfs voordat je het koopt) is om de handleiding te lezen. Dit moeten wij doen vanwege een paar simpele redenen:
Als u nog geen Carrier 58PAV heb gekocht dan nu is een goed moment om kennis te maken met de basisgegevens van het product. Eerst kijk dan naar de eerste pagina\'s van de handleiding, die je hierboven vindt. Je moet daar de belangrijkste technische gegevens Carrier 58PAV vinden. Op dit manier kan je controleren of het apparaat aan jouw behoeften voldoet. Op de volgende pagina's van de handleiding Carrier 58PAV leer je over alle kenmerken van het product en krijg je informatie over de werking. De informatie die je over Carrier 58PAV krijgt, zal je zeker helpen om een besluit over de aankoop te nemen.
In een situatie waarin je al een beziter van Carrier 58PAV bent, maar toch heb je de instructies niet gelezen, moet je het doen voor de hierboven beschreven redenen. Je zult dan weten of je goed de alle beschikbare functies heb gebruikt, en of je fouten heb gemaakt die het leven van de Carrier 58PAV kunnen verkorten.
Maar de belangrijkste taak van de handleiding is om de gebruiker bij het oplossen van problemen te helpen met Carrier 58PAV . Bijna altijd, zal je daar het vinden Troubleshooting met de meest voorkomende storingen en defecten #MANUAl# samen met de instructies over hun opplosinge. Zelfs als je zelf niet kan om het probleem op te lossen, zal de instructie je de weg wijzen naar verdere andere procedure, bijv. door contact met de klantenservice of het dichtstbijzijnde servicecentrum.