Installation, Start-Up and Service Instructions CONTENTS Page GENERAL ...................................2 SAFETY CONSIDERA TIONS ...................2 INST ALLA TION ............................. 2-37 Rigging and Unit Placement ..................2 Roof Curb .
CONTENTS (cont) • AUTOMA TIC PILOT ADJUSTMENT (48 Series Units Only) • GAS V AL VE ADJUSTMENT (48 Series Units Only) • MAIN BURNER ADJUSTMENT (48 Series Units Only) Main Burner Removal (48 Series Units Only) ..5 0 Switch Adjustment .............
If roof curb is not used, support unit with steel beams along its entire length and then support steel as required. As a mini- mum, unit must be supported across its width at each lifting lug location. Positioning — Provide clearance around and above unit for airflow , safety , and service access.
T able 1A — Physical Data; 034, 044 Units BASE UNIT* 034 044 NOMINAL CAP ACITY (tons) 30 40 OPERA TING WEIGHT (lb) Base Unit 48 Series, Low Heat 5641 6541 48 Series, High Heat 5770 6670 50 Series, H.
T able 1B — Physical Data; 054-074 Units BASE UNIT* 054 064 074 NOMINAL CAP ACITY (tons) 50 60 75 OPERA TING WEIGHT (lb) Base Unit 48 Series, Low Heat 8700 9000 9420 48 Series, High Heat 8820 9120 9.
T able 2 — Operating Weights of Options and Accessories OPTION OR ACCESSORY UNIT SIZE 034 044 054 064 074 Roof Curb 48DJ,DK,NP 50DW ,DY ,NB 50DJ,DK,NP 450 450 380 480 480 465 515 560 515 515 560 515.
UNIT MODEL UNIT SIZE XY mm ft-in. mm ft-in. 48DJ,DK,NP 034 6606 21-8 1 ⁄ 16 4056 13- 3 11 ⁄ 16 50DW ,DY ,NB 034 50DJ,DK,NP 034 6131 20-1 3 ⁄ 8 331 1 10-10 3 ⁄ 8 48DJ,DK,NP 044 7825 25-8 1 ⁄ .
UNIT MODEL UNIT SIZE XY Z mm ft-in. mm ft-in. mm ft-in. 48DJ,DK,NP 054,064 2474 8-1 3 ⁄ 8 8476 27-9 11 ⁄ 16 6965 22-10 3 ⁄ 16 50DW ,DY ,NB 054,064 50DJ,DK,NP 054,064 2458 8-0 3 ⁄ 4 7444 24-5 1.
UNIT SIZE DIMENSION X mm Ft-in. 054,064 270 0-10 5 ⁄ 8 074 255 0-10 1 ⁄ 16 UNIT LEVELING TOLERANCES DIMENSIONS* (degrees and inches) AB Deg in. Deg in. 1.0 2.0 .50 .75 *From edge of unit to horizontal. NOTE: T o prevent the hazard of stagnant water build-up in the drain pan of the indoor-air section, unit can only be pitched as shown.
Condensate Drains — See Fig. 4A-4D and Fig. 5 for drain locations. The drain assemblies, each consisting of a 10-gage plate with a 1 1 ⁄ 4 -in. half coupling welded to it, are shipped in the unit fan section. Also included are 16-gage seal plates to cover the drain holes not being used.
UNIT SIZE WEIGHT A B C D E F G H J lb kg mm ft-in. mm ft-in. mm ft-in. mm ft-in. mm ft-in. mm ft-in. mm ft-in. mm ft-in. mm ft-in. 48DJD,DKD,NPD 034 5641 2559 4498 14-9 1 ⁄ 8 3662 12-0 3 ⁄ 16 7278.
UNIT SIZE WEIGHT A B C D E F G H lb kg mm ft-in. mm ft-in. mm ft-in. mm ft-in. mm ft-in. mm ft-in. mm ft-in. mm ft-in. 50DJ,DK,NP 034 5400 2449 4198 13-9 1 ⁄ 4 2916 9-6 13 ⁄ 16 6802 22-3 13 ⁄ 16.
UNIT SIZE WEIGHT A B C D E F G lb kg mm ft-in. mm ft-in. mm ft-in. mm ft-in. mm ft-in. mm ft-in. mm ft-in. 48DJD,DKD,NPD 054 8700 3946 5969 19-7 6717 22-0 7 ⁄ 16 1 163 3-9 13 ⁄ 16 1 1,524 37-9 11 .
UNIT SIZE Weight A B C D E F Lb Kg mm ft-in. mm ft-in. mm ft-in. mm ft-in. mm ft-in. mm ft-in. 50DJ,DK,NP 054 7700 3493 5537 18-2 1 163 3-9 13 ⁄ 16 10,476 34-4 7 ⁄ 16 2864 9-4 3 ⁄ 4 10,092 33-1 .
034 UNITS 044-074 UNITS Fig. 5 — Drain Location Selection Fig. 6 — Condensate Drain Location Fig. 7 — Seal Plate Location ROOF MOUNT DRAIN SLAB MOUNT DRAIN Fig.
Fig. 10 — Outdoor-Air Damper Adjustments (Inside of Hood Shown) O ENTHALPY SENSOR Fig. 1 1 — Enthalpy Sensor Fig. 12 — Enthalpy Sensor Location CONTROL CURVE CONTROL POINT (Approx Deg) A T 50% RH A 73 B 68 C 63 D 58 Fig.
Field Wire Routing UNIT SIZES 034 AND 044 — Field wiring can be brought into the unit through the basepan and roof curb or through the corner post in the side of the unit next to the control box. A 3-1/2 in. NPT coupling for field power and a 3/4-in.
POWER WIRING — Units are factory wired for the voltage shown on the unit nameplate. The main terminal block is suitable for use with aluminum or copper wires.
T able 3 — Electrical Data, 034 Units 208/230-3-60 (V -Ph-Hz) VOL T AGE RANGE COMPR NO. 1 COMPR NO. 2 OFM IFM BASE UNIT ONL Y EXHAUST FA N ELECTRIC HEA T* BASE UNIT WITH EXHAUST F AN AND/OR ELECTRIC HEA T* RLA LRA RLA LRA T otal FLA Hp FLA MCA MOCP T otal Hp T otal FLA kW FLA MCA MOCP 187-254 53.
T able 3 — Electrical Data, 034 Units (cont) 460-3-60 (V -Ph-Hz) VOL T AGE RANGE COMPR NO. 1 COMPR NO. 2 OFM IFM BASE UNIT ONL Y EXHAUST FA N ELECTRIC HEA T* BASE UNIT WITH EXHAUST F AN AND/OR ELECTRIC HEA T* RLA LRA RLA LRA T otal FLA Hp FLA MCA MOCP T otal Hp T otal FLA kW FLA MCA MOCP 414-508 28.
T able 3 — Electrical Data, 034 Units (cont) 575-3-60 (V -Ph-Hz) VOL T AGE RANGE COMPR NO. 1 COMPR NO. 2 OFM IFM BASE UNIT ONL Y EXHAUST FA N ELECTRIC HEA T* BASE UNIT WITH EXHAUST F AN AND/OR ELECTRIC HEA T* RLA LRA RLA LRA T otal FLA Hp FLA MCA MOCP T otal Hp T otal FLA kW FLA MCA MOCP 518-632 23.
T able 4 — Electrical Data, 044 Units 208/230-3-60 (V -Ph-Hz) VOL T AGE RANGE COMPR NO. 1 COMPR NO. 2 OFM IFM BASE UNIT ONL Y EXHAUST FA N ELECTRIC HEA T* BASE UNIT WITH EXHAUST F AN AND/OR ELECTRIC HEA T* RLA LRA RLA LRA T otal FLA Hp FLA MCA MOCP T otal Hp T otal FLA kW FLA MCA MOCP 187-254 69.
T able 4 — Electrical Data, 044 Units (cont) 460-3-60 (V -Ph-Hz) VOL T AGE RANGE COMPR NO. 1 COMPR NO. 2 OFM IFM BASE UNIT ONL Y EXHAUST FA N ELECTRIC HEA T* BASE UNIT WITH EXHAUST F AN AND/OR ELECTRIC HEA T* RLA LRA RLA LRA T otal FLA Hp FLA MCA MOCP T otal Hp T otal FLA kW FLA MCA MOCP 414-508 34.
T able 4 — Electrical Data, 044 Units (cont) 575-3-60 (V -Ph-Hz) VOL T AGE RANGE COMPR NO. 1 COMPR NO. 2 OFM IFM BASE UNIT ONL Y EXHAUST FA N ELECTRIC HEA T* BASE UNIT WITH EXHAUST F AN AND/OR ELECTRIC HEA T* RLA LRA RLA LRA T otal FLA Hp FLA MCA MOCP T otal Hp T otal FLA kW FLA MCA MOCP 518-632 26.
T able 5 — Electrical Data, 054 Units 208/230-3-60 (V -Ph-Hz) VOL T AGE RANGE COMPR NO. 1 COMPR NO. 2 OFM IFM BASE UNIT ONL Y EXHAUST FA N ELECTRIC HEA T* BASE UNIT WITH EXHAUST F AN AND/OR ELECTRIC HEA T* RLA LRA RLA LRA T otal FLA Hp FLA MCA MOCP T otal Hp T otal FLA kW FLA MCA MOCP 187-254 107.
T able 5 — Electrical Data, 054 Units (cont) 460-3-60 (V -Ph-Hz) VOL T AGE RANGE COMPR NO. 1 COMPR NO. 2 OFM IFM BASE UNIT ONL Y EXHAUST FA N ELECTRIC HEA T* BASE UNIT WITH EXHAUST F AN AND/OR ELECTRIC HEA T* RLA LRA RLA LRA T otal FLA Hp FLA MCA MOCP T otal Hp T otal FLA kW FLA MCA MOCP 414-508 50.
T able 5 — Electrical Data, 054 Units (cont) 575-3-60 (V -Ph-Hz) VOL T AGE RANGE COMPR NO. 1 COMPR NO. 2 OFM IFM BASE UNIT ONL Y EXHAUST FA N ELECTRIC HEA T* BASE UNIT WITH EXHAUST F AN AND/OR ELECTRIC HEA T* RLA LRA RLA LRA T otal FLA Hp FLA MCA MOCP T otal Hp T otal FLA kW FLA MCA MOCP 518-632 39.
T able 6 — Electrical Data, 064 Units 208/230-3-60 (V -Ph-Hz) VOL T AGE RANGE COMPR NO. 1 COMPR NO. 2 OFM IFM BASE UNIT ONL Y EXHAUST FA N ELECTRIC HEA T* BASE UNIT WITH EXHAUST F AN AND/OR ELECTRIC HEA T* RLA LRA RLA LRA T otal FLA Hp FLA MCA MOCP T otal Hp T otal FLA kW FLA MCA MOCP 187-254 107.
T able 6 — Electrical Data, 064 Units (cont) 460-3-60 (V -Ph-Hz) VOL T AGE RANGE COMPR NO. 1 COMPR NO. 2 OFM IFM BASE UNIT ONL Y EXHAUST FA N ELECTRIC HEA T* BASE UNIT WITH EXHAUST F AN AND/OR ELECTRIC HEA T* RLA LRA RLA LRA T otal FLA Hp FLA MCA MOCP T otal Hp T otal FLA kW FLA MCA MOCP 414-508 50.
T able 6 — Electrical Data, 064 Units (cont) 575-3-60 (V -Ph-Hz) VOL T AGE RANGE COMPR NO. 1 COMPR NO. 2 OFM IFM BASE UNIT ONL Y EXHAUST FA N ELECTRIC HEA T* BASE UNIT WITH EXHAUST F AN AND/OR ELECTRIC HEA T* RLA LRA RLA LRA T otal FLA Hp FLA MCA MOCP T otal Hp T otal FLA kW FLA MCA MOCP 518-632 39.
T able 7 — Electrical Data, 074 Units 208/230-3-60 (V -Ph-Hz) VOL T AGE RANGE COMPR NO. 1 COMPR NO. 2 OFM IFM BASE UNIT ONL Y EXHAUST FA N ELECTRIC HEA T* BASE UNIT WITH EXHAUST F AN AND/OR ELECTRIC HEA T* RLA LRA RLA LRA T otal FLA Hp FLA MCA MOCP T otal Hp T otal FLA kW FLA MCA MOCP 187-254 107.
T able 7 — Electrical Data, 074 Units (cont) 460-3-60 (V -Ph-Hz) VOL T AGE RANGE COMPR NO. 1 COMPR NO. 2 OFM IFM BASE UNIT ONL Y EXHAUST FA N ELECTRIC HEA T* BASE UNIT WITH EXHAUST F AN AND/OR ELECTRIC HEA T* RLA LRA RLA LRA T otal FLA Hp FLA MCA MOCP T otal Hp T otal FLA kW FLA MCA MOCP 414-508 50.
T able 7 — Electrical Data, 074 Units (cont) 575-3-60 (V -Ph-Hz) VOL T AGE RANGE COMPR NO. 1 COMPR NO. 2 OFM IFM BASE UNIT ONL Y EXHAUST FA N ELECTRIC HEA T* BASE UNIT WITH EXHAUST F AN AND/OR ELECTRIC HEA T* RLA LRA RLA LRA T otal FLA Hp FLA MCA MOCP T otal Hp T otal FLA kW FLA MCA MOCP 518-632 39.
CONTROL WIRING — Install a Carrier-approved acces- sory 24-v thermostat assembly according to the installation instructions shipped with the accessory . Locate thermostat assembly to sense average temperature. Route thermostat cable or equivalent leads of colored wire from subbase terminals to terminal board (P1).
034 AND 044 UNITS BASE UNIT OPTIONAL MODULA TING POWER EXHAUST OPTIONAL NON-MODULA TING EXHAUST 054-074 UNITS BASE UNIT BASE UNIT OPTIONAL MODULA TING POWER EXHAUST OPTIONAL NON-MODULA TING EXHAUST Fig.
Gas Piping (48 Series Units Only) — Unit is equipped for use with natural gas only . Installation must conform with local building codes, or in the absence of local codes, with the National Fuel Gas Code, ANSI Z223.
Fig. 24 — Flue Hood FLUE DEFLECTOR BAFFLE (BOTTOM HOOD ONL Y) FLUE DEFLECTOR BAFFLE (BOTH HOODS) FLUE DEFLECTOR HOOD Fig. 25 — Flue Deflector Baff les, 034,044 Units TOP (WHEN INST ALLED) FLUE DEFLECTOR BAFFLE FOR BOTTOM HOOD ONL Y Fig.
PRE-ST ART -UP Unit Preparation — Check to see that unit has been installed in accordance with these Installation Instructions and all applicable codes. Compressor Mounting — Loosen compressor hold- down bolts until sidewise movement of the washer under each holddown bolt head can be obtained.
If oil charge is above sight glass, do not remove any oil until the compressor crankcase heater has been on for at least 24 hours. When additional oil or a complete char ge is needed, use only Carrier-approved compressor oil. Approved oils: T exaco, Inc.
T able 9B — Field-Supplied Evaporator-Fan Pulley Data, 054-074 Units IFM Hp IFM RPM MOTOR PULLEY BLOWER PULLEY BEL TS 48 Series and 50 Series Horizontal Discharge Units 50 Series V ertical Discharge Units No. Grooves T ype Size (in.) No. Grooves T ype Size (in.
Initial Check IMPOR T ANT : Do not attempt to start unit, even mo- mentarily , until all items on the Start-Up Checklist and the following steps have been completed. 1. V erify unit has been installed per the Installation section of this literature. 2.
When the first-stage thermostat is satisfied, first-stage main gas valve and the pilot valve close. Induced-draft motor shuts of f. T ime-delay relay (built into constant volume control board) opens and timer sequence begins. When sequence is com- plete (after 1 10 ± 5 seconds) evaporator-fan motor shuts of f.
LIQUID SER VICE V AL VES, FIL TER DRIERS, AND SIGHT GLASSES Sizes 034 and 044 — Access to these components is through the access panel on the right side of the unit. See Fig. 34. There is also a Schrader port in each suction line that is ac- cessible through this same panel.
ECONOMIZER DAMPER MOTOR — On units so equipped, the economizer motor is located in the mixing box section. Access to it is through the doors labeled FIL TER SECTION on the sides of the unit.
NOTE: Only the heater element contactors are located in the heater box. The heaters are located in the unit airstream. 25% OUTDOOR-AIR DAMPER — Access to adjust the damper is through the hoods. Remove filters to gain access into unit to adjust linkage arms.
Adjustments EV APORA TOR F AN AND POWER EXHAUST MOTOR PLA TE — Adjust using a 15 ⁄ 16 -in. wrench on the adjusting bolts: 1. Loosen holddown bolts. (See Fig. 44.) 2. T urn the adjusting bolts to move the motor mounting plate toward or away from the fan to loosen or tighten the belts.
25% OUTDOOR-AIR DAMPER — See Manual Outdoor- Air Damper section on page 10 for adjustment details. REFRIGERANT CHARGE — All units are shipped with a complete operating charge of R-22.
Fig. 49 — Charging Chart, 034 Units; System 2, All Condenser Fans Running Fig. 50 — Charging Chart, 044 Units; System 1, One Condenser Fan Running Fig. 51 — Charging Chart, 044 Units; System 1, All Condenser Fans Running Fig. 52 — Charging Chart, 044 Units; System 2, One Condenser Fan Running Fig.
AUTOMA TIC PILOT ADJUSTMENT (48 Series Units Only) 1. Set system selector switch at OFF position to shut of f unit. T urn of f power to unit. 2. Remove screw cap cover on pilot gas valve to expose adjusting screw . 3. T o ensure that main burners do not ignite, remove wire from gas valve terminal 2.
GAS V AL VE ADJUSTMENT (48 Series Units Only) — The gas valve opens and closes in response to the thermostat or limit control. When power is supplied to valve terminal 3 (D1 on low heat), the pilot valve opens to the preset posi- tion. When power is supplied to terminal 2 (W1 on low heat), the main valve opens to its preset position.
Moisture/Liquid Indicator — A clear flow of liquid refrigerant indicates suf f icient charge in the system. Bubbles indicate undercharged system or the presence of noncon- densables.
T able 1 1 — Pressure Switch Settings (psig) SWITCH CUTOUT CUT -IN High 426 6 7 320 6 20 Low 27 6 46 7 6 7 Control Circuit, 1 15 V — This control circuit is pro- tected against overcurrent by a 5-amp circuit breaker . Breaker can be reset. If it trips, determine cause of trouble before resetting.
T able 14 — Economizer Control Board Checkout, T est 2 MOTOR TEST PROCEDURE EXPECTED RESUL T AND RESPONSE A T urn enthalpy set point potentiometer to the A position. 1. The relays energize. If not, check return enthalpy re- sistor . If resistor is o.
Symptom: Evaporator fan will not operate. 1. T urn unit power of f and disconnect plug P1 from the con- trol board. 2. Install a jumper across Pin R and Pin G at plug P1 on the control board. 3. T urn unit power on and check if the indoor (evaporator) fan contactor (IFC) coil has been pulled in.
c. If proper voltage is indicated at the contactor and con- tactor closes, the board is operating properly . 8. T o verify compressor lockout logic: a. Disconnect CLO sensor wires connected to CLO1 at the control board. Check wires for continuity . If there is no continuity , replace the sensor .
LEGEND CLO — Compressor Lockout P— Plug SC — Safety Circuit Fig. 65 — Compressor Lockout Connections 56.
LEGEND FOR FIG. 66-73 ACC — Accessory BP — Building Pressure C— Contactor CB — Circuit Breaker CCB — Control Circuit Breaker CF — Check Filter Switch CLO — Compressor Lockout COM — Com.
Fig. 66 — Gas Heat Sections; 48DJ,NP034,044 Units 58.
Fig. 67 — Gas Heat Sections; 48DJ,NP054-074 Units 59.
Fig. 68 — Gas Heat Section; 48DK034,044 Units 60.
Fig. 69 — Gas Heat Section; 48DK054-074 Units 61.
Fig. 70 — T ypical Wiring Schematic; 48/50DJ,50DW Units (054-074 Shown) 62.
Fig. 70 — T ypical Wiring Schematic; 48/50DJ,50DW Units (054-074 Shown) (cont) 63.
Fig. 71 — T ypical Wiring Schematic; 48/50DK,50DY Units (054-074 Shown) 64.
Fig. 71 — T ypical Wiring Schematic; 48/50DK,50DY Units (054-074 Shown) (cont) 65.
Fig. 72 — T ypical Control Wiring Schematic; 48/50NP ,50NB Units (054-074 Shown) 66.
Fig. 72 — T ypical Control Wiring Schematic; 48/50NP ,50NB Units (054-074 Shown) (cont) 67.
Fig. 72 — T ypical Control Wiring Schematic; 48/50NP ,50NB Units (054-074 Shown) (cont) 68.
Fig. 73 — T ypical Power Wiring Schematic; 48/50NP ,50NB Units (054-074, 208/230 and 460 v Shown) 69.
P ACKAGED SER VICE TRAINING Our packaged service training programs provide an excellent way to increase your knowledge of the equipment discussed in this manual. Product programs cover: • Unit Familiarization • Maintenance • Installation Overview • Operating Sequence A lar ge selection of product, theory , and skills programs is available.
.
ST ART -UP CHECKLIST MODEL NO.: DA TE: SERIAL NO.: TECHNICIAN: PRE-ST ART -UP: M VERIFY THA T ALL P ACKING MA TERIALS HA VE BEEN REMOVED FROM UNIT M LOOSEN ALL SHIPPING HOLDDOWN BOL TS AND REMOVE SHIP.
Een belangrijk punt na aankoop van elk apparaat Carrier NP034-074 (of zelfs voordat je het koopt) is om de handleiding te lezen. Dit moeten wij doen vanwege een paar simpele redenen:
Als u nog geen Carrier NP034-074 heb gekocht dan nu is een goed moment om kennis te maken met de basisgegevens van het product. Eerst kijk dan naar de eerste pagina\'s van de handleiding, die je hierboven vindt. Je moet daar de belangrijkste technische gegevens Carrier NP034-074 vinden. Op dit manier kan je controleren of het apparaat aan jouw behoeften voldoet. Op de volgende pagina's van de handleiding Carrier NP034-074 leer je over alle kenmerken van het product en krijg je informatie over de werking. De informatie die je over Carrier NP034-074 krijgt, zal je zeker helpen om een besluit over de aankoop te nemen.
In een situatie waarin je al een beziter van Carrier NP034-074 bent, maar toch heb je de instructies niet gelezen, moet je het doen voor de hierboven beschreven redenen. Je zult dan weten of je goed de alle beschikbare functies heb gebruikt, en of je fouten heb gemaakt die het leven van de Carrier NP034-074 kunnen verkorten.
Maar de belangrijkste taak van de handleiding is om de gebruiker bij het oplossen van problemen te helpen met Carrier NP034-074 . Bijna altijd, zal je daar het vinden Troubleshooting met de meest voorkomende storingen en defecten #MANUAl# samen met de instructies over hun opplosinge. Zelfs als je zelf niet kan om het probleem op te lossen, zal de instructie je de weg wijzen naar verdere andere procedure, bijv. door contact met de klantenservice of het dichtstbijzijnde servicecentrum.