Gebruiksaanwijzing /service van het product OMNIZONE 50XCA06-24 van de fabrikant Carrier
Ga naar pagina of 36
Copyright 2010 Carrier Cor poration Form 50XCA-1PD The 50XCA single-pac kage cooling units with integ ral air-cooled condensers off er : • Compact, dur able , and attr active cabinet fits an y worki.
2 The compact footprint and service from the front of the units save valu- able floor space in equipment rooms. Belt drive condensers provide adequate static to overcome ducting and louver static losses. This allows units to be po- sitioned against an existing window or wall louver , or ducted to the outside, as required.
3 AHRI* capacity ratings LEGEND *AHRI — Air Conditioning, Heating, and Refrigeration Institute. NO TE: Unit is tested in acco rdance with AHRI standard 340/360. UNIT 50XCA NOMINAL TO N S EV APORA T OR CFM CONDENSER CFM NET COOLING (Btuh) TOT A L kW EER IEER 06 5 1,875 2,800 65,000 5.
4 LEGEND UNIT 50XCA 06 08 12 14 16 24 NOMINAL CAP ACITY (tons) 57 1 / 2 10 12 15 20 UNIT OPERA TING WEIGHT (lb) 891 1144 1269 1298 1575 2000 COMPRESSOR Copeland S croll Compressor Model ZP57 ZP67 ZP51 ZP57 ZP72 ZP103 Qty 112222 Steps of Control 112222 Operating Charge R-410A (lb ) 17.
5 50XCA06 Q P O N Q 50XCA08,12,14 Q N P N O Q RIGHT VIEW TOP VIEW REAR VIEW EVAP ACCESS TOP VIEW PANEL CONDENSER ACCESS PANEL INDOOR SUPPLY AIR FLOW R G F K J H R U M A I T S U L FRONT VIEW CONTROL BOX DISCONNECT (OPT) AIR FLOW (BOTH SIDES) OUTDOOR RTN AIR FLOW FILTER ACCESS INDOOR RTN CONDENSER DISCHARGE COND VFD (OPT) C B E D 6.
6 C 4.9 (1"-2" FLTR) E D B 1.2 OUTDOOR RTN AIR FLOW INDOOR RTN AIR FLOW FILTER ACCESS (BOTH SIDES) COND VFD (OPT) A F I G H T U V S S S V K J M L 13.2 N N N Q Q O R R P SS V V T U TOP VIEW RIGHT VIEW REAR VIEW INDOOR SUPPLY AIR FLOW CONDENSER DISCHARGE REAR VIEW 50XCA24 50XCA16 NO TE: Dimensions are in inches.
7 Selection pr ocedure (50XCA08 unit example) I Determine design conditions. Given: Cooling Requir ements T otal Cooling Capacity (TC) . . . . . . . . . 82,000 Btuh Sensible Cooling Capacity (SHC) . . . . . 65,000 Btuh Evaporator Air Quantity . . . . .
8 GROSS COOLING CAP ACITIES LEGEND 50XCA06 (5 T ONS) Entering Condenser Air AIR ENTERING EV APORA TOR — 80 F Edb (F) - CFM 2500 2000 1500 Air Entering Ev aporator — Ewb (F) ECT (F) CFM 57 62 67 75 57 62 67 75 57 62 67 75 BF 0.20 0.10 0.10 0. 03 0.
9 GROSS COOLING CAP ACITIES (cont) LEGEND 50XCA08 (7 1 / 2 T ons) Entering Condenser Air AIR ENTERING EV APORA TOR — 80 F Edb (F) - CFM 3750 3000 2250 Air Entering Ev aporator — Ewb (F) ECT (F) CFM 57 62 67 75 57 62 67 75 57 62 67 75 BF 0.30 0.11 0.
10 GROSS COOLING CAP ACITIES (cont) LEGEND 50XCA12 (10 T ONS) Entering Condenser Air AIR ENTERING EV APORA TOR — 80 F Edb (F) - CFM 5000 4000 3000 Air Entering Ev aporator — Ewb (F) ECT (F) CFM 57 62 67 75 57 62 67 75 57 62 67 75 BF 0.23 0.06 0.05 0.
11 GROSS COOLING CAP ACITIES (cont) LEGEND 50XCA14 (12 T ONS) Entering Condenser Air AIR ENTERING EV APORA TOR — 80 F Edb (F) - CFM 6000 4800 3600 Air Entering Ev aporator — Ewb (F) ECT (F) CFM 57 62 67 75 57 62 67 75 57 62 67 75 BF 0.24 0.09 0.08 0.
12 GROSS COOLING CAP ACITIES (cont) LEGEND 50XCA16 (15 T ONS) Entering Condenser Air AIR ENTERING EV APORA TOR — 80 F Edb (F) - CFM 7500 6000 4500 Air Entering Ev aporator — Ewb (F) ECT (F) CFM 57 62 67 75 57 62 67 75 57 62 67 75 BF 0.26 0.06 0.05 0.
13 GROSS COOLING CAP ACITIES (cont) LEGEND 50XCA024 (20 T O NS) Entering Condenser Air AIR ENTERING EV APORA TOR — 80 F Edb (F) - CFM 10,000 8,000 6,000 Air Entering Ev aporator — Ewb (F) ECT (F) CFM 57 62 67 75 57 62 67 75 57 62 67 75 BF 0.22 0.06 0.
14 CONDENSER F AN PERFORMANCE LEGEND Bhp — Brake Horsepo wer ESP — External S tatic Pr essure NO TE S : 1. Units are availab le with se veral motor hp options . Refer to the physical data tab le. 2. S tatic pressure losses must be appl ied to e xter nal static pressure before entering the f an performance table .
15 CONDENSER F AN PERFORMANCE (cont) LEGEND Bhp — Brake Horsepo wer ESP — External S tatic Pr essure NO TE S : 1. Units are availab le with sev eral motor hp options. Ref er to the physical data tab le. 2. S tatic pressure losses must be appl ied to external static pressure before entering the f an performance table .
16 CONDENSER F AN PERFORMANCE (cont) LEGEND Bhp — Brake Horsepo wer ESP — External S tatic Pr essure NO TE S : 1. Units are availab le with se veral motor hp options . Refer to the physical data tab le. 2. S tatic pressure losses must be appl ied to e xter nal static pressure before entering the f an performance table .
17 CONDENSER F AN PERFORMANCE (cont ) LEGEND Bhp — Brake Horsepo wer ESP — External S tatic Pr essure NO TE S : 1. Units are availab le with sev eral motor hp options. Ref er to the physical data tab le. 2. S tatic pressure losses must be appl ied to external static pressure before entering the f an performance table .
18 CONDENSER F AN PERFORMANCE (cont ) LEGEND Bhp — Brake Horsepo wer ESP — External S tatic Pr essure NO TE S : 1. Units are availab le with se veral motor hp options . Refer to the physical data tab le. 2. S tatic pressure losses must be appl ied to e xter nal static pressure before entering the f an performance table .
19 CONDENSER F AN PERFORMANCE (cont) LEGEND Bhp — Brake Horsepo wer ESP — External S tatic Pr essure NO TE S : 1. Units are availab le with sev eral motor hp options. Ref er to the physical data tab le. 2. S tatic pressure losses must be appl ied to external static pressure before entering the f an performance table .
20 EV APORA TOR F AN PERFORMANCE LEGEND Bhp — Brake Horsepo wer ESP — External S tatic Pr essure NO TE S : 1. Units are availab le with se veral motor hp options . Refer to the physical data tab le. 2. S tatic pressure losses must be appl ied to e xter nal static pressure before entering the f an performance table .
21 EV APORA TOR F AN PERFORMANCE (cont) LEGEND Bhp — Brake Horsepo wer ESP — External S tatic Pr essure NO TE S : 1. Units are availab le with sev eral motor hp options. Ref er to the physical data tab le. 2. S tatic pressure losses must be appl ied to external static pressure before entering the f an performance table .
22 EV APORA TOR F AN PERFORMANCE (cont ) LEGEND Bhp — Brake Horsepo wer ESP — External S tatic Pr essure NO TE S : 1. Units are availab le with se veral motor hp options . Refer to the physical data tab le. 2. S tatic pressure losses must be appl ied to e xter nal static pressure before entering the f an performance table .
23 EV APORA TOR F AN PERFORMANCE (cont) LEGEND Bhp — Brake Horsepo wer ESP — External S tatic Pr essure NO TE S : 1. Units are availab le with sev eral motor hp options. Ref er to the physical data tab le. 2. S tatic pressure losses must be appl ied to external static pressure before entering the f an performance table .
24 EV APORA TOR F AN PERFORMANCE (cont ) LEGEND Bhp — Brake Horsepo wer ESP — External S tatic Pr essure NO TE S : 1. Units are availab le with se veral motor hp options . Refer to the physical data tab le. 2. S tatic pressure losses must be appl ied to e xter nal static pressure before entering the f an performance table .
25 EV APORA TOR F AN PERFORMANCE (cont) LEGEND Bhp — Brake Horsepo wer ESP — External S tatic Pr essure NO TE S : 1. Units are availab le with sev eral motor hp options. Ref er to the physical data tab le. 2. S tatic pressure losses must be appl ied to external static pressure before entering the f an performance table .
26 UNIT ELECTRICAL DA T A LEGEND NO TE S : 1. In compliance with NEC requirements for multimotor and combination load equipment (NEC Ar ticles 430 and 440), the overcurrent prot ectiv e device f or the unit shall be fuse or HACR circuit break er. Canadian units ma y be fuse or circuit breaker .
27 F AN ELECTRICAL DA T A LEGEND MO TOR CODE HP V -PH- Hz VO L T AG E RANGE FLA Min Max B0 . 5 0 208/230-3-60 187 253 1.8/2.2 460-3-60 414 506 1.1 575-3-60 518 632 — C0 . 7 5 208/230-3-60 187 253 2.5/2.6 460-3-60 414 506 1.3 575-3-60 518 632 1 D1 . 0 0 208/230-3-60 187 253 3.
28 IFM COMP1 12 1 / BLK 12 3 / BL U 12 2 / YE L 11 8 / BLK 12 0 / BL U 11 9 / YE L C1 12 5 / BLK 12 6 / BLK C H 1 TB1 CL O 1-Loo p 10 3 / BLK 10 4 / YE L 10 5 / BL U 10 6 / BLK 10 7 / YE L 10 8 / BL U.
29 TB 3 3 LOGI C 1 2 CL O 1 HP S 1 FR Z 1 LP S 1 T B 2 A B C1 52 3 BLU 52 4 BL U 52 8 BR N 52 7 BL U 52 2 BL U 52 9 BR N R C G A B IF C Y 1 52 9 BR N 52 6 BLK 52 5 BLK 96 95 IFR Y 2 1 3 CR1 50 9 BR N .
30 Operating sequence All units require the addition of a ther mostat accessory package to complete the control circuit. The sequence of operation may vary depending on which package is selected. Room-mounted the rmostat — The unit uses an electronic ther mostat mounted in the conditioned space.
31 LEGEND NO TE S : 1. Wiring and piping shown are general points of connection guides only and are not intended for or to include al l details for a specific installation. 2. All wiring must comply with applicable local and national codes. 3. All piping must f ollow standard piping techn iques.
32 Location For best results unit must b e properly located and installed. Selected location should not be adjacent to an acoustically sensitive space, for example a co nference room or execu- tive office. The best location is in mechanical rooms near areas like elevators, restrooms, stairways, or similar spaces.
33 Setting condenser fan speed The 50XCA condenser has a centrifugal blower and a vari- able pitch drive which allow adjusting the condenser air flow to match the static from the louvers, ductwork, filters, and sound traps (if used). It is best to adjust the fan to the nominal air flow and th e rpm which will achieve this per for mance.
34 Indoor Self-Contain ed Air-Cooled Unit Constant V olume Application HV AC Guide Specifications Size Range: 5 to 20 T ons Carrier Model Number: 50XCA Part 1 — General 1.01 SYSTEM DESCRIPTION Indoor pack aged vertical air -cooled cooling unit using her metic scroll compressors and built-in con- denser fan for cooling duty .
35 ambient. Units shall be able to o perate down to 0° F when equipped with low ambient option. I. Controls and Safeties: 1. Units shall be furnished with a co ntrol ter minal block for connection of low voltage contro ls and ther mostats. 2. Unit shall require a room-mounted ther mostat mounted in the conditioned space.
Manufacturer reserves the right to dis continue, or change at any time, specifications or designs without not ice and without inc urring obligations. Pg 36 Catalog No .
Een belangrijk punt na aankoop van elk apparaat Carrier OMNIZONE 50XCA06-24 (of zelfs voordat je het koopt) is om de handleiding te lezen. Dit moeten wij doen vanwege een paar simpele redenen:
Als u nog geen Carrier OMNIZONE 50XCA06-24 heb gekocht dan nu is een goed moment om kennis te maken met de basisgegevens van het product. Eerst kijk dan naar de eerste pagina\'s van de handleiding, die je hierboven vindt. Je moet daar de belangrijkste technische gegevens Carrier OMNIZONE 50XCA06-24 vinden. Op dit manier kan je controleren of het apparaat aan jouw behoeften voldoet. Op de volgende pagina's van de handleiding Carrier OMNIZONE 50XCA06-24 leer je over alle kenmerken van het product en krijg je informatie over de werking. De informatie die je over Carrier OMNIZONE 50XCA06-24 krijgt, zal je zeker helpen om een besluit over de aankoop te nemen.
In een situatie waarin je al een beziter van Carrier OMNIZONE 50XCA06-24 bent, maar toch heb je de instructies niet gelezen, moet je het doen voor de hierboven beschreven redenen. Je zult dan weten of je goed de alle beschikbare functies heb gebruikt, en of je fouten heb gemaakt die het leven van de Carrier OMNIZONE 50XCA06-24 kunnen verkorten.
Maar de belangrijkste taak van de handleiding is om de gebruiker bij het oplossen van problemen te helpen met Carrier OMNIZONE 50XCA06-24 . Bijna altijd, zal je daar het vinden Troubleshooting met de meest voorkomende storingen en defecten #MANUAl# samen met de instructies over hun opplosinge. Zelfs als je zelf niet kan om het probleem op te lossen, zal de instructie je de weg wijzen naar verdere andere procedure, bijv. door contact met de klantenservice of het dichtstbijzijnde servicecentrum.