3 Phase Voltages* Output Quantity and Rating No./kW Elec at of Contactors of Rating Cap. Vol. 212˚F Heating Model (BHP) (kW) (Gals.) (Lbs./Hr.) 208 240 480† Elements Type CES — 0-100 PSIG CES-6 .6 6 6 18 30 30 30 1-6 CES-9 .9 9 6 27 30 30 30 1-9 CES-12 1.
MODEL CES-24 through CES-180 MODEL CES-6 through CES-18 DIMENSIONS Drain Blowdown Valve K A C H B D E F G Check Valve L Optional T ransformer Safety Valve Outlet J Manual Reset High Limit Control Opti.
T ypical Plumbing Installation of a Steam Boiler with Condensate Return System CES — Dimensions (In.) DIMENSIONS INST ALLA TION Model A B* C D E F G H I J K L CES-6 37 22-1/2 30 15-1/4 20 30-1/2 9-1.
Diagram 1 3 Phase Voltage 3 Phase Voltage 3 Phase Voltage Boiler 208 240 480 Boiler 208 240 480 Boiler 208 240 480 WIRING TYPICAL WIRING DIAGRAMS WARNING: Hazard of Electric Shock. Boiler must be suitably grounded according to N.E.C. standard. 1. Be sure to use the proper wire.
Diagram 2 TYPICAL WIRING DIAGRAMS 2PS BR Heater Contactors Feed Water Boiler On 3 GND B FU9 B 1PB Off 2 GND 1 GND 1 HTR C1 FU1 FU2 FU3 FU8 FU7 H1 H2 X1 X3 L3 1L1 1L3 1L2 L2 L1 X2 X4 Optional T ransfor.
Diagram 4 TYPICAL WIRING DIAGRAMS 2PS BR Heater Contactor Feed Water Boiler On 3 GND B FU12 B 1PB Off 2 GND 1 GND 1 HTR C1 FU1 FU2 FU3 FU11 FU10 H1 H2 X1 X3 L3 1L1 1L3 1L2 L2 L1 X2 X4 Optional T ransf.
Diagram 6 TYPICAL WIRING DIAGRAMS 2PS BR Heater Contactors Feed Water Boiler On 3 GND B FU15 B 1PB Off 2 GND 1 GND 1 HTR C1 FU1 FU2 FU3 FU14 FU13 H1 H2 X1 X3 L3 1L1 1L3 1L2 L2 L1 X2 X4 Optional T rans.
Diagram 8 TYPICAL WIRING DIAGRAMS FU 1 2 3 FU 4 5 6 FU 7 8 9 C1 C3 C2 C4 FU 10 11 12 C5 FU 13 14 15 C6 FU 16 17 18 5 HTR 4 HTR 3 HTR 6 HTR 2 HTR 1 HTR 1 2 2TB 1TB 3 GND 2 GND 1 GND FU21 1PB 3 GND C1 C.
Diagram 10 TYPICAL WIRING DIAGRAMS 13 14 15 16 17 18 19 20 21 C5 C7 C6 C1 1 2 3 C2 4 5 6 C3 7 8 9 5 HTR 4 HTR 3 HTR 6 HTR 2 HTR 1 HTR 1 2 2TB 1TB 3 GND 2 GND 1 GND FU27 1PB 3 GND C1 C2 C6 C3 2PS 3PS 1.
Diagram 12 TYPICAL WIRING DIAGRAMS 13 14 15 16 17 18 19 20 21 C5 C7 C6 C1 1 2 3 C2 4 5 6 C3 7 8 9 5 HTR 4 HTR 3 HTR 6 HTR 2 HTR 1 HTR 1 2 2TB 1TB 3 GND 2 GND 1 GND FU24 1PB 3 GND C1 C2 C5 C3 2PS 3PS 1.
After proper wiring and piping of boiler system is complete, testing of controls can start. Before testing controls, it is recommended that all contactor fusing be removed. This is to prevent possible element failure under test conditions. A. OPERATING AND TESTING THE McDONNELL & MILLER LOW WATER CUTOFF CONTROL.
ADJUSTING OPERATING PRESSURE CONTROLS 1. Chromalox boilers are supplied with operating and high limit pres- sure controls. One is used for controlling the operating pressure of the boiler while the other is used as a high limit control. To deter- mine the difference in the controls, the high limit has a manual reset lever on top of the case.
OPERA TION AUTOMATIC BLOWDOWN INSTRUCTIONS (IF FURNISHED) The Automatic Blowdown is a device which automatically starts up your boiler in the morning; shuts it down at night and blows down (partially drains) the main boiler drain and the low water cut-off col- umn for a predetermined time interval each working day.
OPTIONAL EQUIPMENT FOR STEAM BOILERS AUXILIARY LOW WATER CUTOFF Operation Operation of this control is accomplished by sensing a minute AC current flowing between submerged contact probe in the boiler shell.
OPTIONAL EQUIPMENT FOR STEAM BOILERS IF A CONTROLLER SEEMS TO OPERATE IMPROPERLY If the controller is suspected of operating improperly, it may be further checked as follows: 1. Leave the controller installed where it is, but disconnect all power to the boiler.
Automatic water feed is required on all CES Boilers: LOW PRESSURE FEED Note: Water Pressure feeds must be at least 10 psi greater than steam pressure. Low pressure water feed systems are used to supply make up water to the boiler where incoming water line pressure is 10 psig or greater than the operating pressure of the boiler.
W A TER FEED SYSTEMS Installation Wiring A. Check the voltage of the motor before making the wiring connec- tion. Some Chromalox boilers are supplied with dual voltage sys- tems. The motor should always match the voltage of the control circuit. B. The motor circuit should be wired into the pump control located on the boiler.
Boiler 1" Steam Equalizing Pipe Pump and Low Water Control Normal Boiler Water Level Cutoff Level is Arrow Mark Blowdown Valve 1" Water Equalizing Pipe 1-1/2" 18 1 2 8 7 3 4 6 5 1 6 5 4 3 2 5-3/4 REF. 4-1/2 REF. FIG. 1 FIG. 2 MAINTENANCE 1 2 3 4 2-1/2 REF.
19 RENEW AL P ARTS IDENTIFICA TION Part Description Part Number Check Valve 1/2” CES-6 through CES-18 . . . . . . . . . . . . . . . . . . 344-118536-053 Check Valve 3/4” CES-24 through CES-180 . . . . . . . . . . . . . . . . 344-118536-054 Gauge Glass Assembly Valves (O-ring gaskets included) .
2150 N. RULON WHITE BLVD., OGDEN, UT 84404 Phone: 1-800-368-2493 www.chromalox.com RENEW AL P ARTS IDENTIFICA TION Part Description Part Number 1/4” Ball Valve (Pressure Gauge) . . . . . . . . . . . . . . . . . . . . . . . . 344-300323-002 Blowdown Valve 1/2” CES-6 through CES-18 .
Een belangrijk punt na aankoop van elk apparaat Chromalox CES-6 (of zelfs voordat je het koopt) is om de handleiding te lezen. Dit moeten wij doen vanwege een paar simpele redenen:
Als u nog geen Chromalox CES-6 heb gekocht dan nu is een goed moment om kennis te maken met de basisgegevens van het product. Eerst kijk dan naar de eerste pagina\'s van de handleiding, die je hierboven vindt. Je moet daar de belangrijkste technische gegevens Chromalox CES-6 vinden. Op dit manier kan je controleren of het apparaat aan jouw behoeften voldoet. Op de volgende pagina's van de handleiding Chromalox CES-6 leer je over alle kenmerken van het product en krijg je informatie over de werking. De informatie die je over Chromalox CES-6 krijgt, zal je zeker helpen om een besluit over de aankoop te nemen.
In een situatie waarin je al een beziter van Chromalox CES-6 bent, maar toch heb je de instructies niet gelezen, moet je het doen voor de hierboven beschreven redenen. Je zult dan weten of je goed de alle beschikbare functies heb gebruikt, en of je fouten heb gemaakt die het leven van de Chromalox CES-6 kunnen verkorten.
Maar de belangrijkste taak van de handleiding is om de gebruiker bij het oplossen van problemen te helpen met Chromalox CES-6 . Bijna altijd, zal je daar het vinden Troubleshooting met de meest voorkomende storingen en defecten #MANUAl# samen met de instructies over hun opplosinge. Zelfs als je zelf niet kan om het probleem op te lossen, zal de instructie je de weg wijzen naar verdere andere procedure, bijv. door contact met de klantenservice of het dichtstbijzijnde servicecentrum.