Agilent 6800 Series AC Power Source/Analyzer Product Note Using the Agilent T echnologies 6800 Series AC Power Source/Analyzers for Generation and Measurement Applications: • Simulating A C Line Sub.
2 3 4 6 8 11 14 18 21 24 28 Introduction This note pro vides information on ho w you can use the features of the Agilent Technologies 6800 series ac po wer source/anal yzers to address a variety of applications.
3 The 6800 series ac po wer source/anal yzers are members of the A gilent T echnologies “One-Bo x” Solution po wer products famil y. These products offer an integrat ed solution f or ac pow er testing applications.
4 A programmable output value of the ac pow er source/analyzer can operate in one of f our modes: FIXED, Step, Pulse, or List. The default setting is FIXED mode, where the output will st a y “f ix ed” at the programmed value until anot her command is sent to change it.
5 Model of the T ransient System.
6 In A TE applications, triggers are of ten a conven- ient way of synchr onizing test syst em ev ents and increasing test throughput. These benef its also apply to the triggering subsystems in t he 6800 series products since these products combine the capabilities of many test instruments.
7 Output T ransient T rigger Model Measurement T rigger Model.
8 The built-in po wer analyzer capability off ers many voltage, current, and pow er measurements to the user . While on, the ac po wer sour ce/analyzers are continuously sam pling inst antaneous output volt- age and current for sev eral output cycles and writ- ing the dat a to buf f ers.
9 How Can the Acquisition of V oltage and Current Data be Controlled? T w o characteristics of t he voltage and current acquisition can be controlled: the sample rate, and the beginning of acquisition relative to the trigger .
10 The follo wing section contains six application examples. F or each application, there is: • An o verview of the application • A description of the A gilent 6800 series f eatures used to implem.
11 Overview of application The ability of a switching pow er supply to main- tain its output voltage setting in t he presence of typical ac line disturbances is critical to its end- use.
12 U pon the receipt of the trigger , the ac source continues to output a 120 V r ms, 60 Hz sinewa ve for 5 seconds. After the 5-second trigger delay , the r ms v olt age drops to 0 V rms at 80° of t he cycle and then rises back to 120 V rms (0.001389 seconds later) at 110° of the cycle.
13.
14 Overview of application U .S. Militar y Standard 704D (September 30, 1980) establishes t he requirements of electrical po wer transfer betw een the aircraft or g round support electrical system, and the electronic equipment utilizing this pow er on board the aircraft.
15 Agilent 6800 series setup (continued) • Set the List points as follo ws: List Vrms Dwell Point V rms frequency Slew Time 1 115 V 400 Hz INF *60 s 2 127 V 400 Hz INF 0.01 s 3 88 V 400 Hz 566 V/s 0.07 s 4 115 V 400 Hz INF *60 s 5 57 V 400 Hz INF 0.
16 List Timing Diagram for Application 2.
17.
18 Overview of application IEC 555-2 (1982) is a regulator y st andard that pert ains to ac line disturbances, namely current harmonics. These cur rent harmonics are caused by connecting household appliances and similar elec- trical equipment to a 230 V , 50 Hz ac mains.
19 Agilent 6800 series setup • The ac source output is connected to the ac input of the equipment under test. • Set the output wav eform to sine. • Set the r ms v olt age to Fixed mode. • Set the frequency to F ix ed mode. • Set the voltage to 230 Vrms.
20.
21 Overview of application Swit ch mode pow er supplies are commonly used in many electr onic products. These po wer supplies typically ha ve in put capacit ors that cause high lev els of peak inr ush current to be drawn as they charge from the rectified line at tur n-on.
22 Agilent 6800 series setup • Set the initial (immediate) voltage t o 0 V rms. • Set the triggered voltage level to 120 V rms. • Set the frequency to 60 Hz. • Set the peak cur rent limit to maximum. • Set the transient trigger source to BUS.
23.
24 Overview of application The creation of user -def ined wa vef or ms is useful for simulating ac line disturbances that are unique to the operational environment of the device being tested, and t hen measuring that device’s suscepti- bility to the disturbance.
25 Agilent 6800 series setup • Connect the ac source output to the ac input of the equipment under test. • Use the computer to develop a 1024 point array representing a cy cle of voltage amplitude data. • Use the TR A Ce:DEFine command to name t he wav eform CL ASS 1 and allocate non-volatile storage space.
26.
27.
28 Overview of application F or some applications, such as the simulation of European railwa y po wer systems, a lo w frequency (16.6 Hz) ac wav eform is required.
29.
Agilent T echnologies’ T est and Measurement Support, Services, and Assistance A gilent Technologies aims to maximize the value you receiv e, while minimizing your risk and pr oblems. W e strive to ensure that you get the test and measurement capabilities you paid for and obtain the suppor t y ou need.
Een belangrijk punt na aankoop van elk apparaat Agilent Technologies 6800 (of zelfs voordat je het koopt) is om de handleiding te lezen. Dit moeten wij doen vanwege een paar simpele redenen:
Als u nog geen Agilent Technologies 6800 heb gekocht dan nu is een goed moment om kennis te maken met de basisgegevens van het product. Eerst kijk dan naar de eerste pagina\'s van de handleiding, die je hierboven vindt. Je moet daar de belangrijkste technische gegevens Agilent Technologies 6800 vinden. Op dit manier kan je controleren of het apparaat aan jouw behoeften voldoet. Op de volgende pagina's van de handleiding Agilent Technologies 6800 leer je over alle kenmerken van het product en krijg je informatie over de werking. De informatie die je over Agilent Technologies 6800 krijgt, zal je zeker helpen om een besluit over de aankoop te nemen.
In een situatie waarin je al een beziter van Agilent Technologies 6800 bent, maar toch heb je de instructies niet gelezen, moet je het doen voor de hierboven beschreven redenen. Je zult dan weten of je goed de alle beschikbare functies heb gebruikt, en of je fouten heb gemaakt die het leven van de Agilent Technologies 6800 kunnen verkorten.
Maar de belangrijkste taak van de handleiding is om de gebruiker bij het oplossen van problemen te helpen met Agilent Technologies 6800 . Bijna altijd, zal je daar het vinden Troubleshooting met de meest voorkomende storingen en defecten #MANUAl# samen met de instructies over hun opplosinge. Zelfs als je zelf niet kan om het probleem op te lossen, zal de instructie je de weg wijzen naar verdere andere procedure, bijv. door contact met de klantenservice of het dichtstbijzijnde servicecentrum.