Revised 1-8-2007 Delta Cooling Towers, Inc. TM Series Cooling Tower Installation, Operation & Maintenance Manual.
Revised 1-8-2007 1 Table of Contents Delta Cooling Towers Principle of Cooling Towers………………..……………. 2 Cooling Tower Terms and Definitions…………………… 2 Water Treatment……..………………………….………..
Revised 1-8-2007 2 Delta Cooling Towers Principle of Cooling Towers All Cooling Towers operate on the principle of removing heat from water by evaporating a sm all portion of the water that is recirculated through the unit. The heat that is removed is called the latent heat of vaporization.
Revised 1-8-2007 3 Water Treatment • The Delta Cooling Towers are manufactured from corrosion-resistant plastics which are resistant to water treatment chemicals including com mon fungicides and bactericides. • Follow appropriate water treatment practices as require d and take frequent sample tests to avoid possible water contamination.
Revised 1-8-2007 4 Approximate Weights The TM Series cooling towers are manufactured in three basic sections; a polyethylene tower body, a polyethylene sump, and a fan assembly section. The tower body ships with the fan assem blies installed. The tower sump ships as a separate piece.
Revised 1-8-2007 5 Handling and Installation of Your TM Series Cooling Tower On -Site Inspection Upon arrival at the job site, carefully inspect the shipment for any damage. If shipping dam age has occurred, notify the driver or the carrier immediately and m ake a notation of the damage on the shipping bill of lading.
Revised 1-8-2007 6 Store tower assembly as shipped until the time of installation, in a secure, level and debris free location at the job site. CAUTION : For extended lifts, use duplicate rigging, fabric slings around body as shown, as an additional safety precaution.
Revised 1-8-2007 7 • The body section should then be lifted and carefully position to align the support post of the sump with the corresponding groove of the tower body. Note that the four corner posts are slightly higher than other post to ease installation alignment.
Revised 1-8-2007 8 • On multi cell towers, install PVC water redirector panels between each sump using self-tapping screws provided (See sketch below). Start with screwing the PVC post from the bottom up. Next apply a heavy bead of RTV sealant on the end of each redirector panel.
Revised 1-8-2007 9 Electrical Wiring of Fan Motor and Accessories • Installation of a vibration cut-out switch is recommended. (Refer to tower accessories available). • All electrical work should be performed only by qualified personnel and in accordance to prevailing electrical codes, practices and safety standards.
Revised 1-8-2007 10 PVC Solvent Cementing Instructions The following procedure is recommended for the preparation and cem enting of internal and external piping for Delta Cooling Towers: • Cut ends of pipe square using a handsaw and miter box.
Revised 1-8-2007 11 Operation and Maintenance of Your TM Series Cooling Tower Safety in Operation of the Fan NEVER operate the fan when the access panel or the entire fan guard is removed. NEVER remove access manhole cover while fan is in operation. NEVER operate fan when any work, access, maintenance, trouble-shooting, etc.
Revised 1-8-2007 12 • The maximum operating inlet water temperature should not exceed 140° F. CAUTION: When stepping on top of the fill, distribute th e body weight by means of two plywood plates as described earlier in these instructions.
Revised 1-8-2007 13 • Check spray pattern from nozzles to be sure there is no clogging. Remove drift elim inators for nozzle inspection, then return to proper position. • Start up fan motor and check amperage and voltage against m otor nameplate data.
Revised 1-8-2007 14 Cold Weather Operation Cold Weather Protection The cooling tower may require protection against freezing at light heat loads when the wet-bulb temperature is under 32°F.
15 PVC Distribution System To prevent damage to the PVC distribution system during cold weather shut-down, install an automatic or manual drain line from the hot water inlet piping as close to the cooling tower inlet as possible. The entire inlet and distribution system must be drained for shut-down in sub- freezing weather.
16 Trouble-Shooting Guide For TM Series Induced Draft Cooling Towers Problem Possible Causes Corrective Actions Increase in the leaving water temperature 1. Excess water flow; over pumping. 2. Recirculation of hot discharge air, back into the cooling tower air intakes.
17 Problem Possible Causes Corrective Actions 2. Airlock. 3. Unnecessary obstruction of waterflow (i.e., partially closed valve). 4. Undersized piping. 5. Horizontal pipe run too long. 6. Improper hydraulic pipe design. 7. Outlet vortex breaker provided.
18 Motor Trouble Shooting Guide (General) Problem Possible Causes Corrective Actions High current draw (all 3 phases) 1. Low line voltage (5 to 10% lower than nameplate). 2. 200V motor on 230/240V system. 3. 230V motor on 208V system. 4. Incorrect propeller.
19 TM Series Optional Accessories TM Series Optional Accessories Available Aluminum Ladder(s) with a step platform and railing at the fan elevation custom designed for the cooling tower. Safety cage(s). Two speed motor(s) designed for cooling tower duty to the exclusive specifications of Delta Cooling Towers.
20 Preventative Maintenance Checklist Procedure Monthly Every 3 Months Every 6 months Inspect General Condition of cooling tower. ¨ Check Water Level in cold water basin. Adjust if needed. ¨ Check float ball & Make-up Valve for proper operation.
Een belangrijk punt na aankoop van elk apparaat Delta TM Series Cooling Tower (of zelfs voordat je het koopt) is om de handleiding te lezen. Dit moeten wij doen vanwege een paar simpele redenen:
Als u nog geen Delta TM Series Cooling Tower heb gekocht dan nu is een goed moment om kennis te maken met de basisgegevens van het product. Eerst kijk dan naar de eerste pagina\'s van de handleiding, die je hierboven vindt. Je moet daar de belangrijkste technische gegevens Delta TM Series Cooling Tower vinden. Op dit manier kan je controleren of het apparaat aan jouw behoeften voldoet. Op de volgende pagina's van de handleiding Delta TM Series Cooling Tower leer je over alle kenmerken van het product en krijg je informatie over de werking. De informatie die je over Delta TM Series Cooling Tower krijgt, zal je zeker helpen om een besluit over de aankoop te nemen.
In een situatie waarin je al een beziter van Delta TM Series Cooling Tower bent, maar toch heb je de instructies niet gelezen, moet je het doen voor de hierboven beschreven redenen. Je zult dan weten of je goed de alle beschikbare functies heb gebruikt, en of je fouten heb gemaakt die het leven van de Delta TM Series Cooling Tower kunnen verkorten.
Maar de belangrijkste taak van de handleiding is om de gebruiker bij het oplossen van problemen te helpen met Delta TM Series Cooling Tower . Bijna altijd, zal je daar het vinden Troubleshooting met de meest voorkomende storingen en defecten #MANUAl# samen met de instructies over hun opplosinge. Zelfs als je zelf niet kan om het probleem op te lossen, zal de instructie je de weg wijzen naar verdere andere procedure, bijv. door contact met de klantenservice of het dichtstbijzijnde servicecentrum.