3 Macurco ™ Combustible Gas Detector , Controller and T ransducer User Instructions IMPORT ANT : Keep these User Instructions for reference. GD-6.
1 T ABLE OF CONTENTS GENERAL SAFETY INFORMA TION ................................................................................................................ 2 Intended Use ..........................................................................
2 3 W WARNING GENERAL SAFETY INFORMA TION Intended Use The 3M™ Macurco™ GD-6 Combustible Gas Detector , Controller and T ransducer is a low voltage device with selectable 4-20mA output, buzzer and digital display options.
4 5 Ifyouhaveanydoubtsabouttheapplicabilityoftheequipmenttoyourjobsitua tion, consultanIndustrialHygienistorcall3M Macurco T echnical Ser vice at 1-800-243-4630. In Canada, call 1-800-267-4414.
6 7 Installation 1. The 3M™ Macurco™ GD-6 Combustible Gas Detector mounts on a type 4S electrical box supplied by the contractor . 2. Connect the 3M™ Macurco™ GD-6 Combustible Gas Detector to Class 2 power supply only .
8 9 T ypical Multiple 3M™ Macurco™ GD-6 Combustible Gas Detector Installation INSTALLA TION NOTES 1. One sensor per 900 square feet (approximately). 2. If the gas used is natural gas (methane) or Hydrogen (H2) mount the 3M™ Macurco™ GD-6 Combustible Gas Detector high on a wall about one foot down from the ceiling.
10 11 GD-6 Main Fan Power 120VAC ALARM 120VAC Power Exhaust Fans coil coil power output GD-6 – + power output – + 8 7 6 5 4 4 3 3 2 2 1 1 1 1 3 3 4 5 6 7 8 9 2 24 V RET N.
12 13 T o change settings, remove the Philips screw on the front of the 3M™ Macurco™ GD-6 Combustible Gas Detector . Pull off the front cover of the unit. Gas Selection T o select the Gas Option , in normal mode, press the Next button once to display the current gas selection ( mE is Methane, Pro is Propane and Hy is Hydrogen) .
14 15 Selecting Fan Minimum Run Time – “Frr” T o select the Fan Minimum Runtime setting, in normal mode, press the Ne xt button twice to get to “Con” or the Configuration menu. Then press the Enter button to enter the Con menu. The ninth selection is the “Frr” or Fan Minimum Run Time.
16 17 Operation T est 1. Remove the single screw in the middle of the front cover of the 3M™ Macurco™ GD-6 Combustible Gas Detector . 2. Remove the front cover . 3. Observe the LED light on the front of the 3M™ Macurco™ GD-6 Combustible Gas Detector .
18 19 Gas T esting T esting the Fan Relay Note: The gas concentration to activate the fan relay depends on the setting. 1. Remove the Philips screw on the front of the 3M™ Macurco™ GD-6 Combustible Gas Detector . Remove the front cover . 2. Connect the 10% LEL cylinder of Combustible Gas to the regulator .
20 21 5. The 4-20mA output should ramp up from 4mA in clean air to 20mA at 50% LEL. See 4-20mA diagram in these User Instructions . Note: If the 4-20mA output does not ramp up within 2 minutes, consider these possibilities: a. Gas cylinder is empty , check the pressure gauge.
22 23 7. Press the Enter button and the display will read 10 alternating with the gas, mE, Pro or Hy (blinking), indicating the sensor is looking for gas. 8. Start applying gas to the gas sensor . Note: The sensor will look for the gas for 45 seconds.
24.
3M Occupational Health and Environmental Safety Division 3M Center , Building 0235-02-W-70 St. P aul, MN 55144-1000 Printed in U.S.A. © 3M 2008-2011. All rights reserved.
Requester: Farrel Allen Creator: deZinnia File Name: 34870758629.indd Structure #: SS-41964 Date: 6/17/11 Printed Colors – Front: Printed Colors – Back: Match Colors: This artwork has been created as requested by 3M. 3M is responsible for the artwork AS APPROVED and assumes full responsibility for its correctness.
Een belangrijk punt na aankoop van elk apparaat 3M GD-6 (of zelfs voordat je het koopt) is om de handleiding te lezen. Dit moeten wij doen vanwege een paar simpele redenen:
Als u nog geen 3M GD-6 heb gekocht dan nu is een goed moment om kennis te maken met de basisgegevens van het product. Eerst kijk dan naar de eerste pagina\'s van de handleiding, die je hierboven vindt. Je moet daar de belangrijkste technische gegevens 3M GD-6 vinden. Op dit manier kan je controleren of het apparaat aan jouw behoeften voldoet. Op de volgende pagina's van de handleiding 3M GD-6 leer je over alle kenmerken van het product en krijg je informatie over de werking. De informatie die je over 3M GD-6 krijgt, zal je zeker helpen om een besluit over de aankoop te nemen.
In een situatie waarin je al een beziter van 3M GD-6 bent, maar toch heb je de instructies niet gelezen, moet je het doen voor de hierboven beschreven redenen. Je zult dan weten of je goed de alle beschikbare functies heb gebruikt, en of je fouten heb gemaakt die het leven van de 3M GD-6 kunnen verkorten.
Maar de belangrijkste taak van de handleiding is om de gebruiker bij het oplossen van problemen te helpen met 3M GD-6 . Bijna altijd, zal je daar het vinden Troubleshooting met de meest voorkomende storingen en defecten #MANUAl# samen met de instructies over hun opplosinge. Zelfs als je zelf niet kan om het probleem op te lossen, zal de instructie je de weg wijzen naar verdere andere procedure, bijv. door contact met de klantenservice of het dichtstbijzijnde servicecentrum.