026-1307 Rev 1 11-30-07 Modular Refrigerant Leak Detection Sensor (MRLDS) Inst allation and Operation Manual.
.
Computer Process Controls, Inc. 1640 Airport Road Suite #104 Kennesaw, GA 31044 Phone 770-425-2724 Fax 770-425-9319 ALL RIGHTS RESERVED The information contained in this manual ha s been carefully chec ked and is believed to be accurate. However, Com puter Process Controls, Inc.
.
MRLDS I&O Manual Table of Contents • v Table Of Contents 1 OVERVIEW ............ .............. .............. .............. .............. .............. ............... .............. ........... .............. .............. ............. 1 1.
.
Specifications Overvi ew • 1 1 Overview CPC specs a modular refrigerant leak detection sensor (MRLDS) that continuously monitors for low levels of refrigerants most commonl y us ed in commercial refrigera- tion systems.
2 • MRLDS I&O Manual 026-1307 Rev 1 11-30-07 2 Choosing a Mounting Location Proper location of the refriger ant sensor is necessary to ensure accurate measurement of representative air sam- ples. Mount the sensor: • Indoors, inside a room area where air circulates freely .
MRLDS Dimensions MRLDS Analog Version (809-100x) • 3 2.2 MRLDS Dimensions 3 MRLDS Analog V ersion (809-100x) 3.1 Network Layout 3.2 MRLDS W iring For analog MRLDS units, connect to a MultiFlex board via the analog input (use Belden 87 61 cable).
4 • MRLDS I&O Manual 026-1307 Rev 1 11-30-07 3.3 R efrigerant Jumper Settings The jumper set tings for refr igerant types are located on the label inside the MRLDS sensor cover (shown in Fig- ure 1-1 ). Set the jumpers according to how they are indi- cated on the label.
Network Layout MRLDS Mo dbus Version (809-101x) • 5 3.4.3 RMCC Controllers For RMCC-type controllers, set the Gain parame ter to 250 and Offset to -10 00 . 4M R L D S M o d b u s V ersion (809-101x) 4.1 Network Layout 4.2 MRLDS Setup 4.2.1 MRLDS W iring 4.
6 • MRLDS I&O Manual 026-1307 Rev 1 11-30-07 4.2.3 Address Settings 4.2.4 Refrigerant Jumper Settings The jumper set tings for refr igerant types are located on the label inside the MRLDS sensor cover (shown in Fig- ure 1-1 ). Set the jumpers according to how they are indi- cated on the label.
MRLDS Gateway MRLDS Modbus Version (809-101x) • 7 bits with no parity and 2 (two) stop b its. 4.3 MRLDS Gateway 4.3.1 MRLDS Gateway Setup on I/O Network Modbus versions of the MRLDS must be connected to the 810-3040 MRLDS Gateway .
8 • MRLDS I&O Manual 026-1307 Rev 1 11-30-07 The Gateway Board commun icates with the MRLDS via the Modbus network, which is connected to the Gate- way’ s “Receiver Bus” network terminal. The Gateway communicates with the E2 via the RS485 I/O Network.
MRLDS Gateway MRLDS Modbus Version (809-101x) • 9 controller ’ s user manual. T o connect the Gateway to an MRLDS, feed the wires through the rectangular opening in the sen s or base as in di- cated in Figure 1-1 . Locate the RS485 connector and secure the wire leads to the connector orienting them as shown in Figure 4-10 .
10 • MRLDS I&O Manual 026-1307 Rev 1 11-30-07 4.3.9 Setting the Baud Rate Dip Switches Dip switches 6 and 7 control the baud rate at which th e Gateway communicates w ith the site co ntroller on the RS485 Network.
Controller Setup for Modbus MRLDS MRLDS Modbus Version (809-101x) • 11 4.3.10.4 Setup/Online Screen 2 - The Setup/Online screen displays the addressing of the devices and whether they are enabled. Press the right/ left arrows to select the first address in the list.
12 • MRLDS I&O Manual 026-1307 Rev 1 11-30-07 ways. Navigate to the controller ’ s Input Status screen and highlight the board and point that yo u wish to map. Press F1 to go to the Input Setup screen for that board/ point. Each point will increase incr ementally to co rrespond with each board.
Controller Setup for Modbus MRLDS MRLDS Modbus Version (809-101x) • 13 field to change the name, and press the down or right arrow to move to the (sensor) Type field. Use the “.” and “ — ” keys to scroll through the options and select IRLDS .
14 • MRLDS I&O Manual 026-1307 Rev 1 11-30-07 “MV” should be entered for sensor inputs that read fault status. Gain and Offset Since the output terminals emit one volt fo r every 250 ppm of refrigerant detect ed, the gain for the refrigeran t leak sensors must be set to 250 and the O ffset to 0.
Een belangrijk punt na aankoop van elk apparaat Emerson MRLDS (of zelfs voordat je het koopt) is om de handleiding te lezen. Dit moeten wij doen vanwege een paar simpele redenen:
Als u nog geen Emerson MRLDS heb gekocht dan nu is een goed moment om kennis te maken met de basisgegevens van het product. Eerst kijk dan naar de eerste pagina\'s van de handleiding, die je hierboven vindt. Je moet daar de belangrijkste technische gegevens Emerson MRLDS vinden. Op dit manier kan je controleren of het apparaat aan jouw behoeften voldoet. Op de volgende pagina's van de handleiding Emerson MRLDS leer je over alle kenmerken van het product en krijg je informatie over de werking. De informatie die je over Emerson MRLDS krijgt, zal je zeker helpen om een besluit over de aankoop te nemen.
In een situatie waarin je al een beziter van Emerson MRLDS bent, maar toch heb je de instructies niet gelezen, moet je het doen voor de hierboven beschreven redenen. Je zult dan weten of je goed de alle beschikbare functies heb gebruikt, en of je fouten heb gemaakt die het leven van de Emerson MRLDS kunnen verkorten.
Maar de belangrijkste taak van de handleiding is om de gebruiker bij het oplossen van problemen te helpen met Emerson MRLDS . Bijna altijd, zal je daar het vinden Troubleshooting met de meest voorkomende storingen en defecten #MANUAl# samen met de instructies over hun opplosinge. Zelfs als je zelf niet kan om het probleem op te lossen, zal de instructie je de weg wijzen naar verdere andere procedure, bijv. door contact met de klantenservice of het dichtstbijzijnde servicecentrum.