General Datap.2A1.102 Rev. B Technical Details, Standard Actuatorp.2A1.102.10 Rev. C El-O-Matic Basic Pneumatic Actuator Configurationp.3A1.501.01 Rev. A El-O-Matic Actuator with One Way Limit Stopsp.4A1.501.03 Rev. A Limit Stop Plate Dimensionsp.5A1.501.05 Rev. A El-O-Matic Actuator with Double Stroke Adjustmentp.6Dimensionsp.7A1.103.106 Rev. D Standard Actuator - ISOp.7A1.103.102 Rev. A Standard E12 A ctuator - ISOp.8A1.103.200 Rev. B Drive Inserts for El-O-Matic Actuatorsp.9Torquep.10A1.104.01 Rev. B Double Acting Actuator (In.lb.)p.10A1.104.02 Rev. B Spring Return Actuator (In.lb.)p.11Construction, Parts and Materialsp.12A1.101.33 Rev. A E-Serie Actuatorsp.12A1.101.30 Rev. A P-serie actuatorsp.13A1.101.60 Rev. A DSA Actuatorsp.14A1.101.70 Rev. C Low Temperature Actuator Specificationp.15A1.101.71 Rev. B High Temperature Actuator Specificationp.16Spring Setsp.17A4.201 Rev. A Installation of Springs - P-Seriesp.17A4.202 Rev. A Installation of Springs - E-Seriesp.18Assembly Modesp.19A1.503 Rev. A Double Acting Assembly Modesp.19A1.504 Rev. A Spring Return Assembly Modesp.20Corrosion Protection / Paint Specificationp.21A4.204.01 Rev. B Standard Corrosion Protection Systemp.21A4.204.02 Rev. B El-O-Matic CSR Coatingp.22A4.204.021 Rev. A Chemical Resistance CSR Coatingp.23180° Actuatorsp.24A1.203.011 Rev. A Dimensions Standard 180° Actuatorsp.24A1.204.01 Rev. C Torque 180° Double Acting Actuator (In.lb.)p.25A1.204.02 Rev. C Torque 180° Spring Return Actuator (In.lb.)p.26Contact Usp.27
Page 1 of the Emerson Process Management P2500 user manual — Product Data sheets DOC.DSE.PN.US Rev. G May 2011
Pagina 1 · klik om te vergroten
Pagina 1

Product Data sheets DOC.DSE.PN.US Rev. G May 2011

El-O-Matic E and P Series Technical data pneumatic Rack and Pinion actuators

Emerson Process Management P2500 — Product Data sheets DOC.DSE.PN.US Rev. G May 2011 diagram (page 1)
Afb. 1 · Product Data sheets DOC.DSE.PN.US Rev. G May 2011
Page 2 of the Emerson Process Management P2500 user manual — A1.501.05
Pagina 2 · klik om te vergroten
Pagina 2

Data sheet

Sheet No.: Date: June 2010

A1.102 Rev. B

TECHNICAL DETAILS, STANDARD ACTUATOR E/P

P-series

Specification Pressure range : Double acting 20 to 120 psi : Spring return 80 to 120 psi,, with max. spring set 40 to 120 psi, reduced spring quantity : 180° actuators 87 psi maximum Torque : 1133 to 40,000 in.lb at 80psi supply

European Directives PEDAll actuators are suiteable for use
Emerson Process Management P2500 — P-series diagram (page 2)
Afb. 2 · P-series

with Group 2 gasses according to Pressure Equippement Directive 97/23/EC : Optional : actuators suiteable for

use with Group 1 gasses ATEX : All basic actuators are suiteable

See torque datasheets 1.104.01 and 1.104.02 Operating media : Air, dry or lubricated and inert gasses : For sub-zero applications take appropriate measures Temperature : -4° to +176°F Lubrication : Factory lubricated for the normal life of the actuator Construction : Suitable for indoor and outdoor installation Finish : Polyester non-TGIC based powder coating

for use in hazardous area's classified II 2 GD, zones 1 or 2 (Gasses) and 21 or 22 (Dust)

Russian Approvals El-O-Matic E and P series pneumatic actuators are available with the GOST-R and Rostechnadzor (RTN) approvals.

(see data sheet A4.204.01) Rotation : 91.5° (-0.5° CW to 91° CCW) Double acting : Standard counter clockwise with port "A" pressurized

(code A, see data sheet A1.503 for other assembly codes) Spring return : Clockwise fail action

(code A, see data sheet A1.504 for other assembly codes) Limit stops : Standard on E-series. Adjustable range 91°/80° : Optional on P-series. See datasheet A1.501.01 : For double stroke adjustment. See datasheet

A1.501.05

ED = Double acting ES = Spring return

Emerson Process Management P2500 — A1.501.05 diagram (page 2)
Afb. 3
ACTUATOR TYPEE12E25E40E65E100E150E200E350E600E950E1600P2500P4000 Boreinch1.82.22.83.13.64.14.35.76.97.99.111.812.8 Strokeinch0.50.60.70.91.01.21.51.51.72.02.52.23.2 Weight:Double actinglb.1.32.94.05.36.810.512.823435894125191 Spring returnlb.1.53.75.37.910.115.220.1376185145194291 Operating timesec.0.40.50.71.11.21.82.33.64.55.46.9712 Air consumption at 1 atm (cu./in.)port Astroke3.16.19.820214549110177287445488824 port Bstroke3.76.713223040611161892994885681,068

* only standard on E-Serie actuators

Emerson Process Management P2500 — A1.501.05 diagram (page 2)
Afb. 4

Copyright © Emerson Process Management. The information in this document is subject to change without notice. Updated data sheets can be obtained from our website www.El-O-Matic.com or from your nearest Valve Automation Center USA: +1 813 319 0266 Europe: +31 74 256 10 10 Asia-Pacific: +65 6501 4600

11° Adjustable range*

Page 3 of the Emerson Process Management P2500 user manual — Temperature range
Pagina 3 · klik om te vergroten
Pagina 3

Data sheet

Sheet No.: Date: November 2010

A1.102.10 Rev. C El-O-Matic basic pneumatic actuator configuration E/P

Single or Double action ES or PS = Single acting, ED or PD = Double acting

See following data sheets for more information

A1.104.01 / A1.104.02

0012 = E12 0025 = E25 0040 = E40 0065 = E65 0100 = E100 0150 = E150 0200 = E200 0350 = E 350 0600 = E600 0950 = E950 1600 = E1600 P-series

2500 = P2500 4000 = P4000

Valve flange Metric Metric UNC/NPT Finish ISO 5211 DIN 3337 ISO 5211 M = D = U = Standard N = E = V = CSR coating (2 + Aluminum pinion O = F = W = CSR coating (2 + Stainless Steel pinion (3

A1.103.106 / A1.103.073 / A1.103.102 / A1.103.103 A1.101.30 / A1.101.33 / A4.204.01

Limit stops

A1.501.01/ A1.501.05

0 = No limit stops 1 = L1 One way limit stops 2 = Double Stroke Adjustment Standard on P-series Standard on E-Series Standard on DSA-Series

Assembly code

A1.503/ A1.504

Code Action Rotation Mounting A = Spring to close clock wise in line with pipeline B = Spring to close clock wise across pipeline C = Spring to open counter clock wise across pipeline D = Spring to open counter clock wise in line with pipeline

A1.104.02

Spring set E-serie Spring set P-serie 00 = Double acting actuator 00 = Double acting actuator 01 = Springset 1 04 = Springset 4 04 = Springset 4 10 = Springset 10 02 = Springset 2 05 = Springset 5 06 = Springset 6 12 = Springset 12 03 = Springset 3 06 = Springset 6 08 = Springset 8 14 = Springset 14

Future expansion A = Standard

Default Insert

A1.103.073 A1.103.106 A1.103.120

Size (in mm.) (1 E12 E25 E40 E65 E100 E150 E200 E 350 E600 E950 E1600 P2500 P4000 - ISO or UNC 00 11 14 14 19 19 22 27 27 36 46 00 00 - DIN 00 11 14 14 17 17 22 22 27 36 46 00 00

Visual Indication Code

D = Disk K = Knob N = No visual indication

Temperature range

A1.101.70 / A1.101.71

0 = Standard TS: 80°C (176°F) -20°C ( -4°F) 1 = High temp TS: 120°C (248°F) -20°C ( -4°F) 2 = Low temp TS: 80°C (176°F) -40°C (-40°F) ES 0040.M 1 A 05 A.14 N 1

(1 Actuators E12, P2500 and P4000 have no inserts. They have have a inner square the shaft 180° actuators are not covered by this configuration matrix. (2 CSR Coating not possible in combination with Double Stroke Adjustment limit stops (DSA series). (3 Stainless Steel Pinion not possible in combination with Double Stroke Adjustment limit stops (DSA series).

Copyright © Emerson Process Management. The information in this document is subject to change without notice. Updated data sheets can be obtained from our website www.El-O-Matic.com or from your nearest Valve Automation Center USA: +1 813 319 0266 Europe: +31 74 256 10 10 Asia-Pacific: +65 6501 4600

Actuator size E-series

Page 4 of the Emerson Process Management P2500 user manual — TM
Pagina 4 · klik om te vergroten
Pagina 4

Data sheet Sheet No.: Date: November 2009

A1.501.01 Rev. A EL-O-MATIC ACTUATOR WITH ONE WAY LIMIT STOPS L1/LF

Dim. in inchACTUATOR TYPE P2500P4000 A22.827.9 B31.345.4 C14.015 D1.21.2

Description Actuators with one way adjustable limit stops are used where the maximum opening (or closing) position of the valve needs to be reduced. For instance to adjust the maximum capacity of a remote operated valve. Also actuators with 180° rotation are available with these stops.

DOUBLE ACTING SPRING RETURN

Operation Stop screws are fitted to both endcaps and the screw length is such that adjustment is possible through the specified rotation of the actuator. The modified endcap is machined for -0.5° to +93° rotation for all P-series models.

B

D

A

Identification “L1” is added to the basic part number i.e. PD2500-L1

Specification:

Pressure : Up to 120 PSI Media : Air, dry or lubricated or non-corrosive gas Torque (90°) : Data sheet A1.104.01 - A1.104.04 (180°) : Data sheet P-serie A1.204.01 and A1.204.02 Other dimensions : Data sheet A 1.103.XXX (90°) : Data sheet A 1.203.011 (180°) Temperature : -4.0° to +176°F Adjustable range : 80°-93°(90°) or 160°-186° (180°)

9.236 6.496

5/8"-11x.98

Adjustable position (see data sheet A1.503 or A1.504) code position A Valve open (spring to close) B Valve open (spring to close) C Valve closed (spring to open) D Valve closed (spring to open) Note: 1) Can be provided with extra long screws for full range adjustment (identification: PD2500-LF) 2) This option in combination of a manual override gearbox is redundant

P2500

3/4"-10x1.14

10x1.14

5/8"-11x.98

Adjustable range

90° actuator Adjustable range

2.165 10.000 6.496 3/4"-

180° actuator

P4000

+6° Open Closed Closed

TM

Copyright © Emerson Process Management. The information in this document is subject to change without notice. Updated data sheets can be obtained from our website www.El-O-Matic.com or from your nearest Valve Automation Center USA: +1 813 319 0266 Europe: +31 74 256 10 10 Asia-Pacific: +65 6501 4600

3° 10° Open · -20°

Page 5 of the Emerson Process Management P2500 user manual — F
Pagina 5 · klik om te vergroten
Pagina 5

Data sheet Sheet No.: Date: November 2009

A1.501.03 Rev. A LIMIT STOP PLATE DIMENSIONS LS 420

Description These limit stop plates are used when precise control is required for both end of stroke positions. It is possible to adjust 15° of both ends of the standard stroke.

Construction The complete stop plate assembly may be added to the 90° P- series actuators. The assembly is normally sandwiched between the actuator and mounting surface of the valve or bracket. Bearing rings are used at both surfaces to provide a long life expectancy.

The unit is assembled with a drive adaptor which passes through the stop plate, into the square actuator and provides the coupling between the two components. This drive adaptor normally also accommodates the coupling of the valve stem.

E

Identification "LS420" is added to the basic part number i.e. PD2500-LS420

Other dimensions See data sheet A1.103.xxx

Option Version for 180° or DIN-standard actuator

Gmax.

Dim. in inchesACTUATOR TYPE P2500P4000 E18.319.3 F5.35.3 G H12.7 5.112.7 5.6 O1.82.2 V165165 WM20x30M20x30

Adjustable range

90° actuators

Hmax.

F

W O

+0.5°

Emerson Process Management P2500 — F diagram (page 5)
Afb. 5

Copyright © Emerson Process Management. The information in this document is subject to change without notice. Updated data sheets can be obtained from our website www.El-O-Matic.com or from your nearest Valve Automation Center USA: +1 813 319 0266 Europe: +31 74 256 10 10 Asia-Pacific: +65 6501 4600

Show 10 more labels / short text on this page
Actuator base · Drive shaft · +1° -15° · Open · Cover plate · Housing limit stop · -15° · Drive adaptor · Cam · Closed
Page 6 of the Emerson Process Management P2500 user manual — TM
Pagina 6 · klik om te vergroten
Pagina 6

Data sheet Sheet No.: Date: November 2009

A1.501.05 Rev. A EL-O-MATIC ACTUATOR WITH DOUBLE STROKE ADJUSTMENT DSA

adjustable range

Description Actuators with double stroke adjustment are normally used for high performance butterfly valves where a fine adjustment is required for the closed position. In this version adjustment is provided at the end of the opening and closing stroke positions. DSA actuators may be double acting or spring return, though are normally used as spring return (fail close) actuators.

Operation The closed position is adjusted by means of the stop-screw (1) located in the actuator body and for the open position by the stop-screws (2) in the actuator end caps.

Y

Identification See data sheet A1.102.10

Factory optionFail to Open

A B

Specification Pressure : Up to 120 psi Operating media : Air, dry or lubricated or non‑corrosive gas Torque (90°) : Data sheet A1.104.01 ‑ A1.104.02 Rotation - - Spring return : Clock-wise on air failure. - Double acting : Counter clock-wise with port “A” pressurised. Other dimensions : Data sheet A1.103.XXX Temperature : -4° to +176° F Adjustable range : Closed position (1), -3° - 15° Open position (2), 80° - 93°

D

J 1

H

Dim. in inch.Actuator type E25 E40E65 E100E150E200E350E600E950E1600 A DA6.26 7.097.83 8.7010.0011.14 12.0115.3517.3220.47 B SR6.77 8.039.80 10.5112.2014.17 15.2418.9020.9425.24 C3.15 3.664.13 4.655.515.637.138.6610.2011.69 D0.79 0.790.79 0.790.790.790.791.181.181.18 H2.91 3.393.86 4.254.765.046.818.159.09264.00 I1.81 2.012.26 2.482.762.873.714.454.965.59 J11.11 1.381.57 1.721.922.122.853.504.034.50 L Y 1/ X0.45 0.61 4"-20 5/16"-18 1.42 1.630.61 0.73 5/16"-19 3/8"-16 1.63 1.990.97 3/8"-16 2.360.97 1/2"-13 1 2.460.97 /2"-13 2.851.63 5/8"-11 4.021.63 5/8"-11 4.021.87 3/4"-10 4.31

1 2 Stroke adjustment cam Factory option: "Fail open"

TM

Copyright © Emerson Process Management. The information in this document is subject to change without notice. Updated data sheets can be obtained from our website www.El-O-Matic.com or from your nearest Valve Automation Center USA: +1 813 319 0266 Europe: +31 74 256 10 10 Asia-Pacific: +65 6501 4600

Show 5 more labels / short text on this page
Open stopscrew (2) · 3° 10° · 15° · 3° · Closed stopscrew (1)
Page 7 of the Emerson Process Management P2500 user manual — P4000
Pagina 7 · klik om te vergroten
Pagina 7

Data sheet

Sheet No.: Date: May 2011

A1.103.106 Rev. D DIMENSION SHEET STANDARD ACTUATOR - ISO E/P

UNC 10-24x.31

Dim. in inchActuators E-seriesP-series E 12E 25E 40E 65E100E150E200E 350E600E950E1600P2500P4000 A DAFor E12 dimensions see data sheet A1.103.1026.267.097.838.7010.0011.1412.0115.2416.6920.3114.8819.76 B SR6.778.039.8010.5112.2014.1715.2418.7820.3525.0822.4432.83 C3.153.664.134.655.515.637.138.6610.2011.6914.0214.96 D0.790.790.790.790.790.790.791.181.181.181.181.18 E0.630.870.870.871.421.421.422.172.172.522.172.52 E20.911.181.181.181.771.771.772.562.562.952.563.15 F0.390.550.550.550.750.750.751.421.421.421.421.42 G H0.47 2.910.47 3.390.47 3.860.47 4.250.47 4.760.47 5.040.47 6.810.39 8.150.39 9.090.39 10.430.39 13.780.39 14.96 I J K1.81 1.26 0.942.09 1.32 1.302.26 1.54 1.302.48 1.59 1.502.76 1.59 2.172.87 1.99 2.173.71 2.85 2.174.45 3.33 2.684.96 4.15 2.955.59 4.74 3.747.28 7.01 3.357.87 7.48 4.72 M11.361.361.361.361.971.971.972.052.523.232.603.03 M2---1.06-1.461.46----- M30.6690.6690.6690.7870.7871.1611.1611.1611.9492.303-- N0.040.040.040.060.040.060.060.060.060.060.120.06 O max.0.4370.5560.5560.7530.8710.8711.0681.0681.4241.8171.8172.173 O min.0.4330.5510.5510.7480.8660.8661.0631.0631.4171.8111.8112.165 P0.5550.7130.7130.9921.1101.1101.4251.4251.8982.3702.3702.843 P1 P20.555 -0.713 -0.831 -0.909 0.9881.303 1.2641.303 1.2641.303 1.2641.437 -1.909 -2.382 -- -- - R2.052.562.762.763.393.544.494.885.126.066.696.69 R1 R21.97 -1.97 -1.97 -2.36 -3.54 -3.54 -4.92 5.206.30 -6.30 10.31 S2.052.562.762.763.623.544.494.885.5911.0211.4211.42 S13.943.943.943.943.943.943.946.696.698.279.659.65 T13.1503.1503.1503.1503.1503.1503.1505.1185.1185.1185.1185.118 U11.1811.1811.1811.1811.1811.1811.1811.1811.1811.1811.1811.181 F03F05F05F05F07F07F07F10F10F16F16F16 V1.4171.9691.9691.9692.7562.7562.7564.0164.0166.4966.4966.496 W10-24 x.31"1/4"-20 x.39"1/4"-20 x.39"1/4"-20 x.39"5/16"-18 x.39"5/16"-18 x.39"5/16"-18 x.39"3/8"-16 x.63"3/8"-16 x.63"3/4"-10 x1.14"3/4"-10 x1.14"3/4"-10 x1.14" F05F07F07F07F10F10F10F12F14--F25 V11.9692.7562.7562.7564.0164.0164.0164.9215.512--10.000 W11/4"-20 x.39"5/16"-18 x.39"5/16"-18 x.39"5/16"-18 x.39"3/8"-16 x.63"3/8"-16 x.63"3/8"-16 x.63"1/2"-13 x.79"5/8"-11 x.98"--"5/8""-11 x.98"

T1

UNC 10-24x.31

B

U1 R1

S1 A

0.95 1/4”NPT

E

F G

M6x.47

D

E2

J

A B

H

E-series

P-series

M1 M2

M1

M3

N ±0.02

N ±0.02

T

øP+0.02

W

W2

øP+0.02

W1

O

R

O

U

R

E25-E950

S

W

P2500

S

S

W

W1

E1600

R2

R R2

5/8”-11 x .98”

P4000

Copyright © Emerson Process Management. The information in this document is subject to change without notice. Updated data sheets can be obtained from our website www.El-O-Matic.com or from your nearest Valve Automation Center USA: +1 813 319 0266 Europe: +31 74 256 10 10 Asia-Pacific: +65 6501 4600

Show 9 more labels / short text on this page
øP2 · øP1 · øK · øK · øV · øV1 · øV · øV1 · øV
Page 8 of the Emerson Process Management P2500 user manual — Data sheet Sheet No.: Date: November 2009
Pagina 8 · klik om te vergroten
Pagina 8

Data sheet Sheet No.: Date: November 2009

A1.103.102 Rev. A DIMENSION SHEET ACTUATOR ISO E12 (90°/180°)

Emerson Process Management P2500 — Data sheet Sheet No.: Date: November 2009 diagram (page 8)
Afb. 6 · Data sheet Sheet No.: Date: November 2009
Dim. in Inches90°180° A ED4.066.10 B ES4.658.50 C2.362.36 D0.790.79 E0.630.63 E20.910.91 F0.390.39 G0.470.47 H2.362.36 I1.301.30 J0.830.83 K0.500.50 K10.250.25 L1.001.00 L12.002.00 M0.650.65 N0.0390.039 Omax.0.3580.358 Omin.0.3540.354 P0.4760.476 R1.571.57 R11.571.57 T1.571.57 U1.221.22 V1.6541.654 W10-24 UNCx.24" 10-24 UNCx.24" W110-24 UNCx.24" 10-24 UNCx.24" W210-24 UNCx.24" 10-24 UNCx.24" X1/8"NPT1/8"NPT YM6x.48M6x.48
Pressurepsi405060708090100120 Torque 90°/180°(in.lb.)597489104119134149179
Air strokeSpring stroke Pressurepsi6080100 Position-startendstartendstartendstartend Torque 90°(in.lb.)48238055112876441 Torque 180°(in.lb.)49258157112886340
Emerson Process Management P2500 — Data sheet Sheet No.: Date: November 2009 diagram (page 8)
Afb. 7 · Data sheet Sheet No.: Date: November 2009

Copyright © Emerson Process Management. The information in this document is subject to change without notice. Updated data sheets can be obtained from our website www.El-O-Matic.com or from your nearest Valve Automation Center USA: +1 813 319 0266 Europe: +31 74 256 10 10 Asia-Pacific: +65 6501 4600

Page 9 of the Emerson Process Management P2500 user manual — insert shapes
Pagina 9 · klik om te vergroten
Pagina 9

Data sheet

Sheet No.: Date: May 2011

A1.103.200 Rev. B Drive inserts for El-O-Matic actuators E

Standard available

Insert mounting

Description Most of the El-O-Matic actuators are fitted with drive inserts. This enables actuators to be directly mounted onto suitable valves and eliminates the need for a bracket and coupling type mounting kit. The use of direct mounts significantly cuts the cost of the valve/actuator assembly.

insert shapes

acc. ISO 5211

sq Max. Ø P2 Ø P1 Optional available insert shapes M1 M2 D Max. D Max. E25 0.43 0.35 0.39Standard inserts with inner-square-dimensions per actuator type E40 / E65E100E150E200E350E600 E950 E1600 3 0.5510.7480.8660.8661.0631.063 1.417 1.811 Optional insert dimensions 4 0.3940.4720.5510.5510.5510.551 0.866 4 0.4720.5510.6300.6300.6300.630 0.630.6690.6690.6690.669 0.7480.7480.7480.748 0.9450.9450.8660.866 1.0631.0630.9450.945 Maximum insert dimensions M1 1.361.361.361.971.971.972.05 2.52 3.23 M2 --1.061.461.461.46-- - P1 0.710.710.911.261.261.261.44 1.91 2.38 P2 --0.991.431.431.43-- - Sq max. 0.630 0.6300.7481.0631.0631.0631.063 1.417 1.811 D max. 0.827 0.8270.9291.3231.3231.3231.323 1.772 2.362

Standard actuators are fitted with square drive inserts in accordance with ISO 5211 (or DIN 3337), but a wide variety of other inserts are also available. Special inserts may have oversize or undersize squares, double-D and shaft key way forms.

Drive inserts can be supplied on factory built actuators or as loose items and are easily replaceable at distributor or end user level.

Where direct mounts are not possible, for instance on valves with exposed grand packing, the use of inserts often simplifies the design of the mounting kit.

MaterialAluminum alloy Finish : Anodized

The following actuator types do not have inserts. - E12, - P2500 and P4000 - 180° actuators

These actuators have inner square directly in the bottom of the pinion. See the following data sheets for more information :

E12 ISO5211 A1.103.102 P2500/P4000 ISO 5211 A1.103.106 180° ISO 5211 A1.203.011

Copyright © Emerson Process Management. The information in this document is subject to change without notice. Updated data sheets can be obtained from our website www.El-O-Matic.com or from your nearest Valve Automation Center USA: +1 813 319 0266 Europe: +31 74 256 10 10 Asia-Pacific: +65 6501 4600

Page 10 of the Emerson Process Management P2500 user manual — DOUBLE ACTING TORQUE
Pagina 10 · klik om te vergroten
Pagina 10

Data sheet Sheet No.: Date: January 2010

A1.104.01 Rev. B DOUBLE ACTING ACTUATOR TORQUE (In.lb.) 90°

ActuatorTorque of double acting actuators (in In.lb) Supply pressure (psi) Type Size3035404550556070758090100120 ED 1243.951.458.966.473.981.488.9104111119134149179 ED 2581.495.3109123137151165193206220248276332 ED 40153179205231257283309361387413466518622 ED 65233272312352392431471551590630709789948 ED 100344402461520578637696813872930104811651400 ED 15055164573983392710211115130313971491168018682244 ED 20075488310111140126913981527178419132042229925573072 ED 3501310153417571981220524282652310033233547399444425337 ED 6002226260629863366374741274507526756476028678875489069 ED 9503323389044585025559361606728786284308997101321126713537 ED 1600549364317369830792451018311121129981393614874167501862622379 PD 25008774102731182513270147681626717847208582236323869268802989135912 PD 400014874174141996222495250352757630127352103775140293453755045860623

DOUBLE ACTING TORQUE

Emerson Process Management P2500 — DOUBLE ACTING TORQUE diagram (page 10)
Afb. 8

(Counter Clock Wise or Clock Wise) these maximum requirements occur. 2. If in doubt, or you require any assistance with sizing actuators, do not hesitate to contact your nearest Emerson's Valve Automation Division representative. 3 Pressure on port "A" opens the actuator* 4 The actuator is shown in closed position*

(* code A, data sheet A1.503)

Emerson Process Management P2500 — DOUBLE ACTING TORQUE diagram (page 10)
Afb. 9

Copyright © Emerson Process Management. The information in this document is subject to change without notice. Updated data sheets can be obtained from our website www.El-O-Matic.com or from your nearest Valve Automation Center USA: +1 813 319 0266 Europe: +31 74 256 10 10 Asia-Pacific: +65 6501 4600

Page 11 of the Emerson Process Management P2500 user manual — SPRING STROKE AIR STROKE
Pagina 11 · klik om te vergroten
Pagina 11

Data sheet Sheet No.: Date: January 2010

A1.104.02 Rev. B SPRING RETURN ACTUATOR TORQUE (In.lb.) 90°

SINGLE ACTING TORQUE

Springset nr.Air Stroke (lbf/in)Spring Stroke SUPPLY PRESSURE (in PSI) Actuator Type406080100120(lbf/in) CDCDCDCDC DEF ES 122--4824805511187143 119 6340 ES 252 3 4 5 67144130103189162248221306 280 6239 48810767166126225185284 244 9459 --853114490203149262 208 12578 ----12154180113239 172 15698 ----991815877217 136 188117 ES 40213382243193354303464414575 524 11773 39115201125312236422346533 457 176110 4--15958270169380279491 390 234146 5----228101338212449 322 293183 6----18534296144406 255 351220 ES 652196117365285533454701622870 790 186117 312910297178466347634515802 683 279176 4--23071398240567408735 576 372234 5----331133500301668 470 465292 6----26426432194601 363 558351 ES 100230319255244180169010509391299 1188 258161 3211444602937095429587911206 1039 387242 4--3671446163938656421114 891 516323 5----5232457724941021 743 646403 6----43096679345928 594 775484 ES 150248529788469612831094168114932080 1892 423259 3337547354531134852153312501931 1649 634388 4--587210985609138410071783 1406 845517 5----83736612357641634 1163 1056647 6----68812310875221485 920 1268776 ES 2002656406120295217471498229320432838 2589 579362 3 4448 -74 -994 786619 2871539 13321165 8322085 18771710 13782631 22 2423 1956 868 24 1158542 723 5----1124500166910452215 1591 1447904 6----91616714627132007 1258 17361085 ES 350211056842053163230012580394935284897 4476 1025658 3727951675104326231991357129394519 3887 1537987 4--129745522451403319323514141 3299 20491317 5----1866814281417623762 2710 25611646 6----1488225243611733384 2121 30741975 ES 6002192011833531279451424405675360168364 7628 17231082 312981932909180445203415613150267742 6637 25851624 4--228781438982425550940367120 5647 34462165 5----32761434488730466498 4657 43082706 6----2654444426520555876 3666 51693247 ES 950228981777530341827708658710113899212518 11397 25631587 3198630443912709679651149201751911606 9924 38442381 4--34791236588436418288604610693 8451 51253175 5----49712168737645739781 6978 64073968 6----4059695646431008869 5505 76884762 ES 1600247652988874169641271610939166921491520668 18890 41932646 3324457872204554111968530151711250519147 16481 62893970 4--5699214596756120136501009617626 14071 83855293 5----8154371112129768616105 11662 104816616 6----6633130110608527714584 9252 125787939

SPRING STROKE AIR STROKE

Emerson Process Management P2500 — SPRING STROKE AIR STROKE diagram (page 11)
Afb. 10

identify at which position(s) and direction(s) of rotation (Counter Clock Wise or Clock Wise) these maximum requirements occur. 2. If in doubt, or you require any assistance with sizing actuators, do not hesitate to contact your nearest Emerson's Valve Automation Division representative. 3 Pressure on port "A" opens the actuator* 4 The actuator is shown in closed position* (* code A, data sheet A1.504)

Springset nr.Air Stroke (lbf/in)Spring Stroke SUPPLY PRESSURE (in PSI) Actuator Type406080100120(lbf/in) CDCDCDCDCDEF PS 25006 8 10 12 1468814278128751027318869162672486322261308582825570134401 5251178111245777517239137692323319764292282575893515868 --96155278156091127221603172662759723260116897335 --7985278013979877419973147682596720763140268803 ----123496277183431227124337182651636410270 PS 40006 8 10 12 141170173102186217472320242763342185377955234747956118357429 894930961911113257292722341939434335804959543742157809905 --1635990422652119204366822936546844395271972512381 --1360848282377014989339312515044093353122367014857 ----2101810774311802093641341310972761517333
Emerson Process Management P2500 — SPRING STROKE AIR STROKE diagram (page 11)
Afb. 11

Copyright © Emerson Process Management. The information in this document is subject to change without notice. Updated data sheets can be obtained from our website www.El-O-Matic.com or from your nearest Valve Automation Center USA: +1 813 319 0266 Europe: +31 74 256 10 10 Asia-Pacific: +65 6501 4600

Torque · F End

Page 12 of the Emerson Process Management P2500 user manual — Optional center-plate
Pagina 12 · klik om te vergroten
Pagina 12

Data sheet Sheet No.: Date: November 2009

A1.101.33 Rev. A Construction, Parts and Materials E-Serie Actuators E

PartsMaterialsExcecutions Nr.DescriptionQty.DescriptionSpecification StS.S. d ShaftCSR 1 2 3 4 5 6 7 8 9 10 11 12 20 21 22 23 25 26 27 28 29 30 34 35 36 37 38 40 41 42 43 44*Body Piston Drive pinion End Cap ED End Cap ES Springinner Springmid Springouter Spring Holder Guide Band Guide Band Bearing Bush Bearing Bush O-ring Washer ES Washer ED O-ring O-ring Washer O-ring O-ring O-ring Washer ES Spring Clip End Cap Bolt ED/ES Limit Stop Bolt ES Nut Limit Stop Bolt ED Nut Nut Cover O-ring Insert1 2 1 2 1 2 1 1 1 2 1 1 4 2 2 1 8 2 1Aluminum Alloy Aluminum Alloy GAlSi10Mg, DIN 1725/2 Aluminum Alloy Aluminum Alloy Carbon Spring Steel Carbon Spring Steel Carbon Spring Steel Steel Nylatron PTFE, Carbon filled Nylatron Delrin Nitrile Rubber Nylon Nylon Nitrile Rubber Nitrile Rubber ZEDEX 100 K Nitrile Rubber Nitrile Rubber Nitrile Rubber Steel Carbon Spring Steel Stainless Steel Stainless Steel Stainless Steel Stainless Steel Stainless Steel Polyethylene Nitrile Rubber Aluminum AlloyUNS A13600, ASTM B85 - UNS A03560, ASTM B26 - UNS 1 77075, ASTM 7075 T6 1 UNS A13600, ASTM B85 - UNS A13600, ASTM B85 - UNS G10860, ASTM A228 2 UNS G10860, ASTM A228 2 UNS G10860, ASTM A228 2 C45, DIN 17200 3 PA6.6 + MoS2 - PTFE + 25% C - PA6.6 + MoS2 - POM - Buna N - PA6 - PA6 - Buna N - Buna N - - - Buna N - Buna N - Buna N - C35 3 MIL - R-212 48B 2 AISI 304 - AISI 304 - AlSl 304 - AISI 304 - AISI 304 - PE - Buna N - UNS 1 6082, ASTM 6082 4- - 6 - - 2 2 2 3 - 3 7 - 95 - 6 5 5 2 2 2 3 - 3 7 - 4

Optional center-plate

Remark All materials are European origin, listed are the nearest US equivalents. Finish Standard : Polyester non-TGIC based powder coating (see data sheet A4.204.01) CSR : CSR Coating (see data sheet A4.204.02)

Emerson Process Management P2500 — Optional center-plate diagram (page 12)
Afb. 12 · Optional center-plate

Copyright © Emerson Process Management. The information in this document is subject to change without notice. Updated data sheets can be obtained from our website www.El-O-Matic.com or from your nearest Valve Automation Center USA: +1 813 319 0266 Europe: +31 74 256 10 10 Asia-Pacific: +65 6501 4600

Page 13 of the Emerson Process Management P2500 user manual — Nr. Description Qty. Description Specification Std S.S. Shaft CSR
Pagina 13 · klik om te vergroten
Pagina 13

Data sheet Sheet No.: Date: November 2009

A1.101.30 Rev. A Construction, Parts and Materials P-serie actuators P

Parts Materials Excecutions

Emerson Process Management P2500 — Parts Materials Excecutions diagram (page 13)
Afb. 13 · Parts Materials Excecutions

Nr. Description Qty. Description Specification Std S.S. Shaft CSR

1 Body 1 Aluminum Alloy UNS A13600, ASTM B85 - - 6 2 Piston 2 Aluminum Alloy UNS A03560, ASTM B26 - - - 3 Endcap PDA 2 Aluminum Alloy UNS A13600, ASTM B85 - - 6 4 Endcap PSA 2 Aluminum Alloy UNS A13600, ASTM B85 - - 6 5 Drive pinion 1 Aluminum Alloy UNS 1 77075, ASTM 7075 T6 1 4 4 6 Gear Rack 2 Steel UNS G10950, ASTM A108 - - - 8 Spring 14 Carbon Spring Steel UNS G10860, ASTM A228 2 2 2 9 * Bearing Bush 1 Nylatron GS PA6.6 + MoS2 - - - 10 * Bearing Bush 1 Delrin POM - - - 14 * Guide band 2 PTFE, Carbon filled PTFE + 25% C - - - 15 * Guide band 2 PTFE, Carbon filled PTFE + 25% C - - - 16 * O-ring 2 Nitrile Rubber Buna N - - - 17 * O-ring 2 Nitrile Rubber Buna N - - - 18 * O-ring 1 Nitrile Rubber Buna N - - - 19 * O-ring 1 Nitrile Rubber Buna N - - - 20 * Spring Clip 1 Carbon Spring Steel MIL - R-212 48B 2 5 5 21 * Thrust Washer 1 ZEDEX 100 K - 23 Bolt 4 Alloy Steel 12.9 ASTM F568 - - - 24 Endcap bolt PDA 20 Alloy Steel 8.8 ASTM F568 2 4 4 25 Endcap bolt PSA 20 Alloy Steel 8.8 ASTM F568 2 4 4 26 * O-ring 2 Nitrile Rubber Buna N - - - 27 Threaded insert 20 Steel UNS G10430, ASTM A29 3 3 3 * Recommended spare parts (contained in Repair kit)

6 CSR Coating (see A4.204.02) 7 P4000 has a stainless steel (AISI 304) locking ring between spring clip (20) and thrust washer (21) 8 P4000 has in the springs a guiding bush (PVC)

Remark All materials are European origin, listed are the nearest US equivalents

Finish Standard : Polyester non-TGIC based powder coating (see data sheet A4.204.01) CSR : CSR Coating (see data sheet A4.204.02)

Emerson Process Management P2500 — Nr. Description Qty. Description Specification Std S.S. Shaft CSR diagram (page 13)
Afb. 14 · Nr. Description Qty. Description Specification Std S…

Copyright © Emerson Process Management. The information in this document is subject to change without notice. Updated data sheets can be obtained from our website www.El-O-Matic.com or from your nearest Valve Automation Center USA: +1 813 319 0266 Europe: +31 74 256 10 10 Asia-Pacific: +65 6501 4600

Page 14 of the Emerson Process Management P2500 user manual — Data sheet Sheet No.: Date: November 2009
Pagina 14 · klik om te vergroten
Pagina 14

Data sheet Sheet No.: Date: November 2009

A1.101.60 Rev. A CONSTRUCTION, PARTS AND MATERIALS DSA ACTUATOR

DSA

Nr. Description Qty. Material Specification Note 1 Body DSA 1 Aluminum Alloy UNS A13600, ASTM B85 - 2 Piston DSA 2 Aluminum Alloy UNS A03560, ASTM B26 - 3 Drive pinion DSA 1 Aluminum Alloy UNS 1 77075, ASTM 7075 T6 1 4 * Guide Band DSA 1 Nylatron GS UNS A13600, ASTM B85 - 5 Cam for stroke adj. DSA 1 Stainless Steel UNS A13600, ASTM B85 - 6 Shaftpin for stroke adj. DSA 1 Chrome nickel steel UNS G10860, ASTM A228 - 7 * Washer 1 ZEDEX 100 K - - 8 * Washer 1 Nylon UNS G10860, ASTM A228 - 9 * O-ring shaft top 1 Nitrile Rubber C45, DIN 17200 - 10 * O-ring limit stop bolt DSA 1 Nitrile Rubber PA6.6 + MoS2 - 11 Circlip 1 Carbon spring steel PTFE + 25% C 2 12 Limitstop bolt DSA 1 Stainless Steel PA6.6 + MoS2 - 13 Nut 1 Stainless Steel POM - 14 Nut Cover 1 Polyethylene Buna N - * Recommended spare parts (contained in Repair kits DSA)

Emerson Process Management P2500 — Data sheet Sheet No.: Date: November 2009 diagram (page 14)
Afb. 15 · Data sheet Sheet No.: Date: November 2009

Finish Polyester non-TGIC based powder coating (see data sheet A4.204.01)

Remark This data sheet shows only the extra or specific parts of a DSA actuator. For all the other parts see data sheet A1.101.33

Emerson Process Management P2500 — Data sheet Sheet No.: Date: November 2009 diagram (page 14)
Afb. 16 · Data sheet Sheet No.: Date: November 2009

Copyright © Emerson Process Management. The information in this document is subject to change without notice. Updated data sheets can be obtained from our website www.El-O-Matic.com or from your nearest Valve Automation Center USA: +1 813 319 0266 Europe: +31 74 256 10 10 Asia-Pacific: +65 6501 4600

Page 15 of the Emerson Process Management P2500 user manual — Drive Shaft
Pagina 15 · klik om te vergroten
Pagina 15

Data sheet

-40°C / +80°C

Sheet No.: Date: June 2010

A1.101.70 Rev. C LOW TEMPERATURE ACTUATOR SPECIFICATIONS

-40°F / +176°F

Description A double piston, rack and pinion pneumatic actuator incorporating a three point piston support system, anti-blowout spindle and with high duty synthetic bearings at all bearing points.

Silicone MVQ 70 Sealings

This version is a standard aluminum actuator, but incorporating parts and materials suitable for low temperature operation.

Specification Max. pressure : 120 psi (8 bar) Torque : Standard Media : Air or non corrosive gas Temperature : -40°F to +176°F (-40°C to +80°C) Finish : Polyester non-TGIC based powder coating (see data sheet A4.204.01)

Spare parts Dedicated low temperature spare parts are available for maintenance or make a standard actuator suiteable for low temperature operation.

Materials

Part Material Specifications Remark Housing Aluminum Alloy UNS A13600, ASTM B85

Aluminum Alloy UNS 1 77075, ASTM 7075 T6 Hard anodized Steel (180° rotation) ETG100 or 42CrMo4V XM Zinc Plated type > P750 Stainless Steel Sandvic 1802, SS2382 or X35CrM017 type > E950 Piston Aluminum Alloy UNS A03560, ASTM B26 Sealings Silicone MVQ 70 O-rings -/- Grease Castrol Optitemp TT1 -/-

Drive Shaft

Shaft bearings TopDelrin POM Bottom : Nylatron PA6.6 + MoS2 Piston bearings PTFE 25% Carbon filled

Bodybearings PTFE (“P” serie) 25% Carbon filled Nylatron (“E” serie) PA6.6 + MoS2 Shaft thrust washer ZEDEX 100 K -/-

End cap bolts Stainless Steel (“E” serie) AISI 304 A2 Alloy Steel (“P” serie) 8.8 DIN 912 Deltatone® coating Springs Carbon Spring Steel UNS G10860, ASTM A228 Deltatone® coating

Copyright © Emerson Process Management. The information in this document is subject to change without notice. Updated data sheets can be obtained from our website www.El-O-Matic.com or from your nearest Valve Automation Center USA: +1 813 319 0266 Europe: +31 74 256 10 10 Asia-Pacific: +65 6501 4600

Castrol Optitemp TT1 · Low Temperature · Grease

Page 16 of the Emerson Process Management P2500 user manual — Drive Shaft
Pagina 16 · klik om te vergroten
Pagina 16

Data sheet

-20°C / +120°C

Sheet No.: Date: January 2010

A1.101.71 Rev. B HIGH TEMPERATURE ACTUATOR SPECIFICATIONS

-4°F / +248°F

Description A double piston, rack and pinion pneumatic actuator incorporating a three point piston support system, anti-blowout spindle and with high duty synthetic bearings at all bearing points.

This version is a standard aluminum actuator, but incorporating parts and materials suitable for high temperature operation.

Specification Max. pressure : 8 bar ~ 120psi Torque : Standard Media : Air or non corrosive gas Temperature : -4°F to +248°F (-20°C to +120°C) Finish : Polyester non-TGIC based powder coating (see data sheet A4.204.01)

Spare parts Dedicated high temperature spare parts are available for maintenance or make a standard actuator suiteable for high temperature operation.

Materials

Part Material Specifications Remark Housing Aluminum Alloy UNS A13600, ASTM B85

Aluminum Alloy UNS 1 77075, ASTM 7075 T6 Hard anodized Steel (180° rotation) ETG100 or 42CrMo4V XM Zinc Plated type > P750 Stainless Steel Sandvic 1802, SS2382 or X35CrM017 type > E950 Piston Aluminum Alloy UNS A03560, ASTM B26 Sealings Viton FPM O-rings -/- Grease Castrol LMX -/-

Drive Shaft

Shaft bearings TopDelrin POM Bottom : Nylatron PA6.6 + MoS2 Piston bearings PTFE 25% Carbon filled

Bodybearings PTFE (“P” serie) 25% Carbon filled Nylatron (“E” serie) PA6.6 + MoS2 Shaft thrust washer ZEDEX 100 K -/-

End cap bolts Stainless Steel (“E” serie) AISI 304 A2 Alloy Steel (“P” serie) 8.8 DIN 912 Deltatone® coating Springs Carbon Spring Steel UNS G10860, ASTM A228 Deltatone® coating

Copyright © Emerson Process Management. The information in this document is subject to change without notice. Updated data sheets can be obtained from our website www.El-O-Matic.com or from your nearest Valve Automation Center USA: +1 813 319 0266 Europe: +31 74 256 10 10 Asia-Pacific: +65 6501 4600

Show 4 more labels / short text on this page
Viton · Castrol · FPM Sealings · LMX Grease
Page 17 of the Emerson Process Management P2500 user manual — TM
Pagina 17 · klik om te vergroten
Pagina 17

Data sheet Sheet No.: Date: November 2009

A4.201 Rev.A INSTALLATION OF SPRINGS OF P-SERIES ACTUATOR P

4 SPRINGS 6 SPRINGS 8 SPRINGS

10 SPRINGS 12 SPRINGS 14 SPRINGS

SPRING

TM

Copyright © Emerson Process Management. The information in this document is subject to change without notice. Updated data sheets can be obtained from our website www.El-O-Matic.com or from your nearest Valve Automation Center USA: +1 813 319 0266 Europe: +31 74 256 10 10 Asia-Pacific: +65 6501 4600

Page 18 of the Emerson Process Management P2500 user manual — TM
Pagina 18 · klik om te vergroten
Pagina 18

Data sheet Sheet No.: Date: November 2009

A4.202 Rev.A INSTALLATION OF SPRINGS OF E-SERIES ACTUATOR E

SPRING SET No. 1 inner spring

SPRING SET No. 2 mid spring

SPRING SET No. 3 inner spring mid spring

SPRING SET No. 4 inner spring outer spring

SPRING SET No. 5 mid spring outer spring

SPRING SET No. 6 inner spring mid spring outer spring

TM

Copyright © Emerson Process Management. The information in this document is subject to change without notice. Updated data sheets can be obtained from our website www.El-O-Matic.com or from your nearest Valve Automation Center USA: +1 813 319 0266 Europe: +31 74 256 10 10 Asia-Pacific: +65 6501 4600

Page 19 of the Emerson Process Management P2500 user manual — All views are from above Pistons are shown in inner position A
Pagina 19 · klik om te vergroten
Pagina 19

Data sheet Sheet No.: Date: November 2009

A1.503 Rev. A DOUBLE ACTING ACTUATOR ASSEMBLY MODES E/P

Emerson Process Management P2500 — Data sheet Sheet No.: Date: November 2009 diagram (page 19)
Afb. 17 · Data sheet Sheet No.: Date: November 2009

All views are from above Pistons are shown in inner position A

(OPTIONAL L1/LF) LIMIT STOPS WILL ADJUST THE VALVE AT OPEN POSITION

(OPTIONAL L1/LF) LIMIT STOPS WILL ADJUST THE VALVE AT CLOSED POSITION

Copyright © Emerson Process Management. The information in this document is subject to change without notice. Updated data sheets can be obtained from our website www.El-O-Matic.com or from your nearest Valve Automation Center USA: +1 813 319 0266 Europe: +31 74 256 10 10 Asia-Pacific: +65 6501 4600

Page 20 of the Emerson Process Management P2500 user manual — A All views are from above Pistons are shown in inner position
Pagina 20 · klik om te vergroten
Pagina 20

Data sheet Sheet No.: Date: November 2009

A1.504 Rev. A SPRING RETURN ACTUATOR ASSEMBLY MODES E/P

Emerson Process Management P2500 — Data sheet Sheet No.: Date: November 2009 diagram (page 20)
Afb. 18 · Data sheet Sheet No.: Date: November 2009

A All views are from above Pistons are shown in inner position

Copyright © Emerson Process Management. The information in this document is subject to change without notice. Updated data sheets can be obtained from our website www.El-O-Matic.com or from your nearest Valve Automation Center USA: +1 813 319 0266 Europe: +31 74 256 10 10 Asia-Pacific: +65 6501 4600

Page 21 of the Emerson Process Management P2500 user manual — See data sheet A4.204.02
Pagina 21 · klik om te vergroten
Pagina 21

Data sheet

A4.204.01 Rev.B EL-O-MATIC STANDARD CORROSION PROTECTION SYSTEM Sheet No.: Date: April 2011

Description The corrosion protection system of standard El-O-Matic E&P series pneumatic actuators consist of the following treatments or materials:

1 De-greasing All aluminum parts are de-greased before the powder coating is applied by washing with an alkaline

High grade aluminum alloy, hard anodized (Option : Stainless steel) Stainless steel fasteners

solution to assure the best bonding between the aluminum surface and the coating.

2 Powder coating - Polyester non-TGIC based powder coating for exterior use. - The powder coating is applied cold using automatic electrostatic spray equipment and is cured at

Emerson Process Management P2500 — Data sheet diagram (page 21)
Afb. 19 · Data sheet

minimum 190°C (374°F) offering excellent anti color fade and weather resistance. - The powder coating thickness is 1.5 mm (37 microns) minimum, and 2 mm (50 microns) average. - Good resistance against most chemical bases, acids, solvents, alkalis and oils at normal temperatures. - Excellent exterior mechanical durability. - The coating has passed a salt spray test according to ASTM B117 for 500 hours. The powder coating is

virtually solvent free, and therefore environmentally friendly.

3 High grade & hard anodized aluminum pinion Actuators with high grade & hard anodized aluminum pinions, passed a 500 hours salt spray test.

Optional stainless steel pinions are available for a higher corrosion resistance.

4 Stainless steel or Deltatone® treated external steel parts External parts are stainless steel or steel alloy with a Deltatone® treatment.

Technical data: Coating : Polyester non-TGIC based powder coating Salt spray test : DIN 50021 / ASTM B117: 500h Color : Yellow (RAL 1007) Materials : Housing : Aluminum alloy : Pinion : High grade aluminum alloy, hard anodized

Powder coating: Polyester non-TGIC based powder coating for exterior use.

(Option : Stainless steel) : Fasteners : Stainless steel or alloy steel with Deltatone® treatment : Tagplate : Stainless steel Application : Standard EL-O-MATIC E & P series pneumatic actuators

For Non-Standard actuators, see data sheet A4.204.05 Option : CSR coating for excellent corrosion resistance

See data sheet A4.204.02

Emerson Process Management P2500 — See data sheet A4.204.02 diagram (page 21)
Afb. 20 · See data sheet A4.204.02

Copyright © Emerson Process Management. The information in this document is subject to change without notice. Updated data sheets can be obtained from our website www.El-O-Matic.com or from your nearest Valve Automation Center USA: +1 813 319 0266 Europe: +31 74 256 10 10 Asia-Pacific: +65 6501 4600

Page 22 of the Emerson Process Management P2500 user manual — Hard anodized aluminum (Option : Stainless steel) Stainless steel fasteners
Pagina 22 · klik om te vergroten
Pagina 22

Data sheet

Sheet No.: Date: June 2009

A4.204.02 Rev.B EL-O-MATIC ACTUATOR WITH CSR COATING CSR

Description EL-O-MATIC CSR-actuators have an excellent corrosion resistance in environments where the actuator is in contact with chemicals like caustic soda. The CSR coating itself is resistant to at least 1000 hours of salt spray test exposure. Together with the excellent mechanical properties, the CSR coating is "the" solution for very harsh environments.

CSR actuator housing and caps are completely coated (inside and out) with a ceramic filled fluoropolymer based epoxy resin, impregnated by a temperature of 240°C into the aluminum surface. Approximately 40% of the coating is impregnated into the aluminum, 60% stays on the surface of the component as a seal.

Hard anodized aluminum (Option : Stainless steel) Stainless steel fasteners

Emerson Process Management P2500 — Hard anodized aluminum (Option : Stainless steel) Stainless steel fasteners diagram (page 22)
Afb. 21 · Hard anodized aluminum (Option : Stainless steel) St…

Technical data Coating : Ceramic filled fluoropolymer based epoxy resin Layer thickness : 20 microns Salt spray test : DIN 50021 / ASTM B117: 1000 hours Max. temperature : -4° to 176°F (20° to + 80°C) Materials : Housing : Aluminum alloy : Shaft : Aluminum hard anodized : (Option : Stainless steel) : Fasteners : Stainless steel : Tagplate : Stainless steel Application : Optional on all EL-O-MATIC actuators

Chemical resistances Resistance to various inorganic chemicals, organic chemicals, gasolines, oils, detergents, etc. is generally good to excellent, but also depends on temperature and/or concentration. More detailed information available at data sheet A4.204.021

Emerson Process Management P2500 — Hard anodized aluminum (Option : Stainless steel) Stainless steel fasteners diagram (page 22)
Afb. 22 · Hard anodized aluminum (Option : Stainless steel) St…

Copyright © Emerson Process Management. The information in this document is subject to change without notice. Updated data sheets can be obtained from our website www.El-O-Matic.com or from your nearest Valve Automation Center USA: +1 813 319 0266 Europe: +31 74 256 10 10 Asia-Pacific: +65 6501 4600

Page 23 of the Emerson Process Management P2500 user manual — TM
Pagina 23 · klik om te vergroten
Pagina 23

Data sheet Sheet No.: Date: November 2009

A4.204.021 Rev.A CHEMICAL RESISTANCE LIST FOR CSR COATING CSR

Inorganic chemicals 1 Ammonium hydroxide (10%) 2 Nitric acid (10%) 1 Calcium chloride (~50%) 3 Nitric acid (50%) 3 Chlorine 1 Hydrochloric acid (10%) 3 Chromic acid 1 Hydrochloric acid (concentrated) 3 Hydrofluoric acid (50%) 1 Sulphuric acid (50%) 1 Caustic potash solution (10%) 3 Sulphuric acid (concentrated) 1 Sodium hypochlorite (saturated) 2 Sulphur dioxide 1 Caustic soda solution (10%) 1 Sulphur hexafluoride 1 Caustic soda solution (saturated) 2 Nitric oxide 1 Phosphoric acid (10%) 1 Hydrogen peroxide (100%) 1 Phosphoric acid (50%)

Fuels/lubricants 1 Two-star petrol (50°C) 1 Four-star petrol (50°C) 1 Fuel M 15 (50°C) 1 Diesel oil 1 Kerosene 1 to 2 Hypoid bevel gear oil Shell Spirax HD 90 (150°C) 1 Transmission oil Shell Spirax MA 80 (150°C)

Chemicals 1 Automatic transmission fluid Shell Dextra 11D 20-137 (150°C) 1 Engine oil, mineral, Mihag 1500-40 (150°C) 1 Engine oil, synthetic, Mobil SHC 10 W-40 3 Brake fluid Hydraulan DOT 4 1 Roller bearing grease DIN 51 825

Organic chemicals 3 Acetone 1 Glycerine 3 Acetonitrile 1 Hexane 3 Aniline 1 Isooctane 2 Benzene 1 Isopropanol 1 n-Butanol 1 Methanol 3 Butyl acetate 3 Methylene chloride 3 Chlorobenzene 3 Methyl ethyl ketone 3 Chloroforme 3 N.N-Dimethylformamide 3 o-Chlorophenol 3 N-Methylpyrrolidon 1 Cyclohexane 1 Oxalic acid 3 Cyclohexanone 1 Perchloroethylene 3 1,2-Dichloroethane 1 Petroleum ether 2 Diethyl ether 3 Phenol 2 Dioxane 1 Carbon bisulphide 1 Glacial acetic acid 1 Turpentine 1 Ethanol 2 Tetrachloroethane 3 Ethyl acetate 2 1,1,1-Trichloroethane 1 Ethylene glycol 1 Tetrachloromethane 1 Formaldehyde 3 Trichloroethylene 2 Freon 11 2 Toluene 2 Freon 22 1 Xylene

Technical detergents 2 Genkeene 2 1,1,1Trichloroethane 2 Triklone A 2 Perchloroethylene

Miscellaneous fluids 1 Glysantin (BASF)/water 1 Plasticizer DOP 1 Suds 1 Washing-up liquids 1 Household detergents 1 Linseed oil 1 Milk 1 Soapsuds 1 Silicone oils

1 Excellent 2 Limited resistance; it is recommended to perform field tests under the specified conditions. 3 Not recommended

EL-O-MATIC cannot be held responsible, either for any errors in this list or for their consequences. Because of continued testing this list is subject to change without notice.

TM

Copyright © Emerson Process Management. The information in this document is subject to change without notice. Updated data sheets can be obtained from our website www.El-O-Matic.com or from your nearest Valve Automation Center USA: +1 813 319 0266 Europe: +31 74 256 10 10 Asia-Pacific: +65 6501 4600

Page 24 of the Emerson Process Management P2500 user manual — W2
Pagina 24 · klik om te vergroten
Pagina 24

Data sheet Sheet No.: Date: November 2009

A1.203.011 Rev. A DIMENSION SHEET STANDARD 180° ACTUATOR 180°

T1

Dim. in mm.

ACTUATOR TYPE E12 P60 P150 P280 P500 P750 P1100 P2500 P4000 A DA

P60 - P750

M5x.31

M5x.31

9.17 11.61 13.94 16.30 17.60 19.76 24.92 29.61 B SR 10.08 13.07 17.09 19.57 21.77 25.24 32.17 42.95 C 3.98 5.31 6.30 7.48 9.21 9.72 14.02 14.96 D 0.79 0.79 0.79 1.18 E1 0.63 0.87 1.02 1.42 1.42 1.77 2.17 2.52 E2 0.91 1.18 1.38 1.77 1.77 2.17 2.56 3.15 F 0.39 0.55 0.55 0.75 0.75 1.18 1.42 1.42 G 0.47 0.47 0.47 0.75 0.75 0.39 0.39 0.39 H 3.98 5.43 6.61 7.56 9.41 9.84 13.54 14.65 I 2.28 2.95 3.50 4.29 5.28 5.31 7.20 7.87 J 1.69 2.09 2.72 3.74 4.57 4.92 7.01 7.48 K 1.10 1.50 1.89 2.20 2.20 2.95 3.35 4.72 M1 1.06 1.06 1.22 1.50 1.50 2.01 2.60 3.03 N 0.04 0.04 0.06 0.06 0.08 0.10 0.12 0.06 O max. 0.556 0.674 0.871 1.068 1.068 1.424 1.817 2.173 O min. 0.551 0.669 0.866 1.063 1.063 1.417 1.811 2.165 P 0.713 0.992 1.110 1.425 1.425 1.898 2.370 2.843 R 2.36 3.15 3.98 4.37 5.51 5.51 6.69 6.69 R1 2.01 2.36 2.80 3.19 3.94 4.72 6.30 6.30 R2 2.76 3.94 - 10.31 S 4.37 5.12 5.55 6.34 8.27 8.27 11.42 11.42 S1 4.37 5.12 5.55 5.55 6.30 8.27 9.65 9.65 T - 9.24 - T1 3.15 3.15 3.15 5.12 U - 3.83 - U1 1.18 F05 F07 F07 F10 F10 F14 F16 F16 V 1.969 2.756 2.756 4.016 4.016 5.512 6.496 6.496 W M6 x .35 M8 x .51 M8 x .51 M10 x .63 M10 x .63 M16 x .79 M20 x1.18 M20 x1.18 F07 F10 F10 F12 F12 - - F25 V1 2.756 4.016 4.016 4.921 4.921 - - 10.000 W1 M8 x .51 M10 x .63 M10 x .63 M12 x .63 M12 x .63 - - M16 x 0.98 W2 - M16 x 0.98 -

U1

R1

S1

G1/4"

E1

I M6x.47

F

G D

For E12 dimensions see A1.103.102

E2

J

H

A

B

S

O

M1 N ±0.02

K

R R2

U

M5x.31

W1 øP+0.02

W2

T

W

1.00 G1/2"

P1100 - P4000 P4000

TM

Copyright © Emerson Process Management. The information in this document is subject to change without notice. Updated data sheets can be obtained from our website www.El-O-Matic.com or from your nearest Valve Automation Center USA: +1 813 319 0266 Europe: +31 74 256 10 10 Asia-Pacific: +65 6501 4600

Show 6 more labels / short text on this page
øV1 · øV · 4xW · 8xW1 · øV1 · øV
Page 25 of the Emerson Process Management P2500 user manual — A B
Pagina 25 · klik om te vergroten
Pagina 25

Data sheet

Sheet No.: Date: June 2010

A1.204.01 Rev. C 180° DOUBLE ACTING ACTUATOR TORQUE (In.lb.) 180°

START END

Emerson Process Management P2500 — Sheet No.: Date: June 2010 diagram (page 25)
Afb. 23 · Sheet No.: Date: June 2010

Torque (in in.lb) Supply Pressure (PSI) 30 40 50 60 70 80

Emerson Process Management P2500 — Torque (in in.lb) Supply Pressure (PSI) 30 40 50 60 70 80 diagram (page 25)
Afb. 24 · Torque (in in.lb) Supply Pressure (PSI) 30 40 50 60…

rotation (Counter Clock Wise or Clock Wise) these maximum requirements occur. 2. If in doubt, or you require any assistance with sizing actuators, do not hesitate to contact your nearest Emerson's Valve Automation Division representative. 3. Pressure on port "A" opens the actuator* 4. The actuator is shown in closed position* 5. Do not exceed the maximum supply pressure of 6 bar / 87psi. (*code A, data sheet A1.503)

A B

Emerson Process Management P2500 — A B diagram (page 25)
Afb. 25

Copyright © Emerson Process Management. The information in this document is subject to change without notice. Updated data sheets can be obtained from our website www.El-O-Matic.com or from your nearest Valve Automation Center USA: +1 813 319 0266 Europe: +31 74 256 10 10 Asia-Pacific: +65 6501 4600

Page 26 of the Emerson Process Management P2500 user manual — A B
Pagina 26 · klik om te vergroten
Pagina 26

Data sheet

Sheet No.: Date: June 2010

A1.204.02 Rev. C 180° SPRING RETURN ACTUATOR TORQUE (In.lb.) 180°

SPRING STROKE AIR STROKE

Air Stroke (in.lb.) Spring Stroke SUPPLY PRESSURE (PSI)

nr.

Emerson Process Management P2500 — SPRING STROKE AIR STROKE diagram (page 26)
Afb. 26

40 50 60 70 80 (in.lb.)

C D C D C D C D C D E F ES12 2 - - 33 9 49 25 65 41 81 57 63 41 PE60 8 70 19 105 55 141 90 176 125 212 161 112 62

10. - 88 24 123 60 159 95 194 131 141 78
12. - - - 106 30 142 65 177 101 169 93
14. - 124 35 160 71 197 109 PE150 8 185 76 274 165 364 255 453 344 543 433 258 150
10. - 233 96 322 186 411 275 501 365 322 187
12. - - - 280 117 370 206 459 296 387 225
14. - - - 239 48 328 137 418 227 451 262 PE280 8 - - 493 193 662 361 830 530 999 698 597 303
10. - - - 578 202 746 370 915 539 746 379
12. - 662 211 830 379 896 455
14. - 746 220 1045 531 PE500 8 - - 965 256 1263 554 1561 852 1859 1149 1134 452
10. - - - 1138 251 1435 549 1733 847 1417 565
12. - 1608 544 1701 678
14. - 1984 791 PE750 8 - - 1470 549 1913 992 2356 1434 2799 1877 1529 641
10. - - - 1735 583 2178 1026 2621 1469 1912 801
12. - 2000 618 2443 1060 2294 961
14. - 2265 652 2676 1121 PE1100 8 1454 430 2108 1083 2761 1736 3414 2389 4067 3043 1999 1000

A B

10. - 1830 549 2483 1202 3136 1855 3790 2509 2499 1250
12. - - - 2205 668 2858 1321 3512 1975 2999 1500
14. - 2581 787 3234 1441 3499 1750 PE2500 8 2625 890 4124 2389 5622 3888 7121 5386 8620 6885 4675 2934
10. - 3309 1140 4807 2639 6306 4137 7804 5636 5844 3668

(Counter Clock Wise or Clock Wise) these maximum requirements occur. 2. If in doubt, or you require any assistance with sizing actuators, do not hesitate to contact your nearest Emerson's Valve Automation Division representative. 3. Pressure on port "A" opens the actuator* 4. The actuator is shown in closed position* 5. Do not exceed the maximum supply pressure of 6 bar / 87psi. (*code A, data sheet A1.504)

12. - 2494 -109 3992 1390 5491 2889 6989 4387 7013 4401
14. - - - 3177 141 4676 1640 6174 3138 8182 5135 PE4000 8 4475 1548 7015 4088 9555 6628 12096 9169 14636 11709 7890 4952
10. - 5639 1981 8180 4521 10720 7061 13260 9602 9863 6190
12. - 4264 -127 6804 2414 9344 4954 11885 7494 11835 7429
14. - - - 5428 306 7969 2847 10509 5387 13808 8667
Emerson Process Management P2500 — A B diagram (page 26)
Afb. 27

Copyright © Emerson Process Management. The information in this document is subject to change without notice. Updated data sheets can be obtained from our website www.El-O-Matic.com or from your nearest Valve Automation Center USA: +1 813 319 0266 Europe: +31 74 256 10 10 Asia-Pacific: +65 6501 4600

Spring · C Start · Actuator type

Page 27 of the Emerson Process Management P2500 user manual — Asia Pacific
Pagina 27 · klik om te vergroten
Pagina 27

Contact Us: Emerson Process Management, Valve Automation facilities at your nearest location:

North & South America

Middle East & Africa

Europe

C/ Francisco Gervás, 1 28108 Alcobendas – Madrid Spain T +34 0913 586 000 F +34 0913 589 145

Kawasan Perindustrian Nilai 71807 Nilai, Negeri Sembilan Malaysia T +60 6 799 2323 F +60 6 799 9942

18703 GH Circle PO Box 508 Waller, TX 77484 USA T +1 281 727 5300 F +1 281 727 5353

P. O. Box 17033 Dubai United Arab Emirates T +971 4 811 8100 F +971 4 886 5465

Asveldweg 11 7556 BR Hengelo (O) The Netherlands T +31 74 256 1010 F +31 74 291 0938

Letnikovskaya Str. 10-2 115114 Moscow Russia and FSU T +7 495 981 98 11 F +7 495 981 98 10

471 Mountain Highway Bayswater, Victoria 3153 Australia T +61 3 9721 0200 F +61 3 9720 0588

P. O. Box 105958 Abu Dhabi United Arab Emirates T +971 2 697 2000 F +971 2 555 0364

Siemensring 112 47877 Willich Germany T +49 2154 499 660 F +49 2154 499 6613

2500 Park Avenue West Mansfield, OH 44906 USA T +1 419 529 4311 F +1 419 529 3688

Asia Pacific

301 Solitaire Corporate Park 151 M.V.Road, Andheri (E) Mumbai – 400093 Maharashtra, India T +91 22 6694 2711 F +91 22 2825 3394

P. O. Box 3911 Al Khobar 31952 Saudi Arabia T +966 3 814 7560 F +966 3 814 7570

25, Rue de Villeneuve Silic – BP 40434 94583 RUNGIS Cedex France T +33 1 49 79 73 00 F +33 1 49 79 73 99

No. 9 Gul Road #01-02 Singapore 629361 T +65 6501 4600 F +65 6268 0028

9009 King Palm Drive Tampa, FL 33619 USA T +1 813 630 2255 F +1 813 630 9449

9/F Gateway Building No. 10 Ya Bao Road Chaoyang District Beijing 100020 P.R.China T +86 10 5821 1188 F +86 10 5821 1100

NOF, Shinagawa Konan Bldg 1-2-5, Higashi-shinagwa Shinagwa-ku, Tokyo 140-0002 Japan T +81 3 5769 6873 F +81 3 5769 6902

P. O. Box 10305 Jubail 31961 Saudi Arabia T +966 3 340 8650 F +966 3 340 8790

13840 Pike Road Missouri City, Texas 77489 USA T +1 281 499 1561 F +1 281 499 8445

Via Montello 71/73 20038 Seregno (Milan) Italy T +39 0362 2285 207 F +39 0362 2436 55

P. O. Box 32281 Doha Qatar T +974 4 576777 F +974 4 315448

Av. Hollingsworth, 325, Iporanga Sorocaba, SP 18087-105 Brazil T +55 15 3238 3788 F +55 15 3228 3300

6 Bracken Hill South West Industrial Estate Peterlee SR8 2LS United Kingdom T +44 191 518 0020 F +44 191 518 0032

No.15 Xing Wang Road Wuqing Development Area Tianjin 301700 P.R.China T +86 22 8212 3300 F +86 22 8212 3308 Lot 13111, Mukim Labu

2 Monteer Road, Isando Kempton Park, 1600 South Africa T +27 11 974 3336 F +27 11 974 7005

ul. Konstruktorska str 11A 02-673 Warsaw Poland T +48 22 4589237 F +48 22 45 89 231

© 2010 Emerson Process Management. All rights reserved. The Emerson logo is a trademark and service mark of Emerson Electric Co. “Brand mark listing” are marks of one of the Emerson Process Management family of companies. All other marks are property of their respective owners. The contents of this publication are presented for information purposes only, and while every effort has been made to ensure their accuracy, they are not to be construed as warranties or guarantees, express or implied, regarding the products or services described herein or their use or applicability. All sales are governed by our terms and conditions, which are available on request. We reserve the right to modify or improve the designs or specifications of our products at any time without notice. EL-O-MATIC® is a registered trademark of EL-O-MATIC B.V.

Page 28 of the Emerson Process Management P2500 user manual — English Deutsch Nederlands
Pagina 28 · klik om te vergroten
Pagina 28
Emerson Process Management P2500 — Contact Us diagram (page 28)
Afb. 28 · Contact Us

English Deutsch Nederlands

Page 29 of the Emerson Process Management P2500 user manual — Table of contents
Pagina 29 · klik om te vergroten
Pagina 29

Table of contents

General Datap.2A1.102 Rev. B Technical Details, Standard Actuatorp.2A1.102.10 Rev. C El-O-Matic Basic Pneumatic Actuator Configurationp.3A1.501.01 Rev. A El-O-Matic Actuator with One Way Limit Stopsp.4A1.501.03 Rev. A Limit Stop Plate Dimensionsp.5A1.501.05 Rev. A El-O-Matic Actuator with Double Stroke Adjustmentp.6Dimensionsp.7A1.103.106 Rev. D Standard Actuator - ISOp.7A1.103.102 Rev. A Standard E12 A ctuator - ISOp.8A1.103.200 Rev. B Drive Inserts for El-O-Matic Actuatorsp.9Torquep.10A1.104.01 Rev. B Double Acting Actuator (In.lb.)p.10A1.104.02 Rev. B Spring Return Actuator (In.lb.)p.11Construction, Parts and Materialsp.12A1.101.33 Rev. A E-Serie Actuatorsp.12A1.101.30 Rev. A P-serie actuatorsp.13A1.101.60 Rev. A DSA Actuatorsp.14A1.101.70 Rev. C Low Temperature Actuator Specificationp.15A1.101.71 Rev. B High Temperature Actuator Specificationp.16Spring Setsp.17A4.201 Rev. A Installation of Springs - P-Seriesp.17A4.202 Rev. A Installation of Springs - E-Seriesp.18Assembly Modesp.19A1.503 Rev. A Double Acting Assembly Modesp.19A1.504 Rev. A Spring Return Assembly Modesp.20Corrosion Protection / Paint Specificationp.21A4.204.01 Rev. B Standard Corrosion Protection Systemp.21A4.204.02 Rev. B El-O-Matic CSR Coatingp.22A4.204.021 Rev. A Chemical Resistance CSR Coatingp.23180° Actuatorsp.24A1.203.011 Rev. A Dimensions Standard 180° Actuatorsp.24A1.204.01 Rev. C Torque 180° Double Acting Actuator (In.lb.)p.25A1.204.02 Rev. C Torque 180° Spring Return Actuator (In.lb.)p.26Contact Usp.27
Page 30 of the Emerson Process Management P2500 user manual — Waarschuwing
Pagina 30 · klik om te vergroten
Pagina 30

Warning

The device may only be operated by craftsmen who are familiar with the mounting, the installation and operation of this product.

Craftsmen as mentioned in this installation and operation manual are persons who, on the basis of their crafts education, their knowledge and experience as well their knowledge of the applicable standards can judge the to them commissioned labour and can recognise the possible dangers.

To work on the device in an explosion proof execution, the craftsmen must have an education or instruction respectively the legitimacy to work on explosion proof devices in explosion hazardous areas.

The electrical security will be determined by power supply, because in the device only low voltageis applied. The electrical installation has to comply with the applicable standards. Additionally for the installation of explosion hazardous devices the notifications of the certificate of conformity and the regulations for to establish explosion hazardous installations have to be observed.

WARNUNG

Das Gerät darf nur von Fachpersonal, das mit der Montage, der Inbetriebnahme und dem Betrieb dieses Produktes vertraut ist, montiert und in Betrieb genommen werden.

Fachpersonal im Sinne dieser Einbau- und Bedienungsanleitung sind Personen, die auf Grund ihrer fachlichen Ausbildung, ihrer Kenntnisse und Erfahrungen sowie ihrer Kenntnisse der einschlägigen Normen die ihnen übertragenen Arbeiten beurteilen und mögliche Gefahren erkennen können.

Bei Geräten in explosionsgeschützter Ausführung müssen die Personen eine Ausbildung oder Unterweisung bzw. eine Berechtigung zum Arbeiten an explosions- geschützten Geräten in explosionsgefährdeten Anlagen haben.

Gefährdungen, die am Stellventil vom Durchflußmedium, dem Stelldruck und von beweglichen Teilen ausgehen können, sind durch geeignete Maßnahmen zu verhin- dern. Sachgemäßer Transport und fachgerechte Lagerung des Gerätes werden vorausgesetzt.

Die elektrische Sicherheit wird allein durch die speisenden Geräte bestimmt, da im Gerät nur Kleinspannungen zur Anwendung kommen. Bei der elektrischen Installation sind die geltenden Vorschriften zu beachten. Zusätzlich sind bei der Installation von explosionsgefährdeten Geräten die Angaben der Konformitätsbescheinigung und die Vorschriften für die Errichtung explosionsgefährdeter Anlagen zu beachten.

Waarschuwing

Dit apparaat mag alleen door vakpersoneel, welke met de montage, het in bedrijf stellen en het in bedrijf zijn, bekent zijn, gemonteerd en in bedrijf geno- men worden.

Vakpersoneel zoals in deze montage handleiding bedoelt, zijn personen, die op grond van hun vaktechnische opleiding, hun kennis en ervaring als ook hun kennis van de desbetreffende normen de hun opgedragen arbeid kunnen beoordelen en de mogelijke gevaren kunnen herkennen.

Bij apparaten in explosieveilige uitvoeringen moeten die personen een opleiding of onderricht in resp. een bevoegdheid voor het werken met explosie- veilige apparaten in omgevingen met dreigend explosie gevaar, hebben.

De elektrische zekerheid wordt alleen bepaald door de voedende apparaten, omdat in het apparaat alleen laagspanning gebruikt worden. Bij de elektri- sche installatie moeten alle geldende voorschriften in acht genomen worden. Aanvullend moeten bij de installatie van apparaten met dreigend explosie gevaar de aanwijzing van de konformiteitsgetuigschrift en de voorschriften voor het vestigen van een installatie met dreigend explosie gevaar in acht ge- nomen worden.

Page 31 of the Emerson Process Management P2500 user manual — ELECTRO-PNEUMATIC POSITIONER
Pagina 31 · klik om te vergroten
Pagina 31

1.0 Introduction / Einführung / Introductie

1.1 Product Description F20

El-o-matic POSIFLEX positioners belong to the most advanced positioners of their type on the market today. This latest version is made possible by a combination of the newest electronics developments with a high precision spool type pneumatic pilot for the volume amplifier.

F20

The F20 is a true 2 wire instrument: An industry standard 4 to 20 mA. signal provides both the controlling signal and the power supply for the electronics. As such the positioner is plug compatible with the current industry standard. The use of electronics as the controlling element means that all the usual control characteristics: Zero, range and sensitivity are all electronically resettable using trimmers on the control card.

ELECTRO-PNEUMATIC POSITIONER

Both rotary and linear applications are catered for, the differ- ence being with feedback mechanism and the mounting methods. A single universal positioner is suitable for both double acting and single acting (spring return) actuators. The standard internal feedback provides a linear relationship between the input signal and the output movement.

The functionallity of the F20 positioner can be extended by a "Plug-in" PTF20 Option for a analog 4-20mA feedback signal. This option is, well protected, mounted inside the F20 enclo- sure and has its own feedback potentiometer.

Show 5 more labels / short text on this page
Rotary · Closed · Open Open · Closed · Linear
Page 33 of the Emerson Process Management P2500 user manual — 1.0 Introduction / Einführung / Introductie
Pagina 33 · klik om te vergroten
Pagina 33

1.0 Introduction / Einführung / Introductie

1.2 Operating Principles

The positioner provides the means for a pneumatic actuator to be accurately positioned to any point between full open and full closed position. The actuator’s movement is controlled in proportion to a 4-20 mA incoming signal.

The actuator’s movement is monitored by the integral feedback potentiometer (7), the signal from this and the incoming signal are fed to the comparative electronics on the main circuit board (1).

Providing these two signals are equal the resulting signal sent to the I/P converter (2) is “Neutral” and the spool of the pilot valve (3) is held in the mid or blocked position. In this state the actuator remains locked in the last set position, that is at it’s “Set point”.

If, either the input mA. signal or the valve position changes then the difference is sensed and the signal to the I/P is either increased or decreased. This causes a corresponding move- ment of the pilot spool (3) which in turn starts the actuator’s movement (4) towards the new “Set point”. On reaching this the two signals are again equal and movement stops at this new “Set point”.

For single acting (spring return) actuators only a single air line is used, the other port at the spool valve (3) is plugged off.

4-20 mA Signal input = 4-20 mA Eingangssignal = 4-20 mA Stuursignaal

4-20 mA Signal input

Page 34 of the Emerson Process Management P2500 user manual — 1.0 Introduction / Einführung / Introductie
Pagina 34 · klik om te vergroten
Pagina 34

1.0 Introduction / Einführung / Introductie

1.2 Arbeitsweise

1.2 Werkingsprincipes

Der Stellungsregler bietet die Möglichkeit, ein pneumatisches Stell- glied in jeder beliebigen Stellung zwischen völlig auf und völlig ge- schlossen zu positionieren. Die Bewegung des Stellgliedes wird pro- portional zu einem Eingangssignal von 4-20 mA geregelt.

Door de montage van klepstandsteller F20 kan een pneumati- sche aandrijving nauwkeurig in elke stand tussen volledig geo- pend en volledig gesloten worden gezet. De beweging van de aandrijving wordt evenredig aan een 4-20 mA ingangssignaal geregeld.

Die Stellbewegung des Antriebes wird von einem Rückführ- potentiometer (7) erfaßt und in der Elektronikbaugruppe (1) mit dem Eingangssignal verglichen.

De beweging van de aandrijving wordt bewaakt door de inte- grale terugkoppelpotentiometer (7). Het door deze potentiometer afgegeven signaal en het ingangssignaal worden aan de vergelijkingselektronica op de hoofdprintplaat (1) toe- gevoerd.

Liegt Soll-Istwert Gleichheit vor, verbleibt der Stellantrieb in der je- weiligen Position.

Ändert sich das Stellsignal oder die Antriebsposition, wird die Ab- weichung erfaßt. Die Soll-Istwert Differenz wird elektronisch ver- stärkt und ändert das Magnetfeld der Festspule (2). Damit ändert sich der Abstand zwischen Düse und Prallplatte. Die Kaskaden- druckänderung verstellt das Verstärker-Ventil (3) am Ausgang. Der Antrieb (4) bewegt sich in Richtung neuer Sollwert und stoppt bei Erreichen der neuen Sollposition.

Alleen wanneer deze twee signalen gelijk zijn, zal het aan de I/ P-omzetter (2) afgegeven resulterende signaal “neutraal” zijn, waarbij de plunjer van de stuurklep (3) in de centrale of geblok- keerde stand wordt gehouden. In deze stand blijft de aandrijving in de laatst ingestelde positie, te weten het instelpunt, vergrendeld.

Indien het mA-ingangssignaal of de klepstand verandert, wordt het verschil gedetecteerd, waardoor het signaal naar de I/P verhoogd dan wel verlaagd wordt. Dit resulteert in een corres- ponderende beweging van de stuurklepplunjer (3) die wederom de beweging van de aandrijving (4) naar het nieuwe instelpunt in gang zet. Zodra dit punt is bereikt, zijn de beide signalen weer gelijk en komt de beweging bij dit nieuwe instelpunt tot stilstand.

Bei einfachwirkenden Antrieben wird nur der eine Ausgang genutzt. Der andere Ausgang wird verschlossen.

Bij enkelwerkende (veerbelaste) aandrijvingen wordt slechts een enkele luchtleiding gebruikt; de andere poort bij de plunjerklep (3) wordt afgestopt.

Page 35 of the Emerson Process Management P2500 user manual — Contact Us
Pagina 35 · klik om te vergroten
Pagina 35

2.0 Installation - Rotary Actuators / Einbau Drehantriebe / Montage op roterende aandrijvingen

2.1 Mechanical Installation - Rotary Actuators The positioner is mounted on to the top surface of the pneu- matic actuator using an appropriate mounting kit.

The positioner’s mounting configuration is to the VDE/VDI 3845 standard, if the actuator is to the same standard, a standard NAMUR mounting kit can be used, otherwise a special mounting kit will have to be obtained.

Assuming the installation will use the standard NAMUR mounting kit, proceed as follows: 1. Fix the bracket to the top surface of the actuator using the 4 screws provided. 2. Locate the positioner in place on top of the bracket, making sure that the 4 mm. tongue locates properly into it’s slot in the actuator spindle. 3. Fix the positioner to the bracket using the 4 screws pro- vided.

Page 37 of the Emerson Process Management P2500 user manual — A
Pagina 37 · klik om te vergroten
Pagina 37

2.0 Installation - Rotary Actuators / Einbau Drehantriebe / Montage op roterende aandrijvingen

2.2 Pneumatic Connections Assuming a standard (direct acting) installation with an increasing signal to open the valve in a CCW (counter clock- wise) direction.

Before connecting any air supply make sure that the air available is clean dry instrument air filtered to at least 25 microns.

2.2.1 Double acting 1. Connect an appropriate piece of air tubing between the port 1. on the positioner to the “A” port on the actuator. (The “A” port is the one that when air is applied to it, rotates the actuator in a counter clockwise direction). 2. Connect an appropriate piece of air tubing between the port 2. on the positioner to the “B” port on the actuator. (The “B” port is the one that when air is applied to it, rotates the actuator in a clockwise direction). 3. If the positioner is required to meet enclosure rating IP54, be sure that the sintered filter is in place at the “Exhaust” port. 4. Connect an air supply to the positioner port marked “Supply”.

A B

Double acting

2.2.2 Single acting 1. Connect an appropriate piece of air tubing between the port 1. on the positioner to the “A” port on the actuator. (The “A” port is the one that, when air is applied to it, rotates the actuator in a counter clockwise direction). 2. Connect an air supply to the positioner port marked “Supply”. 3. If the positioner is required to meet enclosure rating IP54, be sure that the sintered filter is in place at the “Exhaust” port.

A

Single acting

Double acting Supply Exhaust

= Doppelt Wirkend = Luftversorgung = Entlüftung

= Dubbel werkend = Luchtaansluiting = Ontluchting

Show 4 more labels / short text on this page
Supply · Exhaust 1 2 · Supply · Exhaust
Page 39 of the Emerson Process Management P2500 user manual — A 6
Pagina 39 · klik om te vergroten
Pagina 39

3.0 Installation - Linear Actuators / Einbau - Hubantriebe / Montage - lineaire aandrijvingen

3.1 Mechanical Installation - Linear Ac- tuators The mounting set is used for mounting POSIFLEX positioners on linear actuator which have mountings in accordance with DIN IEC 534-6. All parts are made from stainless steel. The mounting sets contain two different levers for different stroke ranges: 1. Stroke 10 - 65 mm 2. Stroke 65 - 100 mm

A 6

Mounting is possible for actuators with pillars, by using the bracket (7) with the U-bolt (8). Or for actuators with a cast pad, by direct fitting using the screw M8x20 (16) with washer M8 (17). The linear moving of actuator has to be converted into a rotation of the shaft of positioner. The distance ”A” between coupling bolt (6) and shaft of positioner is set with reference to the table below. This distance is a function of stroke S. Pre- setting the linkage with this distance ”A” enables the best range setting to be achieved with only a small adjustment on the positioners’ range setting. A spring (3); (5) in lever (2); (4) eliminates play in the linkage.

S (in mm.) A (in mm.) ∝= 24,5° ∝= 40° ∝= 49° 10 23 (k) 16 22 (k) 20 27 (k) 30 41 (k) 32 44 (k) 50 68 (k) 55 75 (k) 65 89 (k), (l) 75 103 (l) 80 110 (l) 100 110 (l)

3.1.1 Installation sequence The following installation sequence is for a positioner with a direct action (increasing signal opens the valve with rising spindle.) 1. Insert lever (2); (4) at end of positioner shaft and fix it with screw. 2. Check the standard interface of actuator and mount bracket (7) at left side of actuator - at pillar or casting pad. 3. Choose the position of bracket (7) where lever (2); (4) is in a horizontal position and the actuator is in mid stroke. 4. Position the coupling bolt (6) for a correct distance ”A”, with

3.2 l = long lever (4) k = short lever (2)

l = lange hefboom (4) k = korte hefboom (2)

l = langer Hebel (4) k = kurzer Hebel (2)

No. Qty Description Ums chreibung Omschrijving N orm 1 1 Carrier bracket Mitnehmerblech Meeneembeugel 2 1 Lever, short Hebel-kurz Hefboom kort 3 1 Spring, short Feder-kurz Veer kort 4 1 Lever, long Hebel-lang Hefboom lang 5 1 Spring, long Feder-lang Hefboom kort 6 1 Coupling bolt Mitnehmer Meeneembout 7 1 Bracket for postioner Montagewinkel Montagebeugel 8 2 U-bolt Spannbügel Spanbeugel 9 4 Nut M8 Mutter M8 Moer M8 DIN 934 10 1 Nut M6 Mutter M6 Moer M6 DIN 439 11 4 Lockwasher B8 Federring B8 Ring B8 DIN 127 12 3 Lockwasher B6 Federring B6 Ring B6 DIN 127 13 1 Disk A6,4 Scheibe A6,4 Schijf A6,4 DIN9021 14 3 Screw M6x10 Schraube M6x10 Schroef M6x10 DIN 933 15 1 Screw M3x10 Schraube M3x10 Schroef M3x10 DIN 912 16 1 Screw M8x20 Schraube M8x20 Schroef M8x20 DIN 933 17 1 Lockwasher B8 Federring B8 Ring B8 DIN 917 18 2 Screw M6x12 Schraube M6x12 Schroef M6x12 DIN 933

reference to the table 3.2. 5. Fix coupling bolt with nut M6 (10). 6. Adjust positioner (zero, range, amplification). 7. Change setting of zero and range as required.

Note: 1. POSIFLEX positioners for linear applications are adjusted for an angle of 40° as standard (see table above). For different strokes i.e. 10mm or 100 mm (other angle!) reset zero and range adjustment of F20. 2. Several parts, standard parts e.g., of mounting kit are already pre-assembled for ease of assembly. 3. Using only one lever is possible in applications of F20 if the relation of stroke and distance ”A” is not more than 1,0. To use this type of assembly, please also order coupling bolt ES (Part number 6.003618).

Show 5 more labels / short text on this page
9;11 · 12;14 · 10;13 · 12;18 · 2;3 / 4;5
Page 40 of the Emerson Process Management P2500 user manual — 3.1 Mechanischer Einbau - Hubantriebe
Pagina 40 · klik om te vergroten
Pagina 40

3.0 Installation - Linear Actuators / Einbau - Hubantriebe / Montage - lineaire aandrijvingen

3.1 Mechanischer Einbau - Hubantriebe

3.1 Montage - lineaire aandrijvingen

Zum Anbau ist der Montagewinkel (7) mit den Spannbügeln (8) für Antriebe mit Säulenjoch oder Schraube M8x20 (16) mit Unterleg- scheibe M8 (17) für Antriebe mit Gußjoch vorgesehen. Die Montagesätze haben zwei verschiedene Hebel für verschiedene Hubbereiche; 1. Hub 10 - 65 mm 2. Hub 65 - 100 mm

Voor aandrijvingen met een zuilenjuk worden een Montage- beugel (7) en een Spanbeugel (8) meegeleverd. Voor aandrij- vingen met gietwerkjuk worden schroef M8x20 (16) met sluit- ring M8 (17) meegeleverd. De montageset hebben twee ver- schillende hefbomen voor verschillende slagbereiken; 1. Slag 10 - 65 mm 2. Slag 65 - 100 mm

Zur funktionellen Kopplung muß die Linearbewegung des Antriebs in eine Drehbewegung der Welle des Stellungsreglers gewandelt werden. Hierzu dient das an der standardisierten Schnittstelle der Antriebsspindel montierte Mitnehmerblech (1), das über den Mit- nehmer (6) den Hebel (2); (4) dreht. Um mit optimalen Übertragungsbedingungen und nur geringfügigen Korrekturen der Stellungsregler-Kalibrierung arbeiten zu können, ist der Abstand "A" des Mitnehmers von der Stellungsregler-Welle in Abhängigkeit vom Antriebshub gemäß Tabelle (siehe unten) einzustellen. Zur Ver- meidung von Übertragungsspiel ist im Hebel (2); (4) die Feder (3); (5) eingelegt.

De lineaire beweging van de regelklep moet omgezet worden in een draaibeweging van de as van de klepstandsteller. Hier- voor dient het aan de gestandardiseerde interface van de aandrijvingsspindel gemonteerde meeneembeugel (1), welke via de meeneembout (6) hefboom (2;4) verdraait. Afstand "A" dient volgens onderstaande abel ingesteld te worden. Dit zorgt voor een optimale bereiksinstelling welke naderhand dan nog gering bijgesteld dient te worden. De veer (3:5) zorgt voor een spellingsvrije overbrenging

3.1.1 Montageablauf Nachstehend folgt ein typisches Montagebeispiel für eine direkt wir- kende Einheit (ansteigendes Signal öffnet ein Ventil mit steigender Spindel). 1. Hebel (2); (4) auf Zweiflach am Wellenende des Stellungsreglers aufstecken und anschrauben. 2. Montagewinkel (7) an linke Seite des Antriebsjochs (bei Sicht auf Schnittstelle an Spindel) montieren 3. Im Säulenjoch den Montagewinkel in der Höhe so einstellen, daß Hebel bei Hubmitte horizontal steht 4. Mitnehmer-Abstand A in Abhängigkeit vom Hub aus der Tabelle entnehmen. 5. Mitnehmer auf Maß A einstellen und mit Mutter M6 (10) fest ar- retieren. 6. Inbetriebnahme des Stellungsreglers 7. Bei Bedarf Nullpunkt und Bereichseinstellung korrigieren

3.1.1 Montagevolgorde Hieronder volgd een typische montagevolgorde voor een direct werkende samenstelling (Bij stijgend signaal opend de afsluiter met steigende spindel). 1. Hefboom (2);(4) op asuiteinde van de klepstandsteller mon- teren 2. Montagebeugel (7) aan de linker kant van het aandrijvings- juk (met zicht op de inteface aan de spindel) monteren. 3. De montagebeugel zodanig in de hoogte verschuiven, dat hefboom horizontaal staat. De aandrijving moet hierbij in de midden positie staan. 4. Afstand “A” volgens onderstaande tabel instellen. 5. Meeneembout vastzetten met moer M6 (10). 6. Afstellen klepstandsteller - Zie “Montage en bediening”. 7. Eventueel nulpunt, bereik en gevoeligheid corrigeren.

Opmerking 1. POSIFLEX-klepstandsteller voor lineaire aandrijvingen zijn standaard ingesteld voor een hoekverdraaiing van α=40° (zie tabel). Bij grotere of kleinere hoekverdraaiingen (bij een slag van 10mm resp. 100mm) moet bij de elektro-pneumati- sche klepstandsteller F20 de instelling voor nulpunt en be- reik veranderd worden. 2. Voorgemonteerde montagesets zijn beschikbaar voor de verschillende slagbereiken. 3. Een Eenstiftbediening van de hefboom (zonder meeneem- beugel 1) is voor de klepstandsteller F20 mogelijk, wanneer de verhouding van slag en maat “A” maximaal 1,0 is. Hier- voor is als optie meenemer ES Eénstiftbediening voor F20 (Typ-Nr. 6.003618) te bestellen.

Hinweise 1. Die POSIFLEX-Geräte für Hubantriebe sind auf den Schwenk- winkel α=40° (siehe Tabelle) standardmäßig justiert. Für die An- passung auf den kleineren oder größeren Schwenkwinkel für Hub 10mm bzw. 100mm ist bei dem elektropneumatischen Stel- lungsregler F20 die Einstellung für Nullpunkt und Bereich zu än- dern. 2. Zur Erleichterung der Handhabung sind einzelne Baugruppen mit Normteilen vorkomplettiert. 3. Eine Einstiftbetätigung des Schwenkhebels (ohne Mitnehmer- blech 1) ist für den Stellungsregler F20 möglich, wenn das Ver- hältnis von Hub und Maß A maximal 1,0 ist. Hierfür als Option Mitnehmer ES (Typ-Nr. 6.003618) bestellen.

Page 41 of the Emerson Process Management P2500 user manual — Single acting
Pagina 41 · klik om te vergroten
Pagina 41

3.0 Installation - Linear Actuators / Einbau - Hubantriebe / Montage - lineaire aandrijvingen

3.2 Pneumatic Connections Assuming a standard installation, with direct acting an increas- ing signal to open the valve (rising spindle).

Before connecting any air supply make sure that the air available is clean dry instrument air filtered to at least 25 microns.

3.2.1 Double acting 1. Connect an appropriate piece of air tubing between the port 1. on the positioner to the “A” port on the actuator. (The “A” port is the one that, when air is applied to it, opens the valve). 2. Connect an appropriate piece of air tubing between the port 2. on the positioner to the “B” port on the actuator. (The “B” port is the one that when air is applied to it, closes the valve). 3. If the positioner is required to meet enclosure rating IP54, be sure that the sintered filter is in place at the “Exhaust” port. 4. Connect an air supply to the positioner port marked “Supply”.

3.4 Double acting

3.2.2 Single acting 1. Connect an appropriate piece of air tubing between the port 1. on the positioner to the “A” port on the actuator. (The “A” port is the one that when air is applied to it, opens the valve). 2. If the positioner is required to meet enclosure rating IP54, be sure that the sintered filter is in place at the “Exhaust” port. 3. Connect an air supply to the positioner port marked “Supply”.

Single acting

Page 42 of the Emerson Process Management P2500 user manual — Contact Us
Pagina 42 · klik om te vergroten
Pagina 42

3.0 Installation - Linear Actuators / Einbau - Hubantriebe / Montage - lineaire aandrijvingen

3.2 Pneumatikanschlüsse Es wird ausgegangen von einer direkt wirkenden Standardaus- führung mit ansteigendem Signal zum Öffnen eines Ventils (mit stei- gender Spindel).

3.2 Pneumatische aansluitingen Hierbij wordt uitgegaan van een standaard montage (voor di- recte werking), waarbij een in intensiteit toenemend signaal de afsluiter moet openen (omhoogkomende klepstang).

Bevor die Luftversorgung angeschlossen wird, ist sicherzustellen, daß die verfügbare Luft reine trockene Instrumentenluft ist, die mit einer Feinheit von mindestens 25 Mikrometer gefiltert ist.

Alvorens lucht aan te sluiten, dient u te controleren of hier sprake is van schone, droge instrumentenlucht die mini- maal tot op 25 micron is gefilterd.

3.2.1 Doppeltwirkende Ausführung 1. Einen geeigneten Luftschlauch zwischen Anschluß 1 am Stellungsregler und Anschluß "A" am Stellglied anbringen. (An- schluß "A" ist der Anschluß, der bei Beaufschlagung mit Luft das Ventil öffnet). 2. Einen geeigneten Luftschlauch zwischen Anschluß 2 am Stellungsregler und Anschluß "B" am Stellglied anbringen. (An- schluß "B" ist der Anschluß, der bei Beaufschlagung mit Luft das Ventil schließt). 3. Die Luftversorgung an den Anschluß "SUPPLY" (Zuluft) des Stellungsreglers anschließen. 4. An den Anschluß "Exhaust" (Entlüftung) sind Elemente anzu- schließen, die IP54 gewährleisten (z.B. mitgelieferter Schall- dämpfer).

3.2.1 Dubbelwerkende uitvoering 1. Breng een passend stuk luchtleiding tussen poort 1 op de klepstandsteller en poort “A” op de aandrijving aan. (Met poort “A” wordt die poort bedoeld welke de klep opent wan- neer lucht op deze poort wordt gezet.) 2. Breng een passend stuk luchtleiding tussen poort 2 op de klepstandsteller en poort “B” op de aandrijving aan. (Met poort “B” wordt die poort bedoeld welke de klep afsluit wan- neer lucht op deze poort wordt gezet.) 3. Sluit lucht aan op de met “Supply” aangeduide poort van de klepstandsteller. 4. Indien de klepstandsteller aan beschermingsklasse IP54 moet voldoen, dient b.v. de meegeleverde geluidsdemper in de met “Exhaust” aangeduide poort te zijn aangebracht.

Bemerkung: Für einen doppeltwirkenden Antrieb mit Wirkung in umgekehr- ter Richtung ist dem selben Verfahren zu folgen, mit dem Unter- schied, daß die Einstellung "Umgekehrte Wirkungsrichtung" zu wählen ist. Siehe Seite 21. Elektrische Anschlüsse, siehe Seite 17.

3.2.2 Einfachwirkende Ausführung 1. Einen geeigneten Luftschlauch zwischen Anschluß 1 am Stellungsregler und Anschluß "A" am Stellglied anbringen. (An- schluß "A" ist der Anschluß, der bei Beaufschlagung mit Luft das Ventil öffnet). 2. Die Luftversorgung an den Anschluß "SUPPLY" (Zuluft) des Stellungsreglers anschließen. 3. An den Anschluß "Exhaust" (Entlüftung) sind Elemente anzu- schließen, die IP54 gewährleisten (z.B. mitgelieferter Schall- dämpfer).

3.2.2 Enkelwerkende uitvoering 1. Breng een passend stuk luchtleiding tussen poort 1 op de klepstandsteller en poort “A” op de aandrijving aan. (Met poort “A” wordt die poort bedoeld welke de afsluiter opent wanneer lucht op deze poort wordt gezet.) 2. Sluit lucht aan op de met “Supply” aangeduide poort van de klepstandsteller. 3. Indien de klepstandsteller aan beschermingsklasse IP54 moet voldoen, dient b.v. de meegeleverde geluidsdemper in de met “Exhaust” aangeduide poort te zijn aangebracht.

Bemerkung: Für einen einfachwirkenden Antrieb mit Wirkung in umgekehr- ter Richtung ist dem selben Verfahren zu folgen, mit dem Unter- schied, daß die Einstellung "Umgekehrte Wirkungsrichtung" zu wählen ist. Siehe Seite 23. Elektrische Anschlüsse, siehe Seite 17.

Page 43 of the Emerson Process Management P2500 user manual — Contact Us
Pagina 43 · klik om te vergroten
Pagina 43

4.0 Electrical Connections and settings / Elektrische Anschlüsse und Einstellungen / Elektrische aansluitingen en instellingen

4.1 Electrical Connections Connect the 4 - 20 mA signal to the terminals (4) and (5), making sure that the + and - are the correct way round. The voltage is ~8 VDC.

4.2 Initial Setup - Zero, Range and Sensi- tivity The factory settings provide the positioner with an initial range of settings that will allow the operation of positioners on most applications.

Signal Input - 4 mA. - 20 mA. Range - 0% to 100% Control Function - Linear. Action - Direct Acting.

(CCW with increasing Signal).

Three settings are provided on the main circuit board. These allow adjustments of the zero, range and dead band (sensitiv- ity). Before making adjustments the positioner should be already mounted on the valve/actuator, air supply connected, and a 4 - 20 mA.(¯8V.) signal connected to the signal input terminals.

- 4-20 mA (~8 VDC Input signal) +

Damp Zero Span Input signal Positioner coil Feedback potentiometer

= Empfindlichkeit = Nullpunkt = Bereich = Eingangssignal = Festspule = Rückmelde-

= Gevoeligheid = Nulpunt = Bereik = Ingangssignaal = Standsteller Spoel = Terugmeld

4.3 Zero Setting The zero resetting trimmer on the circuit board is marked “Zero”. To change the position for the 4 mA signal, first set the signal to 4 mA, then turn the trimmer screw until the desired position is reached.

4.4 Range Setting The positioner range is limited by the stroke position at the 20 mA. signal point. The range resetting trimmer on the circuit board is marked “Span”. To change range, first set the signal to 20 mA, then turn the trimmer screw until the desired position is reached.

4.5 Sensitivity Setting A setting that is too high will cause the positioner to “hunt” with difficulty in establishing a settled output. A setting that is too low causes an output that is sluggish and lacking in response. The sensitivity resetting trimmer on the circuit board is marked “Damp”. To change sensitivity, first set the signal to an approxi- mate mid point between 4 and 20 mA, then turn the trimmer screw until the best result is reached.

Show 7 more labels / short text on this page
Positioner coil · Feeback potentiometer · Span · Zero · Damp · potentiometer · potentiometer
Page 44 of the Emerson Process Management P2500 user manual — Contact Us
Pagina 44 · klik om te vergroten
Pagina 44

4.0 Electrical Connections and settings / Elektrische Anschlüsse und Einstellungen / Elektrische aansluitingen en instellingen

4.1 Elektrische Anschlüsse Anschließen des 4-20 mA Eingangssignales mit den Anschlüssen (4) und (5). Es ist sicherzustellen, daß das + Signal richtig angeschlos- sen ist. Die Spannung ist ~8 VDC

4.1 Elektrische aansluitingen Sluit het 4-20 mA signaal aan op de klemmen (4) en (5). Let erop dat de + en - op de juiste wijze worden aangesloten. Het voltage is ~8VDC

4.2 Anfangseinstellungen - Null, Bereich und Totzone Die Fabrikseinstellungen verschaffen dem Stellungsregler eine Rei- he von Anfangseinstellungen, die den Betrieb von Stellungsreglern für die meisten Anwendungen ermöglichen.

4.2 Initiële instelling - nulpunt, bereik en gevoeligheid De klepstandstellers worden fabrieksmatig zodanig afgesteld, dat zij voor de meeste toepassingen geschikt zijn.

Signaalingang - 4 - 20 mA Bereik - 0% tot 100% Regelfunctie - lineair Gevoeligheid - 0,1% Werking - direct werkend (Tegen de klok in ope-

Signaleingang - 4 mA - 20 mA Bereich - 0% bis 100% Steuerfunktion - linear Empfindlichkeit - 0,1% Wirkung - Direkt wirkend (EDUL, mit ansteigendem

nend bij een in intensiteit toenemend signaal.)

Die Hauptplatine hat drei Einstellungsmöglichkeiten. Sie ermögli- chen das Justieren vom Nullpunkt, Bereich und Empfindlichkeit. Vor dem Justieren soll der Stellungsregler bereits am Ventil/Stellantrieb montiert, die Luftversorgung angeschlossen und ein Signal von 4-20 mA (~8V) an den Eingangssignalklemmen angeschlossen sein.

De printplaat heeft drie instelmogelijkheden om het nulpunt, het bereik en de gevoeligheid in te stellen. Voordat er gewijzigd wordt, dient de klep-standsteller op de klep/aandrijving gemon- teerd, lucht toegevoerd en een 4-20 mA (~8 V) signaal op de signaalingangsklemmen aangesloten te worden.

4.3 Nullpunkteinstellung Der Nullpunkt wird mit dem Einstellregler ,"zero" eingestellt. Das Eingangssignal in den Stellungsregler wird auf 4mA abgesenkt. Durch Verändern des Einstellreglers ,zero" wird der Punkt einge- stellt, an dem der Antrieb gerade seine Bewegung beginnt.

4.3 Nulpunt instellen Het nulpunt wordt met de trimmer “zero” ingesteld. Om de stand voor het 4 mA signaal te veranderen, dient het signaal eerst op 4 mA te worden ingesteld. Draai nu de trimmer totdat de gewenste stand is bereikt.

4.4 Bereicheinstellung Die Bereichseinstellung wird mit dem Einstellregler ,"span" vorge- nommen. Das Eingangssignal in den Stellungsregler wird auf 20mA erhöht. Durch Verändern des Einstellreglers ,span" wird der Punkt eingestellt, an dem der Antrieb gerade seine Bewegung beginnt.

4.4 Instellen van het bereik Het bereik van de klepstandsteller wordt beperkt door de slag die bij het 20 mA signaalpunt wordt gemaakt. Het bereik wordt met de trimmer “span” ingesteld. Voor het veranderen van het bereik dient het signaal eerst op 20 mA te worden ingesteld. Draai nu de trimmer totdat de gewenste stand is bereikt.

4.5 Einstellung der Empfindlichkeit Die Empfindlichkeit wird mit dem Einstellregler ,"damp" eingestellt. Eine zu hohe Empfindlichkeit kann zum Schwingen des Antriebes führen. Eine zu kleine Einstellung bewirkt ein sehr langsames Rea- gieren des Antriebes und eine zu große Totzone. Die Empfindlichkeit kann man optimal einstellen, wenn man den Stellungsregler mit ca. 12mA betreibt. Durch Drehen des Reglers ,damp" wird der Punkt eingestellt, an dem der Antrieb gerade nicht mehr schwingt. Bei großen Antrieben kann man die volle Empfind- lichkeit nutzen.

4.5 Instellen van de gevoeligheid Bij een te hoge instelwaarde zal de klepstandsteller zich onrus- tig gedragen, waardoor het moeilijk wordt een vaste uitgaande beweging te krijgen. Een te lage instelwaarde resulteert in een trage uitgaande beweging. Om de gevoeligheid te wijzigen, dient het signaal eerst te wor- den ingesteld op 12 mA. Draai nu de trimmer "damp" totdat de gewenste stand is bereikt. Bij grote aandrijvingen kan men de volledige gevoeligheid benutten.

Vermerke: Zum Anstieg die Abgleichschrauben mit dem Uhrzeigerlauf (MUL), und zur Senkung entgegen dem Uhrzeigerlauf (EDUL) drehen.

Signal)

Page 45 of the Emerson Process Management P2500 user manual — Contact Us
Pagina 45 · klik om te vergroten
Pagina 45

4.0 Electrical Connections and settings / Elektrische Anschlüsse und Eeinstellungen / Elektrische aansluitingen en instellingen

4.6 Split range setting To change the range from full range to split range remove the split range jumper. This way the positioner can be controlled either by a 4 to 12mA signal or a 12 to 20mA signal.

The start point can be set at 4 or 12mA with the "ZERO"- trimmer. The end point (range) can be set at 12 or 20mA with the "SPAN"-trimmer.

Standard setting = Standard Einstellung = Standaard instelling

4mA 0mA 0% 100%

4mA 0mA 0% 100% Split range setting Setting of second positioner

Split range setting = Einstellung für geteilten Eingangsbereich = Instellen voor gesplitst bereik

Setting of second positioner = Einstellung für den zweiten Stellungsregler = Instelling voor tweede klepstandsteller

Split range jumper = Jumper für geteilten Eingangsbereich = Jumper voor gedeeld bereik

Show 9 more labels / short text on this page
20mA · 4mA 0mA · 0% 100% · Standard setting · 20mA · 20mA · 12mA · 12mA · Split range jumper
Page 46 of the Emerson Process Management P2500 user manual — Contact Us
Pagina 46 · klik om te vergroten
Pagina 46

4.0 Electrical Connections and settings / Elektrische Anschlüsse und Eeinstellungen / Elektrische aansluitingen en instellingen

4.6 Einstellung für geteilten Eingangsbereich / Split range Durch Ziehen des einzelnen roten Jumpers auf der Leiterplatte kann der Eingangssignalbereich halbiert werden. Damit kann man den Stellungsregler entweder mit einem Eingangssignal von 4 bis 12mA oder 12 bis 20mA betreiben.

4.6 Instellen voor gesplitst bereik Door het verwijderen van de rode jumper op de printplaat kan het ingangssignaalbereik gehalveerd worden. Zo kan men de klepstandsteller of met een ingangssignaal van 4 tot 12 mA of 12 tot 20 mA besturen.

Met de trimmers “zero” en “span” kan dan het beginpunt (4 of 12 mA) en het eindpunt (12 of 20 mA ) ingesteld worden.

Mit dem Einstellregler "ZERO" wird der jeweilige Startpunkt (4 oder 12mA) und mit "SPAN" das Bereichsende (12 oder 20mA) wie oben beschrieben eingestellt.

Bemerkungen 1 Alle Einstellvorgänge beeinflussen sich. Deshalb muß ca. 2 bis 3 mal iterativ der Nullpunkt und der Bereich eingestellt wer- den, um die maximale Genauigkeit zu erreichen. 2 Zum Anstieg die Abgleichschrauben mit dem Uhrzeigerlauf (MUL), und zur Senkung entgegen dem Uhrzeigerlauf (EDUL) drehen.

Page 47 of the Emerson Process Management P2500 user manual — B
Pagina 47 · klik om te vergroten
Pagina 47

5.0 Failure Modes / Ausfallarten / Storingen

5.1 Failure Modes - Double acting

The standard setup for double acting actuators is so that an increasing input signal opens the valve. Signal failure, then, moves the valve to the closed position . This may be changed to “Open on signal failure” by changing the setup to REVERSE ACTING.

B

A

A

B

The effect of signal and air failure depends on the way the air connections and the potentiometer connections are made:

1. Direct acting - Standard Setup

Action Air failure Signal failure Direct Position not defined Closed

2. Reverse acting

Action Air failure Signal failure Reverse Position not defined Open

B

A

A

5.1.1 Changes for Reverse Acting

B

To change from the standard setup to reverse acting:

1. Change the tubing (see fig. 5.1). 2. Remove the cover. 3. Change the action jumper setting by setting both jumpers to the right side (see fig. 5.2). 4. Replace the cover taking care that the “O” ring seal is in place and the fixing screws are tightened correctly.

- Jumper setting "Action" - Jumper Einstellung "Wirkungsweise - Jumper instelling "Werkwijze"

Action "Direct" Wirkungsweise "Direkt" Werkwijze "Direkt"

Action "Reverse" Wirkungsweise "Umgekehrt" Werkwijze "Omgekeert"

Show 10 more labels / short text on this page
Input signal · Rotary actuator · Linear actuator · Close · Direct acting · Input signal · Rotary actuator · Linear actuator · Close · Reverse acting
Page 48 of the Emerson Process Management P2500 user manual — 5.1.1 Umschaltung auf umgekehrte Wirkung
Pagina 48 · klik om te vergroten
Pagina 48

5.0 Failure Modes / Ausfallarten / Storingen

5.1 Ausfallarten Doppeltwirkend

5.1 Storingen - dubbelwerkend

Die Standardeinstellung für doppeltwirkende Stellantriebe ist die, bei der ein ansteigendes Gerätesignal das Ventil öffnet. Beim Ausfal- len des Signals wird das Ventil geschlossen. Dies läßt sich ändern in ,Öffnen bei Signalausfall", indem die Einstellung auf REVERSE ACTING (UMGEKEHRTE WIRKUNG) umgestellt wird.

De standaardinstelling voor dubbelwerkende aandrijvingen is zodanig dat een in intensiteit toenemend ingangssignaal de klep opent. Door een signaalstoring wordt de klep gesloten. Dit kan worden gewijzigd in “Open bij signaalstoring” door de in- stelling te veranderen in OMGEKEERD WERKEND.

Die Auswirkung eines Signal- und/oder Luftausfalls hängt davon ab, wie Luft- und Potentiometeranschlüsse verbunden sind:

Het effect van een signaal- en luchtstoring is afhankelijk van de wijze waarop de lucht- en potentiometeraansluitingen zijn ge- maakt:

1. Direkt wirkend - Standardeinstellung

1. Direkt werkend - Standardeinstellung

Wirkung Luftausfall Signalausfall Direkt Stellung nicht definiert Zu

Werking Luchtstoring Signaalstoring Direkt Stand niet gedefinieerd Dicht

2. Umgekehrt wirkend

2. Omgekeerd werkend

Wirkung Luftausfall Signalausfall Umgekehrt Stellung nicht definiert Offen

Werking Luchtstoring Signaalstoring Omgekeerd Stand niet gedefinieerd Open

5.1.1 Umschaltung auf umgekehrte Wirkung

5.1.1 Wijzigingen voor omgekeerde werking

Zur Umschaltung von den Standardeinstellungen auf die umgekehr- te Wirkung:

Om van standaardinstelling op de instelling voor omgekeerde werking over te schakelen:

1. Die Schläuche ändern (siehe Abb. 5.1). 2. Den Deckel entfernen. 3. Wirkungsweise-Jumper auf umgekehrte Wirkung einstellen (Beide Jumper auf die rechte Position stecken, siehe Abb. 5.2). 4. Den Deckel wieder einlegen, dabei darauf achten, daß die ORingabdichtung in der richtigen Lage ist und die Fixierschrauben ordnungsgemäß festgezogen werden.
1. De luchtleidingen wijzigen (zie Afb. 5.1). 2. Verwijder het deksel. 3. Stel de "werkwijze"-jumpers in op omgekeerde werking (Beide jumpers op de rechter positie plaatsen, zie Afb. 5.2). 4. Breng het deksel weer aan en controleer of de O-ring op de juiste plaats zit en de bevestigingsschroeven correct zijn aangehaald.
Page 49 of the Emerson Process Management P2500 user manual — A
Pagina 49 · klik om te vergroten
Pagina 49

5.0 Failure Modes / Ausfallarten / Storingen

5.2 Failure Modes - Single Acting (Spring return)

1. Fail Close - Direct acting Input signal Rotary actuator

Spring return actuators may be “fail open” or “fail close” depending on what happens when the air fails. This air failure mode must be built into the actuator and maintained when the actuator is built onto the valve.

A

A

F20

In addition both these air failure modes may be either direct acting or reverse acting depending on what happens at the positioner when the 4 - 20 mA. signal fails or is reduced to it’s lowest level.

2. Fail Open - Direct acting Input signal Rotary actuator

A

Action

Air connection Failure

A

F20

1 2 Air Signal Direct A Block Close Close Direct Block A Open Close Reverse A Block Open Open Reverse Block A Close Open

3. Fail Close - Reverse acting Input signal Rotary actuator

5.2.1 Changes for Reverse Acting

To change from the standard setup to reverse acting:

A

A

1. Change the tubing (see fig. 5.3 to 5.6). 2. Plug the unused actuator port. 2. Remove the cover. 3. Change the action jumper setting by setting both jumpers to the right side (see fig. 5.2). 4. Replace the cover taking care that the “O” ring seal is in place and the fixing screws are tightened correctly.

F20

4. Fail Open - Reverse acting Input signal Rotary actuator

A

A

F20

Show 8 more labels / short text on this page
Linear actuator · Close · Linear actuator · Close · Linear actuator · Close · Linear actuator · Close
Page 50 of the Emerson Process Management P2500 user manual — 7.0 Position transmitter option PTF20 / Stellungsgeberoption PTF20 / Positietransmitter optie PTF20
Pagina 50 · klik om te vergroten
Pagina 50

7.0 Position transmitter option PTF20 / Stellungsgeberoption PTF20 / Positietransmitter optie PTF20

4. Mount positioner on actuator (see chapter 2 or 3). 5. Make electrical connections as shown in fig. 7.2. Connect also the control signal of the positioner as decribed in chapter 4.

Wiring information Wiring dimension : 1.5 mm 2 / 14 AWG Tool : Screwdriver 0.6 x x 3.5 mm Turning moment : 0.8 Nm / 7 in/lb

6. Set jumpers to “Direct” or “Reverse” to achieve a 4-20 mA or a 20-4 mA feedback (see fig. 7.3). 7. Move the actuator pneumatically to the fully closed position. Adjust the trimmer marked “Zero” to achieve a 4 mA reading (20 mA in case of "Revers Action"). 8. Move the actuator pneumatically to the fully open position. Adjust the trimmer marked “Span” to achieve a 20 mA reading (4 mA in case of "Revers Action").
Output signalSignal ; 4-20 mA Voltage : 15-30 VDC "Zero" "Span"

Action "Direct" = 4-20mA at CCW rotation Wirkungsweise "Direkt" = 4-20mA bei CCW Rotation Werkwijze "Direkt" = 4-20mA bij rota- tie tegen de klok in

Action "Reverse" = 20-4mA at CCW rotation Wirkungsweise "Umgekehrt" = 20-4mA bei CCW Rotation Werkwijze "Omgekeert" = 20-4mA bij rotatie tegem de klok in.

Show 9 more labels / short text on this page
Jumpersetting "Action" · - + · Standard "Direct" Action · 20 mA · 4 mA · "Revers" Action · 0 mA · Valve position · 0% 100%
Page 51 of the Emerson Process Management P2500 user manual — 7.0 Position transmitter option PTF20 / Stellungsgeberoption PTF20 / Positietransmitter optie PTF20
Pagina 51 · klik om te vergroten
Pagina 51

7.0 Position transmitter option PTF20 / Stellungsgeberoption PTF20 / Positietransmitter optie PTF20

4. Den Stellungsregler mit dem Antrieb zusammenbauen (siehe Kapitel 2 oder 3). 5. Die in Abb. 7.2 gezeigten Verbindungen herstellen. Ebenfalls das Steuersignal des Stellungsreglers anschliessen wie beschrieben in Kapitel 4.
4. De standsteller samenbouwen met de aandrijving (zie hoofdstuk 2 of 3). 5. Maak de verbindingen zoals getoond in afb. 7.2. Sluit ook het stuursignaal aan van de standsteller zoals beschreven in hoofdstuk 4.

Verdrahtungsinformation Drahtabmessung : 1,5 mm 2 / 14 AWG Werkzeug : Schraubenzieher 0,6 x x 3,5 mm Anzugsdrehmoment : 0,8 Nm / 7 in/lb.

Bedradingsinformatie Draadafmeting : 1,5 mm 2 / 14 AWG Gereedschap : Schroevendraaier 0,6 x x 3,5 mm Aanhaalmoment : 0,8 Nm / 7 in/lb

6. Die Jumper in der Position anbringen, die “Direkt” bzw. “Umgekehrt” entspricht, um eine 4-20 mAoder 20-4 mA-Rückmeldung zu bewirken (siehe Abb.7.3). 7. Den Antrieb pneumatisch in die völlig geschlossene Stellung fahren. Den mit “Zero” bezeichneten Trimmer so einstellen, daß 4 mA angezeigt wird (20 mA bei Umgekehrter Wirkung). 8. Den Antrieb pneumatisch in die völlig offene Position fahren. Den mit “Span” bezeichnetenTrimmer so einstellen, daß 20 mA angezeigt wird (4 mA bei Umgekehrter Wirkung)..

6. Stel de jumpers op “direkt” of “omgekeerde werking” in om een terugkoppeling van 4-20 mA of van 20-4 mA te bereiken (zie afb. 7.3). 7. Beweeg de aandrijving pneumatisch naar de positie volledig gesloten. Stel de trimmer met de markering “nul” (zero) bij om een 4 mA uitlezing te bereiken (20 mA bij omgekeerde werking). 8. Beweeg de aandrijving pneumatisch naar de positie volledig open. Stel de trimmer met de markering “spanwijdte” (span) bij om een 20 mA uitlezing te bereiken (4 mA bij omge- keerde werking).

Omgekeerde werking Umgekehrte Wirkungsweise

Show 11 more labels / short text on this page
20 mA · 20 mA · 4 mA · 4 mA · Stanfard "Direkte" Wirkungsweise · Standaard "Direkte" werking · 0 mA · 0 mA · Armturen Stellung Afsluiterstand · 0% 100% · 0% 100%
Page 52 of the Emerson Process Management P2500 user manual — Contact Us
Pagina 52 · klik om te vergroten
Pagina 52
Page 52 of the Emerson Process Management P2500 user manual — Contact Us
Page 53 of the Emerson Process Management P2500 user manual — Contact Us
Pagina 53 · klik om te vergroten
Pagina 53
Page 53 of the Emerson Process Management P2500 user manual — Contact Us
Page 54 of the Emerson Process Management P2500 user manual — Contact Us
Pagina 54 · klik om te vergroten
Pagina 54

INTERNATIONAL BENELUX GERMANY EL-O-MATIC B.V. EL-O-MATIC Benelux EL-O-MATIC GmbH. P.O. Box 223 P.O. Box 223 Postfach 460234 . D-47856 Willich 7550 AE Hengelo (O) 7550 AE Hengelo (O) Siemensring 112 . D-47877 Willich Asveldweg 19 Asveldweg 11 Tel. +49 2154 499660 7556 BR Hengelo (O) 7556 BT Hengelo (O) Fax. +49 2154 427669 Holland Holland Löbtauer Strasse 65/67. D-01159 Dresden Tel. +31 74 256 10 10 Tel. +31 74 256 10 20 Tel. +49 351 867 96 30 Fax. +31 74 291 09 38 Fax. +31 74 243 86 90 Fax. +49 351 867 96 50

UNITED KINGDOM SOUTH AFRICA VENEZUELA EL-O-MATIC Ltd. EL-O-MATIC (Pty) Ltd. EL-O-MATIC INTERNATIONAL 16/17 Beeding Close Teknipark, 62 Lower Germiston Road Av. Principal Los Ruices Southern Cross Trading Estate Heriotdale, Johannesburg Edif. stemo piso 1 Ofc. 1A Bognor Regis P.O. Box 40348 Caracas West Sussex, PO 22 9TS Cleveland 2022 Venezuela Tel. +44 1243 830 363 Tel. +27 11 626 2880/1/2 Tel. +58 2 237 77 51 Fax. +44 1243 830 843 Fax. +27 11 626 2905 Fax. +58 2 238 9023

U.S.A. INDIA SINGAPORE EL-O-MATIC U.S.A. Inc. EL-O-MATIC India Pvt Ltd. EL-O-MATIC Valve Actuators 135 English Street 296/A/1/5, St. Patrick’s Town Far East Pte Ltd. Hackensack NJ 07601 Near Railway Crossing 28 Third Lok Yang Road Tel. +1 201 489 5550 Hadapsar Industrial Estate Singapore 628016 Fax. +1 201 489 9171 Pune 411 013 Tel. +65 26 24 515 www.el-o-matic.com Tel. +91 212 672916 Fax. +65 2680028 / 770 80 80 Fax. +91 212 674465

Bronnen

Referenties en links

Pagina's waarnaar wordt verwezen in deze handleiding — fabrikant, ondersteuning en downloads.

Vraag stellen over de Emerson Process Management P2500

Eigenaren en ons team reageren doorgaans binnen een dag — en uw vraag helpt ook de volgende persoon.

Add your email to get notified when it’s answered — no spam, ever.

0 questions
Nog geen vragen over de Emerson Process Management P2500

Stel als eerste een vraag — andere eigenaren of ons team geven antwoord.

Origineel document

Emerson Process Management P2500 handleiding-pdf

59 pagina's·2.3 MB·Auto-onderdelen·PDF
Klik op een bovenstaande pagina om deze hier te openen
Pagina 1 / …
100%
Pagina's laden…