Gebruiksaanwijzing /service van het product SG5K-1TXC van de fabrikant Falcon
Ga naar pagina of 30
OWNER'S OPERATING MANUAL SG Series UPS Plus ® Uninterruptible Power Supply Models: SG5K-1TX, SG5K-1TXC, SG5K-2T. SG5K-2TC SG5K-2TX, SG5K-2TXC SG6K-1TX SG6K-2T, SG6K-2TC Detailed SG Series product specifications are available in PDF format at www.
SG UPS Features. ...... 1 SG Series Online UPS Block Diagram. ..... 1 Important Safety Instructions (READ FIRST) .... 2 Chapter 1. SG Series UPS Overview ..... . 3 True Regenerative On-line Design .... . 3 Input Power Factor Correction .... . 3 Microprocessor Control .
SG SERIES UPS FEATURES SG SERIES ON-LINE UPS SYSTEM BLOCK DIAGRAM Models available with either 120V or 208-240Vac Input True Double Conversion On-Line Design Input Power Factor Correction Dual Output .
IMPORTANT SAFETY INSTRUCTIONS SAVE THESE INSTRUCTIONS This manual contains important instructions which must be followed during the installation, operation and maintenance of this UPS and its batteries. Please read all instructions before operating this equipment and save this manual for future reference.
CHAPTER 1 CHAPTER 1 SG Series UPS - Overview True Regenerative On-Line Design As new and innovative technologies have become the backbone of today's businesses, maxi - mum system availability is critical and downtime is more expensive than ever.
CHAPTER 2 CHAPTER 2 INSTALLATION INSTRUCTIONS General - Common for all models 1. Verify the following is included in the UPS shipping carton: (1) UPS, (1) Software Diskette(s) & Manual, (1) Owners Manual & (1) UPS/Computer Cable. 2. Verify the UPS unit is configured for the proper input/output voltage and frequency.
DIP SWITCHES SELECTION TABLE ON = 1 OFF = 0 SW2 SW1 OUTPUT VOLTAGE 1 (All models) OUTPUT VOLTAGE 2 (- TX & - TXC models only) Down Down 208 Vac 115 Vac Down Up 220 Vac (default) 120 Vac Up Down 23.
6. Select a suitable location for the UPS. VERIFY THE FLOOR OR SURFACE SUPPORTING THE UPS WILL SUPPORT THE WEIGHT OF THE UPS AND ANY OPTIONAL EXTENDED BATTERY BANKS. SG5K-2T & SG6K-2T UPS MODELS = 216 lbs. (98 kg) SG5K-2TC & SG6K-2TC UPS MODELS = 239 lbs.
Installation Instructions For Hardwire Models (see model numbers referenced below) 1.0 UPS Input & Output Requirements. Note: All SG Series hardwire UPS models must be installed by a licensed electrician, in accordance with the National Electrical Code (NEC) ANSI/NFPA70 and all local regulations.
2.0. UPS Output Requirements Note: The outputs of SG 5 & 6kVA models are not configured for 208 or 240Vac split-phase operation. Please reference the output configuration diagrams on pages 9-10 prior to making any wiring connections to the UPS. Should a 208 or 240Vac split-phase output configuration be required, please contact the factory.
Terminal #10 Terminal #1 PFC INPUT RECTIFIER PWM INVERTER Output 2 - 120Vac Line (Black Wire) Output 2 - 120Vac Neutral (White WIre ) Chassis Ground (Output 1 & 2) Chassis Ground (Input) 120 Vac I.
INTERNAL UPS DIAGRAM SG5K-2TX(C) & SG6K-2TX(C) Terminal #10 Terminal #1 PFC INPUT RECTIFIER PWM INVERTER Output 2 - 120Vac Line (Black Wire) Output 2 - 120Vac Neutral (White WIre ) Chassis Ground .
3. Select a suitable location for the the extended battery bank, preferably close to the UPS to minimize the risk of DC voltage drop due to excessive long wiring runs. Use 10 Awg, 600V insulated wire for all hardwired DC connections between the UPS and battery bank(s).
12 G N D L 1 L 1 L 2 L 2 240 Vdc + UTILITY INPUT OUTPUT TO NEXT BANK BATTERY Battery Disconnect & Circuit Breaker Input/Battery Termi n a l Block CAUTION Reference the torque specifications in this manual prior to making terminal block conn ections.
Installation Instructions for All Models Except Hardwire 1.0 UPS Input & Output Requirements. Note: All SG Series UPS models, except Hardwire models, may be installed by anyone providing the specified outlet, circuit and circuit protections are available.
2.1 Output Power Distribution Center All models referenced on the previous page come equipped with a (4) bay power distribution center mounted on the rear of the UPS. The Power Distribution center is shown in the “standard” or “base” configuration.
15 Typical SG5 & 6kVA Rear Panel Layout (Shown with Power Distribution Center ) Output Voltage & Green Mode Select Switches RS-232 Computer Interface Connector Communications Option Slot Cover.
16 INSTALLATION PROCEDURE 1. Verify the battery disconnect circuit breaker on the UPS and all external battery banks to be connected are in the off position. 2. Locate the battery interconnect cable(s). 3. Connect one end of the battery interconnect cable to the the UPS battery connector located on the power distribution center (see page 14).
17 CHAPTER 3 CHAPTER 3 OPERATION 1 2 3 4 5 6 7 8 9 10 11 UPS FRONT PANEL INDICATOR AND FUNCTION KEYS 1. LOAD LEVEL INDICATOR LEDs *The first or bottom LED is lit when the output load is greater than 25% of the ` rated output of the UPS. *The second LED is lit when the output load is greater than 50% of the rated output of the UPS.
5. BYPASS INDICATOR LED When this led is lit, the UPS bypass is active. Should the Alarm led be lit at the same time, the UPS detected an internal failure and the UPS must be serviced. 6. INVERTER INDICATOR LED When this led is lit, the UPS inverter is operating and powering the connected load.
AUDIBLE ALARMS Audible alarm signals are divided into two different levels of alarm status. Category one alarms represent normal or correctable operational alarms. Category two alarms are sounded in the event of abnormal operation. 1. Category one alarms : a.
Maintenance Bypass Operating Instructions Unless configured as a frequency converter, SG 5 & 6kVA models are equipped with an internal maintenance bypass switch. The switch is located on the rear panel of the UPS and is clearly identified, See page 15.
CHAPTER 4 CHAPTER 4 COMMUNICATIONS INTERFACES RS-232 INTERFACE 21 Pin # Function explanation I/O 9 RS 232 Rx INPUT 6 RS 232 Tx OUTPUT 7 Ground Location: The RS-232 interface is standard on all SG series UPS models. The port is located on the UPS rear panel, via a DB-9 female connector.
22 DRY CONTACT & OPTO COUPLER INTERFACE BOARD OPTIONS JP1 JP2 JP3 J1 J2 J3 DB - 9 Typical Falcon Dry Contact Relay Board PIN DESCRIPTION 1 Low Battery ( When UPS reaches low battery, contact activates) (J1, 1 - 2 short = N.O) (J1, 2 - 3 short = N.
23 PIN ASSIGNMENT FOR THE FALCON UA88373 OPTO-COUPLER OPTION BOARD (no-bypass signal) PIN DESCRIPTION 1 Not Used 2 Utility Loss (N.O.) (Closes upon utility loss) 3 Utility Loss (N.C.) (Opens upon utility loss) 4 Common for pins 2, 3 & 5 5 Low Battery (N.
CHAPTER 5 CHAPTER 5 Maintenance & Technical Support 1. Care & Maintenance FALCON ® SG Series UPSs are designed to be maintenance-free. They can be cleaned with a damp cloth or non-abrasive cleanser, providing the UPS is turned off and the input plug is disconnected from the utility source.
The following precautions should be observed by a qualified technician when working with batteries. 1. Remove watches, rings, or other metal objects. 2. Use tools with insulated handles. 3. Wear rubber gloves and boots. 4. Do not lay tools or metal parts on top of batteries.
6. Technical Support Your FALCON ® Electric SG Series UPS is backed by one of the finest customer service teams assembled. Write, call, fax or email should you require technical assistance or service. Falcon Electric, Inc. 5106 Azusa Canyon Road Irwindale, CA.
GENERAL PROVISIONS FALCON® ELECTRIC INC., hereby warrants product shipped under this agreement to be free from defective workmanship for a period of two years following date of shipment. This Limited New Product Warranty Agreement only applies to covered repairs to the product occurring within the United States and Canada.
SG Series TM UPS PLUS ® 5-6kVA MODELS 28 Electrical Input Nominal AC Voltage 120V 230V 230 V 120V 230 V 230 V AC Voltage Range 87 - 140V 170 - 275V 170 - 27 5V 87 - 140 V 170 - 275V 170 - 275V Current - Amps 38.
Een belangrijk punt na aankoop van elk apparaat Falcon SG5K-1TXC (of zelfs voordat je het koopt) is om de handleiding te lezen. Dit moeten wij doen vanwege een paar simpele redenen:
Als u nog geen Falcon SG5K-1TXC heb gekocht dan nu is een goed moment om kennis te maken met de basisgegevens van het product. Eerst kijk dan naar de eerste pagina\'s van de handleiding, die je hierboven vindt. Je moet daar de belangrijkste technische gegevens Falcon SG5K-1TXC vinden. Op dit manier kan je controleren of het apparaat aan jouw behoeften voldoet. Op de volgende pagina's van de handleiding Falcon SG5K-1TXC leer je over alle kenmerken van het product en krijg je informatie over de werking. De informatie die je over Falcon SG5K-1TXC krijgt, zal je zeker helpen om een besluit over de aankoop te nemen.
In een situatie waarin je al een beziter van Falcon SG5K-1TXC bent, maar toch heb je de instructies niet gelezen, moet je het doen voor de hierboven beschreven redenen. Je zult dan weten of je goed de alle beschikbare functies heb gebruikt, en of je fouten heb gemaakt die het leven van de Falcon SG5K-1TXC kunnen verkorten.
Maar de belangrijkste taak van de handleiding is om de gebruiker bij het oplossen van problemen te helpen met Falcon SG5K-1TXC . Bijna altijd, zal je daar het vinden Troubleshooting met de meest voorkomende storingen en defecten #MANUAl# samen met de instructies over hun opplosinge. Zelfs als je zelf niet kan om het probleem op te lossen, zal de instructie je de weg wijzen naar verdere andere procedure, bijv. door contact met de klantenservice of het dichtstbijzijnde servicecentrum.