Gebruiksaanwijzing /service van het product BT- 65 van de fabrikant A.O. Smith
Ga naar pagina of 16
1 MODEL BT- 65 PLACE THESE INSTRUCTIONS ADJACENT T O HEA TER AND NOTIFY OWNER TO KEEP FOR FUTURE REFERENCE. COMMERCIAL GAS W A TER HEA TER Glass-Lined T ank-type W ater Heater P ART NO.
2 ROUGH-IN-DIMENSIONS FOREWORD The design of Model BT-65 complies with the latest version of ANSI Z21.10.1/CSA 4.1 M98 as automatic storage type water heater . Installation diagrams are found in this manual. These diagrams will serve to provide the installer with a reference for the materials and method of piping necessary .
3 TABLE OF CONTENTS Page ROUGH-IN DIMENSIONS ....................................................................... 2 FOREWORD .......................................................................................... 2 GENERAL SAFETY INFORMA TION ..
4 to flow . THERE SHOULD BE NO SMOKING OR OPEN FLAME NEAR THE FAUCET A T THE TIME IT IS OPEN. INSULA TION BLANKETS Insulation blankets available to the general public for external use on gas water heaters are not necessary with A.O. Smith water heater .
5 U.S. REQUIREMENTS Ratings specified by manufacturers for most appliances apply for elevations up to 2000 feet (610 m). For elevations above 2000 feet (610 m), ratings must be reduced at the rate of 4% for each 1000 feet (305 m) above sea level.
6 2. T oxic chemicals, such as those used for boiler treatment, shall NEVER be introduced into this system. 3. This unit may NEVER be connected to any existing heating system or component(s) previously used with a non-potable water heating appliance. 4 .
7 In addition to the appliance relief valve, each remote storage tank which may be used in conjunction with this appliance shall also be installed with a properly sized, rated and approved combination temperature (ANSI) and pressure (ASME) relief valve(s).
8 TABLE 1 - GAS SUPPLY LINE SIZES (IN INCHES)* MAXIMUM CAPACITY OF PIPE IN CUBIC FEET PER HOUR LENGTH NORMAL IRON PIPE SIZES (INCHES) I N INPUT IN THOUSANDS BTU/HR FEET 1/2" 3/4" 1" 1 1.
9 T ABLE 2 MANIFOLD PRESSURE SETTING Model T ype of Manifold Number G as Input Pressure BT-65 Natural 65,000 Btu/hr 4.0 in. W .C. 16.7 KW/hr 1.0 Kpa BT-65 Propane 55,000 Btu/hr 10.0 in. W.C. 16Kw 2.49kPa OPERA TION It is recommended that a qualified person perform the initial firing of the heater.
10 FOR YOUR SAFETY READ BEFORE LIGHTING LIGHTING INSTRUCTIONS W ARNING I f you do not follow these instructions exactly , a fire or explosion may result causing property damage, personal injury or loss of life. • If you cannot reach your gas supplier , call the fire department.
11 TEMPERA TURE REGULA TION DANGER THIS W A TER HEA TER IS EQUIPPED WITH AN ADJUST ABLE THERMOST A T TO CONTROL W A TER TEMPERA TURE. HOT W A TER TEMPERA TURES REQUIRED FOR AUTOMA TIC DISHW ASHER AND LAUNDRY USE CAN CAUSE P AINFUL SCALDING WITH POSSIBLE SERIOUS AND PERMANENT INJURY .
12 of the building. Turn on all appliances not connected to the venting system. Turn on all exhaust fans, such as range hoods and bathroom exhausts, so they shall operate at maximum speed. Close fireplace dampers. 4. Follow the lighting instruction. Place the water heater being inspected in operation.
13 Compare the actual input rate to that given on the heater’s rating plate. In the example, the BT-65’s full input rate should be 65,000 Btuh (19.0 KW) for natural gas. VENT SYSTEM Examine the venting system every 6 months for obstructions and/ or deterioration of vent piping.
14 W A TER TEMPERATURE IS T OO HOT 1. The thermostat water temperature adjusting dial may be set too high. 2 . If lowering control setting does not reduce the water temperature contact your dealer . GAS SMELL A T THE HEA TER 1. Close the main Shut-off valve in the gas supply pipe near the heater , see fig.
15 Model BT Limited W arranty A. O. Smith Corporation, the warrantor, extends the following LIMITED W ARRANTY to the owner of this water heater . 1. THE T ANK If the glass-lined tank in this water hea.
16 PRODUCT SERVICE DIVISION 5621 W . 1 15TH STREET , ALSIP , IL 60803 PHONE: 1-800-433-2545 F AX: 1-800-433-2515 E-MAIL: part s@hotwater .com www .hotwater .
Een belangrijk punt na aankoop van elk apparaat A.O. Smith BT- 65 (of zelfs voordat je het koopt) is om de handleiding te lezen. Dit moeten wij doen vanwege een paar simpele redenen:
Als u nog geen A.O. Smith BT- 65 heb gekocht dan nu is een goed moment om kennis te maken met de basisgegevens van het product. Eerst kijk dan naar de eerste pagina\'s van de handleiding, die je hierboven vindt. Je moet daar de belangrijkste technische gegevens A.O. Smith BT- 65 vinden. Op dit manier kan je controleren of het apparaat aan jouw behoeften voldoet. Op de volgende pagina's van de handleiding A.O. Smith BT- 65 leer je over alle kenmerken van het product en krijg je informatie over de werking. De informatie die je over A.O. Smith BT- 65 krijgt, zal je zeker helpen om een besluit over de aankoop te nemen.
In een situatie waarin je al een beziter van A.O. Smith BT- 65 bent, maar toch heb je de instructies niet gelezen, moet je het doen voor de hierboven beschreven redenen. Je zult dan weten of je goed de alle beschikbare functies heb gebruikt, en of je fouten heb gemaakt die het leven van de A.O. Smith BT- 65 kunnen verkorten.
Maar de belangrijkste taak van de handleiding is om de gebruiker bij het oplossen van problemen te helpen met A.O. Smith BT- 65 . Bijna altijd, zal je daar het vinden Troubleshooting met de meest voorkomende storingen en defecten #MANUAl# samen met de instructies over hun opplosinge. Zelfs als je zelf niet kan om het probleem op te lossen, zal de instructie je de weg wijzen naar verdere andere procedure, bijv. door contact met de klantenservice of het dichtstbijzijnde servicecentrum.