ENGINEERING DESIGN GUIDEp.1HTV/HTD/HTH Seriesp.1Two-Stage Geothermal Heat Pumpsp.12 to 6 Tonsp.1Model Breakdownp.2Model nomenclature – Two Stage geothermal heat Pumpp.2Design Featuresp.3Service Advantagesp.3Factory Qualityp.3-Verifies that the correct components are being assembled;p.3-Automatically performs special leak tests on all joints;p.3-Conducts pressure tests;p.3-Performs a highly detailed run test;p.3-Automatically prevents a "failed" unit from being packaged forp.3shipment;p.3Operating Efficienciesp.3-Performs all refrigerant brazing in a nitrogen-rich environment;p.3Options & Accessoriesp.3What’s Newp.41>7JI(;MM?J> B?C7J;'7IJ;HI.H7DGK?B?JOWp.4the HT series?p.4HFC-410Ap.4M7HC?D=FEJ;DJ?7B Q 0?HJK7BBODE=B?:; /DB?A;EJ>;H7BJ;HD7J?L;H;<H?=;H7DJI J>;p.4£Î‡p.4<4AE%%p.4HT Seriesp.4̜p.4fixed-capacity compressors byp.49ECFH;IIEHI;9J?ED97D8;I;HL?9;:<HECJ>;<HEDJp.4.>;";D;I?I"-p.5Copeland UltraTech Two-Stage Scroll Compressorp.5)FJ?ED7B-J7J; )< .>; HJ" 07H?78B;-F;;: BEM;H'EJEHp.5>ÌiÃÌÊ/iV ˜œœ}އ iVÌÀœ˜ˆV>ÞÊVœ““ÕÌ>Ìi`]Ê *Àœ}À>““>Li]Ê6>Àˆ>LiÊ-«ii`Ê œÜiÀÊ œÌœÀp.5E7J;: ?H E?Bp.5iVÌÀœÊ`i«œÃˆÌˆœ˜ÊVœ>Ìi`Ê>ˆÀÊVœˆp.5!KBBO$DIKB7J;: BEM;H-;9J?ED M?J>!KBBO $DIKB7J;: ECFH;IIEH-;9J?EDp.5$DJ;=H7J;:!?BJ;H,79AM?J>,;JKHD ?H K9J EDD;9J?EDp.5-BEF;: H7?D*7DM?J> ED:;DI7J; )L;HYEM-;DIEH 6p.5-œ«i`Ê-Ì>ˆ˜iÃÃÊ-ÌiiÊ À>ˆ˜Ê*>˜ÊÜˆÌ Ê œ˜`i˜Ã>ÌiÊ"ÛiÀyœÜÊ-i˜ÃœÀp.5N9BKI?L; EK8B;-FH?D= D:"HECC;J ECFH;IIEH$IEB7J?ED!EH/BJH7 +K?;J)F;H7J?EDp.5œÕLiÊ-«Àˆ˜}ʘ`ÊÀœ““iÌÊ œ“«ÀiÃÜÀÊ Ãœ>̈œ˜ÊœÀÊ1ÌÀ>Ê+ՈiÌÊ"«iÀ>̈œ˜p.5™ orp.5!?L; 7IO &?<J EKJ-;HL?9; 99;II*7D;BI 9p.5ˆÛiÊ >ȏÞÊ,i“œÛ>LiÊ-iÀۈViÊVViÃÃÊ *>˜iÃp.5I7 i˜Êˆ˜ÃÌ>i`ÊÜˆÌ Ê>ÊÌ iÀ“œÃÌ>ÌÊÌ >ÌÊ >ÃÊ>Êv>ՏÌÊp.5HT Series Ratings ARI/ASHRAE/ISO 13256-1 at EWT (Entering Water Temperature)p.6HTV/HTD/HTH024p.6HTV/HTD/HTH036p.6HTV/HTD/HTH048p.6HTV/HTD/HTH060p.6HTV/HTD/HTH070p.6HT Physical Datap.7HT 024 HT 036 HT 048 HT 060 HT 070p.7Vertical-HTV & Downflow-HTDp.7Dimensions – Vertical Upflowp.8Right Return Right Viewp.9Left Return Left View - Filter Rack Knife Edgep.9Front-Viewp.9- Filter Rack Knife Edgep.9Dimensions – Vertical Downflowp.10Discharge Connection Duct Flange Installed (+/- 0.10 in, +/- 2.5mm)p.13PERFORMANCE DATA HT024 Part Loadp.14/6äÓ{Ê*>ÀÌÊ œ>`p.14HTV024, HTD024 & HTH024 Part Loadp.14HTV024 & HTD024 Part Loadp.14PERFORMANCE DATA HT024 Full Loadp.15HTV024 & HTD024 Full Loadp.15HTV024, HTD024 & HTH024 Full Loadp.15/6äÓ{ÊՏÊ œ>`p.15PERFORMANCE DATA HT036 Part Loadp.16/6äÎÈÊ*>ÀÌÊ œ>`p.16HTV036 & HTD036 Part Loadp.16HTV036, HTD036 & HTH036 Part Loadp.16PERFORMANCE DATA HT036 Full Loadp.17/6äÎÈÊՏÊ œ>`p.17HTV036, HTD036 & HTH036 Full Loadp.17HTV036 & HTD036 Full Loadp.17PERFORMANCE DATA HT048 Part Loadp.18/6ä{nÊ*>ÀÌÊ œ>`p.18HTV048 & HTD048 Part Loadp.18
Page 1 of the Heat Controller HTV SERIES user manual — ENGINEERING DESIGN GUIDE
Pagina 1 · klik om te vergroten
Pagina 1
Heat Controller HTV SERIES — ENGINEERING DESIGN GUIDE diagram (page 1)
Afb. 1

ENGINEERING DESIGN GUIDE

HTV/HTD/HTH Series

Two-Stage Geothermal Heat Pumps

2 to 6 Tons

  • Heat Controller, Inc.
  • 1900 Wellworth Ave.
  • Jackson, MI 49203
  • (517)787-2100
  • <a href="http://www.heatcontroller.com" rel="nofollow noopener" target="_blank">www.heatcontroller.com</a>
Page 2 of the Heat Controller HTV SERIES user manual — Model Breakdown
Pagina 2 · klik om te vergroten
Pagina 2

Model Breakdown

Model nomenclature – Two Stage geothermal heat Pump

Heat Controller HTV SERIES — Model Breakdown diagram (page 2)
Afb. 2 · Model Breakdown

P = Back W = Straight

Heat Controller HTV SERIES — Model Breakdown diagram (page 2)
Afb. 3 · Model Breakdown
Heat Controller HTV SERIES — Model Breakdown diagram (page 2)
Afb. 4 · Model Breakdown

H = Horizontal · J = Cupro-Nickel

Page 3 of the Heat Controller HTV SERIES user manual — Options & Accessories
Pagina 3 · klik om te vergroten
Pagina 3

Features of the Two Stage HT Series The HT Series Geothermal Heat Pumps are some of the most efficient and innovative geothermal units on the market today. Packed with features, they offer the best value to the homeowner who is interested in quiet comfort and low operating costs as a result of extraordinary efficiencies.

Technically, the HT Series are state-of-the-art with digital electronic controls, multi-stage scroll compressors, computer controlled fan motors, zero ozone depleting refrigerant, and much more.

Design Features

Service Advantages

  • Five capacities to meet all application requirements—two, three, four and six ton models.
  • Three removable access panels for the compressor compartment and one or two (depends on model) for the air handler compart ment offer quick access to all internal components even with ductwork in place, making the unit service-friendly.
  • Efficient operation from 20°F to 120°F entering water tempera tures. Flow rates may be as low as 1.6 gpm/ton.
  • Built with bi-directional thermal expansion valve.
  • Top supply air discharge accommodates upflow applications.
  • Select left or right hand return air positions for all models; cabinets include a deluxe filter rack/duct collar.
  • Brass, swivel water connections make it easy to connect loop and hot water piping.
  • Insulated divider and separate air handling/compressor access panels allow service testing without air bypass.
  • Variable speed ECM blower motor adjusts to multiple duct system applications and provides soft start for added comfort and quiet operation.
  • Design allows in-place service in tight installation spaces.
  • Narrow cabinet design can be easily moved through doorways.
  • CXM control features LED status light with memory feature for easy diagnostics.
  • Internally trapped condensate piping (on all vertical units) allows easy, compact installation.
  • Control box and fan motors have quick-attach wiring connections for fast removal/reconnection.
  • Internal electric heat unit (optional) is designed for easy field installation.
  • Biflow liquid line filter drier is factory-installed.
  • Electric box is positioned for easy field wiring from two sides.
  • 75 VA control transformer comes with circuit breaker.
  • Loop pump power block is built with circuit breaker.
  • Internal drop-out blower assemblymakes servicing simple.
  • Coaxial low temperature protection can be selected in the field for well or closed loop installations.
  • Refrigerant circuit includes high and low pressure service ports.
  • E-coated refrigerant-to-air coil helps protect the coil from corrosion and extends life expectancy.
  • Air coil low temp. protection utilizes high accuracy thermistors.
  • Coaxial heat exchanger, refrigerant suction lines, hot water generator coil, and all water pipes are fully insulated to reduce condensation in low temperature conditions.

Factory Quality

  • All units are built using our state-of-the-art manufacturing system that is designed to assure quality of the highest standards. This system:
  • Isolation mounted compressors and low RPM blowers are used to reduce noise; compressor compartment and interior cabinet are insulated with 1/2" coated glass fiber insulation.

-Verifies that the correct components are being assembled;

-Automatically performs special leak tests on all joints;

  • Double isolated compressor delivers extra quiet operation.
  • Safety features include: high pressure and loss of charge pro tection for the compressor; condensate overflow protection; low temperature protection sensors to safeguard the coaxial heat exchanger and air coil; hot water high-limit hot water genera tor pump shutdown; fault lockout that enables emergency heat and prevents compressor operation until thermostat or circuit breaker has been reset.

-Conducts pressure tests;

-Performs a highly detailed run test;

-Automatically prevents a "failed" unit from being packaged for

shipment;

-Creates a computer database of run tests for future service analysis and diagnostics;

Operating Efficiencies

-Includes painting heavy gauge steel cabinets with durable epoxy for a long-lasting finish;

  • AHRI/ASHRAE/ISO 13256-1 ratings for heating COPs and cooling EERs are industry leaders.

-Performs all refrigerant brazing in a nitrogen-rich environment;

  • Hot water generator (HWG) with internal pump generates hot water at dramatic savings while improving system performance.

-Evacuates units to a deep vacuum of less than 50 microns prior to refrigerant charging

  • Efficient scroll compressors provide quiet, reliable operation.

-Halogen leak tests all joints to ensure a leak rate of less than 1/4 ounce per year.

  • Oversized coaxial tube water-to-refrigerant heat exchanger delivers high efficiency and extra heating capacity; convoluted water tube functions efficiently at low flow rates and provides resistance to freeze damage.

Options & Accessories

  • Optional internal auxiliary electric heat.
  • Oversized rifled copper tube/lanced aluminum fin air-to-refriger ant heat exchanger offers high efficiencies at low air velocity.
  • Electronic auto-changeover thermostats with indicator LEDs.
  • Closed loop flow controller and hose kits.
  • Large, low RPM blower is both quiet and efficient, and provides high static capability.

See Geo Accessories brochure for complete list of accessories.

Page 4 of the Heat Controller HTV SERIES user manual — ̜
Pagina 4 · klik om te vergroten
Pagina 4

What’s New

1>7JI(;MM?J> B?C7J;'7IJ;HI.H7DGK?B?JOW

the HT series?

,‡{£äÊ,ivÀˆ}iÀ>˜Ì,‡{£äʈÃÊ>ʘœ˜‡V œÀˆ˜iÊL>Ãi`]Ê ‡{£ä]Ê ÀivÀˆ}iÀ>˜ÌÊÜˆÌ ÊâiÀœÊœâœ˜iÊ`i«ïœ˜Ê>˜`ʏœÜÊ}œL>ÊÜ>À“ˆ˜}Ê«œÌi˜‡ ̈>°ÊÊÌʈÃÊÃii˜Ê>ÃÊÌ iÊvÕÌÕÀiÊ>Ê ÀivÀˆ}iÀ>˜ÌÃÊÕÃi`ÊܜÀ`܈`i° ,‡{£äÊV >À>VÌiÀˆÃ̈VÃÊ>Ài\ UÊÊ i>ÀÊ>âiœÌÀœ«ˆVʓˆÝÌÕÀiʜvÊxä¯Ê,‡ÎÓÊ>˜`Ê Ê xä¯Ê,‡£Óx° UÊ6ˆÀÌÕ>ÞʘœÊ}ˆ`i° UÊxä‡Èä¯Ê ˆ} iÀʜ«iÀ>̈˜}Ê«ÀiÃÃÕÀiÃÊÌ >˜Ê,‡ÓÓ° UÊÊÌ œÕ} Ê>ÊLˆ˜>ÀÞÊLi˜`ÊÌ iÊÌܜÊVœ“«œ˜i˜ÌÃÊ >ÛiÊÊÊ Ê Ê Ì iÊÃ>“iʏi>ŽÊÀ>Ìi°ÊÃÊ>ÊÀiÃՏÌÊÀivÀˆ}iÀ>˜ÌÊV>˜ÊÊ LiÊ>``i`]ʈvʘiViÃÃ>ÀÞ]ÊÜˆÌ œÕÌÊÀiVœÛiÀˆ˜}ÊÌ iÊ Ê V >À}i°

(*!+( 2 (" (%* 7HJ>*KH;Z?I7DED 9>BEH?D;87I;:#! H;7J M?J>, 7D:, ?II;;D7IJ>;

HFC-410A

J;CF;H7JKH;B;L;BI7D:BEM;HH;B7J?L;>KC?:?JO .>?I;B?C?D7J;I KD;L;DF;7AI7D:L7BB;OI7D:7BBEMI;7J?D=7D:9EEB?D=IOIJ;C H7?I?D=J>;?HB;L;BE;DOEKH9KIJEC;HID;;:7D;M >;7J?D=7D:9EEB?D=IOIJ;C C7A;IKH;?J>7IJ>;8;IJJ;9>DEBE=O ?DI?:;SJ>; EF;B7D:-9HEBB/BJH7.;9>W9ECFH;IIEH

R-410A is a non-chlorine-based refrigerant with zero ozone depletion and low global warming potential

, Q #?=>;H;<X9?;D9?;I >?=>;HEF;H7J?D=FH;IIKH;I Q 4;HEEPED;:;FB;J?EDFEJ;DJ?7B7D:BEM=BE87B

-7L;M?J>IKF;H?EH;; EF;B7D:-9HEBB/BJH7.;9>W9ECFH;IIEH:;B?L;HI>?=>;H ;7D7DOEJ>;HI?D=B;9ECFH;IIEHIOIJ;C $D/BJH7.;9>WFHEL?:;KFJE =H;7J;H;D;H=O;?9>97DI7L;>EC;EMD;HI >KD:H;:IE

M7HC?D=FEJ;DJ?7B Q 0?HJK7BBODE=B?:; /DB?A;EJ>;H7BJ;HD7J?L;H;<H?=;H7DJI J>;

JME9ECFED;DJI?D#! >7L;L?HJK7BBOJ>;I7C;B;7A H7J;I .>;H;<EH; H;<H?=;H7DJ97D8;7::;:?<D;9;II7HOM?J>EKJ H;9EL;H?D=J>;9>7H=;

£Î‡

0# * 1#* ( BB.H7DGK?B?JOWKD?JI?D9BK:;7 7UFB;7J;:>?=>;

.7A;?J;7IOM?J>GK?;J;H9EDJHEB EF;B7D:-9HEBB/BJH7.;9>W?I H;C7HA78BOGK?;J7J8EJ>;EF;H7J?ED &;7HDJ>;8;7KJO E;:;I?=D 1?J> EF;B7D:-9HEBB /BJH7.;9>W JME ?DJ;HD7B8OF7IIFEHJI ;D78B;J>;IOIJ;CJE HKD7JF7HJ BE7: 97F79?JO;CE:KB7J?EDH?D=?I79J?L7J;: I;7B?D= J>;8OF7IIFEHJI7D:?DIJ7DJBOI>?7D=?D=DEIJEFF?D=7D: IJ7HJ?D=H;GK?H;:B?A;EJ>;HJME IJ7=;9ECFH;IIEHI

<4AE%%

Heat Controller HTV SERIES — <4AE%% diagram (page 4)
Afb. 5
Heat Controller HTV SERIES — <4AE%% diagram (page 4)
Afb. 6

Electro deposition-Coated Air Coil Ê/ÊÃiÀˆiÃʓœ`iÃÊvi>ÌÕÀiÊ>˜Êi‡Vœ>Ìi` >ˆÀ‡Vœˆ°Ê/ ˆÃÊ iVÌÀœ‡`i«œÃˆÌˆœ˜Ê«ÀœViÃÃÊ ÜˆÊ«ÀœÛˆ`iÊÞi>ÀÃʜvÊ«ÀœÌiV̈œ˜Ê>}>ˆ˜ÃÌÊ VœÀÀœÃˆœ˜ÊvÀœ“Ê>ˆÀLœÀ˜iÊV i“ˆV>ÃÊ ÀiÃՏ̈˜}ÊvÀœ“Ê“œ`iÀ˜ÊLՈ`ˆ˜}ʓ>ÌiÀˆ>Ê œÕÌÊ}>ÃȘ}Ê>˜`ʓœÃÌÊi˜ÛˆÀœ˜“i˜Ì>Ê

HT Series

Heat Controller HTV SERIES — HT Series diagram (page 4)
Afb. 7 · HT Series

7 ˆiÊ œ«i>˜`Ê-VÀœÊ1ÌÀ>Ê/iV ÒÊLՈ`Ãʜ˜ÊiÃÌ>LˆÃ i`ÊÃVÀœÊ ÌiV ˜œœ}Þ]ʈÌʈÃÊÃ̈Ê>ÊÃVÀœÊ>ÌÊ i>ÀÌ]ÊÜ ˆV ʓi>˜ÃʈÌʜ«iÀ>ÌiÃÊ ÜˆÌ ÊviÜiÀʓœÛˆ˜}Ê«>ÀÌÃÊ>˜`ÊÀiÃՏÌʈ˜Ê՘ÃÕÀ«>ÃÃi`ÊÀiˆ>LˆˆÌÞÊ>˜`Ê ÛˆÀÌÕ>ÞÊȏi˜Ìʜ«iÀ>̈œ˜°

>EEI;FHEL;DI9HEBBF;H?B; EF;B7D:-9HEBB /BJH7.;9>W8K?B:IED;IJ78B?I>;:I9HEBBJ;9>DEBE=O ?J?IIJ?BB7I9HEBB 7J>;7HJ M>?9>C;7DI?JEF;H7J;IM?J>

JEH;FB79; -JK:?;I>7L; ?CFHEL;CE?IJKH;I>;: CE?IJKH;H;CEL7B97F78 .>;.HH7TD SGKe?rB?iJeOsW-;H 9E?BB?<;7D:9EC<EHJ-JK:?;I>7L; E?IJKH;I>;: CEL7B97F787BIEI>EMDJ>7JJ>;I;7?H9E?B9E7J?D=I :?D=7D:J>;H;<EH;?CFHEL;7KD?JVI ?B?JOH;IKBJ?D=?D7CEH;9EC<EHJ78B;>EC ?;I?IOEKH7IIKH7D9;E<8EJ>C7N?CKC7? .HH7TD SGKe?rB?iJeOsW-;H?;I
-JOB?I>JME JED;BEEAM?J>J;NJKH;:8B79AFEM:;H9E7JF7?DJ 7D:IJ7?DB;IIIJ;;B<HEDJ799;IIF7D;BI &?<JEKJ>7D:B;I<EH<HEDJ799;IIF7D;BI EHHEI?ED7D:IJ7?DH;I?IJ7DJIJ7?DB;IIIJ;;B:H7?DF7DM?J>;NJH7 IBEF;:;I?=D;:?D
Heat Controller HTV SERIES — HT Series diagram (page 4)
Afb. 8 · HT Series

&' #% (&## &$'( ))&( 9>?;L;7=H;7J;HB;L;BEWFHEL?:;IIKF;H?EH 9EC7DXN;: 97F79?JO9ECFH;IIEHI8O ?D9EHFEH7J?D=7H;LEBKJ?ED7HOJME IJ;F:;I?=D 1?J>7KD?GK;F7HJ BE7:97F79?JOIJ;F IOIJ;CIM?J>/BJH7.;9>WC7?DJ7?DFH;9?I;

̜

fixed-capacity compressors by

9ECFH;IIEHI;9J?ED97D8;I;HL?9;:<HECJ>;<HEDJ

HFC-410A is a

Page 5 of the Heat Controller HTV SERIES user manual — I7 i˜Êˆ˜ÃÌ>i`ÊÜˆÌ Ê>ÊÌ iÀ“œÃÌ>ÌÊÌ >ÌÊ >ÃÊ>Êv>ՏÌÊ
Pagina 5 · klik om te vergroten
Pagina 5

.>;";D;I?I"-

HT Series

Heat Controller HTV SERIES — .>;";D;I?I"- diagram (page 5)
Afb. 9

EF;B7D:W#?=> <X9?;D9O-9HEBB ECFH;IIEHEH #?=> <X9?;D9O,EJ7HO ECFH;IIEH

Copeland UltraTech Two-Stage Scroll Compressor

)FJ?ED7B-J7J; )< .>; HJ" 07H?78B;-F;;: BEM;H'EJEH

>ÌiÃÌÊ/iV ˜œœ}އ iVÌÀœ˜ˆV>ÞÊVœ““ÕÌ>Ìi`]Ê *Àœ}À>““>Li]Ê6>Àˆ>LiÊ-«ii`Ê œÜiÀÊ œÌœÀ

Ó

E7J;: ?H E?B

iVÌÀœÊ`i«œÃˆÌˆœ˜ÊVœ>Ìi`Ê>ˆÀÊVœˆ

!KBBO$DIKB7J;: BEM;H-;9J?ED M?J>!KBBO $DIKB7J;: ECFH;IIEH-;9J?ED

$DJ;=H7J;:!?BJ;H,79AM?J>,;JKHD ?H K9J EDD;9J?ED

-BEF;: H7?D*7DM?J> ED:;DI7J; )L;HYEM-;DIEH 6

-œ«i`Ê-Ì>ˆ˜iÃÃÊ-ÌiiÊ À>ˆ˜Ê*>˜ÊÜˆÌ Ê œ˜`i˜Ã>ÌiÊ"ÛiÀyœÜÊ-i˜ÃœÀ

Î

{

/D?J*;H<EHC7D9;-;DJ?D;B KJEC7J?9 B;HJ-OIJ;C&;JI3EK%DEM$<.>;-OIJ;C $I(EJ,KDD?D= J*;7A*;H<EHC7D9; 7

1˜ˆÌÊ*iÀvœÀ“>˜ViÊ-i˜Ìˆ˜i\ÊÕ̜“>̈VÊ iÀÌÊ-ÞÃÌi“Ê iÌÃʜ“iœÜ˜iÀÊ ˜œÜÊvÊ / iÊ-ÞÃÌi“ÊÃÊ œÌÊ,՘˜ˆ˜}ÊÌÊ*i>ŽÊ *iÀvœÀ“>˜ViI

È

N9BKI?L; EK8B;-FH?D= D:"HECC;J ECFH;IIEH$IEB7J?ED!EH/BJH7 +K?;J)F;H7J?ED

œÕLiÊ-«Àˆ˜}ʘ`ÊÀœ““iÌÊ œ“«ÀiÃÜÀÊ Ãœ>̈œ˜ÊœÀÊ1ÌÀ>Ê+ՈiÌÊ"«iÀ>̈œ˜

™ or

£

!?L; 7IO &?<J EKJ-;HL?9; 99;II*7D;BI 9

ˆÛiÊ >ȏÞÊ,i“œÛ>LiÊ-iÀۈViÊVViÃÃÊ *>˜iÃ

Ç

Heat Controller HTV SERIES — EF;B7D:W#?=> <X9?;D9O-9HEBB ECFH;IIEHEH #?=> <X9?;D9O,EJ7HO ECFH;IIEH    diagram (page 5)
Afb. 10
Heat Controller HTV SERIES — EF;B7D:W#?=> <X9?;D9O-9HEBB ECFH;IIEHEH #?=> <X9?;D9O,EJ7HO ECFH;IIEH    diagram (page 5)
Afb. 11
Heat Controller HTV SERIES — EF;B7D:W#?=> <X9?;D9O-9HEBB ECFH;IIEHEH #?=> <X9?;D9O,EJ7HO ECFH;IIEH    diagram (page 5)
Afb. 12

I7 i˜Êˆ˜ÃÌ>i`ÊÜˆÌ Ê>ÊÌ iÀ“œÃÌ>ÌÊÌ >ÌÊ >ÃÊ>Êv>ՏÌÊ

Ó

Page 6 of the Heat Controller HTV SERIES user manual — HTV/HTD/HTH024
Pagina 6 · klik om te vergroten
Pagina 6

HT Series Ratings ARI/ASHRAE/ISO 13256-1 at EWT (Entering Water Temperature)

Heat Controller HTV SERIES — HT Series Ratings ARI/ASHRAE/ISO 13256-1 at EWT (Entering Water Temperature) diagram (page 6)
Afb. 13 · HT Series Ratings ARI/ASHRAE/ISO 13256-1 at EWT (Ent…

HTV/HTD/HTH024

HTV/HTD/HTH036

HTV/HTD/HTH048

HTV/HTD/HTH060

HTV/HTD/HTH070

Heating capacities based upon 68°F DB, 59°F WB entering air temperature.

Heat Controller HTV SERIES — HTV/HTD/HTH024 diagram (page 6)
Afb. 14
ModelVoltage CodeVoltageMin/Max VoltageCompressorFan Motor FLATotal Unit FLAMCAMax/Fuse QTYRLALRA 0241208/230-60/1197/254110.352.03.918.621.230 0361208/230-60/1197/254116.782.03.925.029.245 0481208/230-60/1197/254121.296.06.932.537.850 0601208/230-60/1197/254125.6118.06.936.943.360 0701208/230-60/1197/254127.2150.06.938.545.370

Min/Max Voltage of 197/254 HACR circuit breaker in USA only All fuses Class RK-5 Wire size based on 60°C copper conductor and Minimum Circuit Ampacity. Wire length based on one way measurement with 2% voltage drop

Page 7 of the Heat Controller HTV SERIES user manual — Vertical-HTV & Downflow-HTD
Pagina 7 · klik om te vergroten
Pagina 7

HT Physical Data

Heat Controller HTV SERIES — HT Physical Data diagram (page 7)
Afb. 15 · HT Physical Data

HT 024 HT 036 HT 048 HT 060 HT 070

Vertical-HTV & Downflow-HTD

Standard Filter - 2” Pleated HERV11, Quantity - in x in

(2) 14-24 (2) 14x30 (2) 10x30 (1) 16x30 (1) 16x30 (1) 12x30 (1) 20x30 (1) 20x30

1. 24 x 28 1 - 28 x 30 1 - 30 x 32 1 - 30 x 36 1 - 30 x 36
Horizontal-HTH Air Coil Dimensions (H x W), in18 x 3120 x 3520 x 4020 x 4520 x 45 Standard Filter - 2” Pleated MERV11, Quantity - in x in2 - 18 x 181 - 12 x 20 1 - 20 x 251 - 18 x 20 1 - 20 x 242 - 20 x 242 - 20 x 24 Weight - Operating, lbs266327416443443 Weight - Packaged, lbs276337426453453

All units have spring compressor mountings, TXV expansion devices, and 1/2” [12.7mm] & 3/4” [19.1mm] electrical knockouts.

Two-Stage Scroll · ECM Variable Speed

Page 8 of the Heat Controller HTV SERIES user manual — Dimensions – Vertical Upflow
Pagina 8 · klik om te vergroten
Pagina 8

Dimensions – Vertical Upflow

Heat Controller HTV SERIES — Dimensions – Vertical Upflow diagram (page 8)
Afb. 16 · Dimensions – Vertical Upflow
Vertical Upflow ModelOverall Cabinet A WidthB DepthC Height 002264in cm22.4 56.825.6 65.148.5 123.2 003386in cm25.4 64.530.6 77.850.5 128.3 004498in cm25.4 64.530.6 77.854.5 138.4 006640in cm25.4 64.530.6 77.858.5 148.6 007720in cm25.4 64.530.6 77.858.5 148.6
Vertical Upflow ModelWater Connections 12345 D InE OutF HWG ING HWG OutH CondensateLoop Water IPTHWG IPT 002264in cm2.1 5.210.0 25.413.9 35.216.9 42.97.8 19.81” Swivel1” Swivel 003386in cm3.4 8.610.8 27.515.6 39.718.9 47.97.8 19.81” Swivel1” Swivel 004498in cm3.4 8.610.8 27.515.6 39.718.9 47.97.8 19.81” Swivel1” Swivel 006640in cm3.4 8.610.8 27.515.6 39.718.9 47.97.8 19.81” Swivel1” Swivel 007720in cm3.4 8.610.8 27.515.6 39.718.9 47.97.8 19.71” Swivel1” Swivel
Vertical Upflow ModelElectrical Knockouts J 1/2”K 1/2”L 3/4” Low VoltageExternal PumpPower Supply 002264in cm3.6 9.26.1 15.68.6 21.9 003386in cm3.6 9.26.1 15.68.6 21.9 004498in cm3.6 9.26.1 15.68.6 21.9 006640in cm3.6 9.26.1 15.68.6 21.9 007720in cm3.6 9.26.1 15.68.6 21.9

Condensate is 3/4” PVC female glue socket and is switchable from front to side. Unit shipped with deluxe duct collar/filter rack extending from unit 3” [7.6cm] and is suitable for duct connection. Discharge flange is field installed.

2” (5.1 cm) and is suitable for duct connection.

Page 9 of the Heat Controller HTV SERIES user manual — Right Return Right View
Pagina 9 · klik om te vergroten
Pagina 9

Dimensions – Vertical Upflow

Heat Controller HTV SERIES — Dimensions – Vertical Upflow diagram (page 9)
Afb. 17 · Dimensions – Vertical Upflow
Vertical Upflow ModelDischarge Connection Duct Flange Installed (+/- 0.10 in, +/- 2.5mm)Return Connection Standard Deluxe Filter Rack (+/- 0.10 in, +/- 2.5mm) M Left ReturnNO Supply WidthP Supply DepthQ Right RetuenRS Return DepthT Return HeightU 002264in cm7.8 18.35.8 14.814.0 35.614.0 35.64.9 12.41.7 4.222.2 56.426.2 66.41.5 3.9 003386in cm6.4 16.16.3 16.018.0 45.718.0 45.75.3 13.52.1 5.427.1 68.926.1 66.41.5 3.9 004498in cm6.4 16.16.3 16.018.0 45.718.0 45.75.3 13.52.1 5.427.1 68.930.1 76.51.5 3.9 006640in cm6.4 16.16.3 16.018.0 45.718.0 45.75.3 13.52.1 5.427.1 68.934.1 86.71.5 3.9 007720in cm6.4 16.16.3 16.018.0 45.718.0 45.75.3 13.52.1 5.427.1 68.934.1 86.71.5 3.9

Field Installed Discharge Flange

Heat Controller HTV SERIES — Dimensions – Vertical Upflow diagram (page 9)
Afb. 18 · Dimensions – Vertical Upflow

Legend CAP=Control Access Panel CSP=Compressor Service Panel BSP=Blower Service Panel ASP=Alternate Service Panel

Service Access Left Rtn

Right Return Right View

Left Return Left View - Filter Rack Knife Edge

Front-View

- Filter Rack Knife Edge

2' (61cm) Optional · (right Opposite)

Page 10 of the Heat Controller HTV SERIES user manual — Dimensions – Vertical Downflow
Pagina 10 · klik om te vergroten
Pagina 10

Dimensions – Vertical Downflow

Heat Controller HTV SERIES — Dimensions – Vertical Downflow diagram (page 10)
Afb. 19 · Dimensions – Vertical Downflow
Vertical Downflow ModelOverall Cabinet A WidthB DepthC Height 002264in cm2222..44 5566..882255..66 6655..115522..45 113333..14 003386in cm2255..44 6644..553300..66 7777..885544..45 113388..24 004498in cm2255..44 6644..553300..66 7777..885588..45 114488..26 006640in cm2255..44 6644..553300..66 7777..886622..45 115588..58 007720in cm2255..44 6644..553300..66 7777..886622..45 115588..58
Vertical Downflow ModelWater Connections 12345 D InE OutF HWG ING HWG OutH CondensateLoop Water IPTHWG IPT 002264in cm1177..20 4432..79194.3.0 2335..6355..44 1133..7722..44 66..1133..66 89..921” Swivel1” Swivel 003386in cm1197..09 4485..051160..05 4206..4755..47 1134..7522..44 66..1133..66 89..921” Swivel1” Swivel 004498in cm1197..09 4485..051106..50 2460..7455..47 1134..7522..44 66..1133..66 89..921” Swivel1” Swivel 006640in cm1197..09 4485..051106..50 2460..7455..47 1134..7522..44 66..1133..66 89..921” Swivel1” Swivel 007720in cm1179..90 4458..501106..50 2460..7455..74 1143..5722..44 66..1133..66 89..921” Swivel1” Swivel
Vertical Downflow ModelElectrical Knockouts J 1/2”K 1/2”L 3/4” Low VoltageExternal PumpPower Supply 002264in cm1153..77 3393..90193.7.2 2343..15170.2.7 1277..82 003386in cm1173..77 4353..00195.7.2 2348..16172.2.7 1372..83 004498in cm1173..77 4353..00195.7.2 2348..16172.2.7 1372..83 006640in cm1173..77 4353..00195.7.2 2348..16172.2.7 1372..83 007720in cm1173..77 4353..00195..72 3284..61172.2.7 1372..83

Condensate is 3/4” PVC female glue socket and is switchable from front to side. Unit shipped with deluxe duct collar/filter rack extending from unit 3” [7.6cm] and is suitable for duct connection. Downflow unit does not have discharge flange, and is rated for zero clearance installation.

2” (5.1 cm) and is suitable for duct connection.

Page 11 of the Heat Controller HTV SERIES user manual — Dimensions – Vertical Downflow
Pagina 11 · klik om te vergroten
Pagina 11

Dimensions – Vertical Downflow

Heat Controller HTV SERIES — Dimensions – Vertical Downflow diagram (page 11)
Afb. 20 · Dimensions – Vertical Downflow
Vertical Downflow ModelDischarge Connection Duct Flange Installed (+/- 0.10 in, M O Left N Supply Su Return Width DeReturn Connection Standard Deluxe Filter Rack +/- 2.5mm) (+/- 0.10 in, +/- 2.5mm) O N Supply Su Width DeP Q pply Right R pth ReturnS Return DepthT Return HeightU i 002264 cn 66..71 m 1175..1488..42 190..94 99 2210..48 2265..43 2233..14 1100..98 11..87 ..05 2277..94 44..622222..32 5566..642266..22 6666..542211..21 5533..96 i 003386 cn 77..44 m 1188..7398..06 1133..16 1132 2222..91 3334..34 3332..39 1100..54 11..57 ..77 2276..55 34..822277..81 7608..692266..21 6666..542233..21 5598..04 i 004498 cn 77..44 m 1188..7398..06 1133..16 1123 2222..91 3334..34 3323..93 1100..54 11..75 ..77 2276..55 43..282277..18 6780..963300..12 7766..572233..12 5589..40 i 006640 cn 77..44 m 1188..7389..60 1133..16 1132 2222..19 3334..34 3332..39 1100..54 11..75 ..77 2276..55 43..282277..18 6780..962364..21 6866..572233..21 5598..04 i 007720 cn 77..44 m 1188..7398..06 1133..16 1123 2222..91 3334..34 3323..93 1100..54 11..75 ..77 2276..55 43..282277..18 6780..963344..12 8866..792233..21 5598..04

Legend CAP=Control Access Panel CSP=Compressor Service Panel BSP=Blower Service Panel ASP=Alternate Service Panel

P N B O Op Qlower eningA AirCoil Side B Right Return Dischar Floor Foot Print

Discharge Dimensions Discharge Dimensions

Page 12 of the Heat Controller HTV SERIES user manual — Dimensions – Vertical Downflow
Pagina 12 · klik om te vergroten
Pagina 12
Heat Controller HTV SERIES — Dimensions – Vertical Downflow diagram (page 12)
Afb. 21 · Dimensions – Vertical Downflow
Horizontal ModelOverall Cabinet A WidthB DepthC Height 024in cm22.4 56.862.2 158.019.3 48.9 036in cm25.4 64.571.2 180.821.3 54.0 048in cm25.4 64.576.2 193.521.3 54.0 060in cm25.4 64.581.2 206.221.3 54.0 070in cm25.4 64.581.2 206.221.3 54.0
Heat Controller HTV SERIES — Dimensions – Vertical Downflow diagram (page 12)
Afb. 22 · Dimensions – Vertical Downflow
Horizontal ModelWater Connections 12345 D InE OutF HWG ING HWG OutH CondensateLoop Water IPTHWG IPT 024in cm2.1 5.210.0 25.413.9 35.216.9 42.90.6 1.51” Swivel1” Swivel 036in cm3.4 8.610.8 27.515.6 39.718.9 47.90.6 1.51” Swivel1” Swivel 048in cm3.4 8.610.8 27.515.6 39.718.9 47.90.6 1.51” Swivel1” Swivel 060in cm3.4 8.610.8 27.515.6 39.718.9 47.90.6 1.51” Swivel1” Swivel 070in cm3.4 8.610.8 27.515.6 39.718.9 47.90.6 1.51” Swivel1” Swivel
Heat Controller HTV SERIES — Dimensions – Vertical Downflow diagram (page 12)
Afb. 23 · Dimensions – Vertical Downflow
Horizontal ModelElectrical Knockouts J 1/2”K 1/2”L 3/4” Low VoltageExternal PumpPower Supply 024in cm3.6 9.26.1 15.68.6 21.9 036in cm3.4 9.26.1 15.68.6 21.9 048in cm3.6 9.26.1 15.68.6 21.9 060in cm3.6 9.26.1 15.68.6 21.9 070in cm3.6 9.26.1 15.68.6 21.9

Condensate is 3/4” IPT. Unit shipped with deluxe duct collar/filter rack extending from unit 3” [7.6cm] and is suitable for duct connection. Discharge flange and hanger brackets are factory installed.

Page 13 of the Heat Controller HTV SERIES user manual — Discharge Connection Duct Flange Installed (+/- 0.10 in, +/- 2.5mm)
Pagina 13 · klik om te vergroten
Pagina 13
Heat Controller HTV SERIES — Discharge Connection Duct Flange Installed (+/- 0.10 in, +/- 2.5mm) diagram (page 13)
Afb. 24 · Discharge Connection Duct Flange Installed (+/- 0.10…

Discharge Connection Duct Flange Installed (+/- 0.10 in, +/- 2.5mm)

3.6 9.3 2.0 5.1 12.5 31.8 15.5 39.4 3.6 9.2 2.0 5.2 33.8 85.8 16.2 41.0 2.3 5.8 1.5 3.9

3.1 7.4 1.2 3.1 19.0 48.3 17.5 44.5 3.1 7.4 1.0 2.6 34.8 88.3 18.2 46.1 3.1 7.8 1.5 3.9

3.1 7.4 1.2 3.1 19.0 48.3 17.5 44.5 3.1 7.4 1.0 2.6 39.8 101.0 18.2 46.1 3.1 7.8 1.5 3.9

3.1 7.4 1.2 3.1 19.0 48.3 17.5 44.5 3.1 7.4 1.0 2.6 44.8 113.7 18.2 46.1 3.1 7.8 1.5 3.9

3.1 7.4 1.2 3.1 19.0 48.3 17.5 44.5 3.1 7.4 1.0 2.6 44.8 113.7 18.2 46.1 3.1 7.8 1.5 3.9

Heat Controller HTV SERIES — Discharge Connection Duct Flange Installed (+/- 0.10 in, +/- 2.5mm) diagram (page 13)
Afb. 25 · Discharge Connection Duct Flange Installed (+/- 0.10…

Legend CAP=Control Access Panel CSP=Compressor Service Panel BSP=Blower Service Panel ASP=Alternate Service Panel

Model X Y Z in. cm. in. cm. in. cm. 024 62.1 157.7 24.5 62.2 20.25 51.5 036 71.1 180.6 27.5 69.9 23.25 59.1 048 76.1 193.3 27.5 69.9 23.25 59.1 060 81.1 206 27.5 69.9 23.25 59.1

Left Return Left View - Filter Rack Knife Edge

Right Return Right View - Filter Rack Knife Edge

Page 14 of the Heat Controller HTV SERIES user manual — HTV024, HTD024 & HTH024 Part Load
Pagina 14 · klik om te vergroten
Pagina 14

PERFORMANCE DATA HT024 Part Load

/6äÓ{Ê*>ÀÌÊ œ>`

HTV024, HTD024 & HTH024 Part Load

HTV024 & HTD024 Part Load

Ratio KW HR EER HWG HC KW HE LAT COP HWG

20 7.0 4.5 10.3 11.4 1.06 7.8 88.8 3.14 1.9

3.5 1.2 2.8 21.6 13.5 0.62 0.57 23.6 37.8 - 13.3 1.10 9.6 92.1 3.54 2.0

30 5.8 2.8 6.5 21.9 13.5 0.62 0.56 23.8 38.7 - 13.9 1.11 10.2 93.0 3.69 2.0

7.0 4.1 9.4 21.9 13.5 0.62 0.56 23.8 39.3 - 14.1 1.11 10.3 93.3 3.74 1.9

3.5 1.1 2.5 22.4 14.5 0.65 0.64 24.6 34.8 - 15.7 1.17 11.8 96.0 3.95 2.0

40 5.8 2.6 5.9 22.6 14.6 0.65 0.60 24.6 37.4 - 16.4 1.17 12.4 97.1 4.11 2.0

7.0 3.6 8.4 22.6 14.6 0.64 0.60 24.7 37.8 - 16.6 1.17 12.6 97.4 4.16 2.0

3.5 1.0 2.3 22.2 14.9 0.67 0.73 24.7 30.3 0.7 17.9 1.19 13.9 99.7 4.41 2.1

50 5.8 2.4 5.5 22.4 14.9 0.67 0.68 24.7 33.0 0.6 18.7 1.19 14.6 100.9 4.58 2.1

7.0 3.4 7.9 22.5 14.9 0.67 0.67 24.7 33.7 0.6 18.9 1.20 14.8 101.2 4.63 2.0

3.5 1.0 2.2 21.4 14.8 0.69 0.84 24.2 25.6 1.1 20.0 1.23 15.8 103.1 4.77 2.2

2.1 1.9

1.9 2.0

60 5.8 2.2 5.1 21.9 15.0 0.68 0.78 24.5 28.2 1.0 20.8 1.23 16.6 104.4 4.94 2.2

7.0 3.2 7.4 22.0 15.0 0.68 0.76 24.6 29.0 0.9 21.0 1.24 16.8 104.8 4.99 2.1

3.5 0.9 2.1 20.2 14.3 0.71 0.96 23.5 21.1 1.4 22.0 1.24 17.7 106.3 5.18 2.3

70 5.8 2.1 4.8 20.9 14.6 0.70 0.89 23.9 23.5 1.3 22.8 1.25 18.5 107.7 5.35 2.3

7.0 3.0 7.0 21.1 14.7 0.70 0.87 24.0 24.2 1.2 23.1 1.25 18.8 108.1 5.39 2.3

3.5 0.8 1.9 18.9 13.7 0.73 1.09 22.6 17.3 1.8 23.9 1.26 19.6 109.5 5.55 2.4

2.2 2.3

80 5.8 2.0 4.5 19.6 14.0 0.72 1.02 23.1 19.2 1.6 24.8 1.27 20.5 111.0 5.71 2.4

7.0 2.8 6.5 19.8 14.1 0.71 1.00 23.2 19.8 1.5 25.1 1.27 20.7 111.4 5.76 2.4

3.5 0.8 1.8 17.6 13.2 0.75 1.24 21.8 14.3 2.2 25.8 1.28 21.4 112.6 5.88 2.6

90 5.8 1.9 4.3 18.1 13.4 0.74 1.17 22.1 15.6 1.9 26.8 1.30 22.3 114.3 6.05 2.6

7.0 2.7 6.2 18.4 13.5 0.73 1.14 22.3 16.1 1.8 27.1 1.30 22.6 114.8 6.10 2.5

3.5 0.8 1.8 16.2 12.5 0.78 1.40 20.9 11.6 2.4

100 5.8 1.8 4.1 16.7 12.7 0.76 1.33 21.2 12.6 2.2

7.0 2.6 6.0 16.9 12.8 0.76 1.31 21.3 12.9 2.0

3.5 0.7 1.7 15.1 12.3 0.81 1.57 20.5 9.6 2.7

110 5.8 1.7 4.0 15.4 12.2 0.79 1.51 20.6 10.2 2.5

7.0 2.5 5.7 15.6 12.3 0.79 1.49 20.6 10.5 2.2

3.5 0.7 1.6 14.2 12.2 0.86 1.82 20.4 7.8 3.0

120 5.8 1.7 3.9 14.5 12.1 0.84 1.71 20.3 8.4 2.7

7.0 2.4 5.5 14.6 12.1 0.83 1.69 20.3 8.6 2.4

†ARI/ASHRAE/ISO 13256-1 (WLHP applications) certified conditions are 86°F EWT, 80.6°F DB / 66.2°F WB Rev: 01/07/07JH

EAT in cooling and 68°F DB / 59°F WB EAT in heating.

All entering air conditions are 80°F DB and 67°F WB in cooling and 70°F DB in heating

All performance data is based upon the lower voltage of dual voltage rated units

See performance correction tables for operating conditions other than those listed above.

œÌi\ œÀʜ«iÀ>̈œ˜Êˆ˜ÊÌ iÊà >`i`Ê>Ài>ÊÜ i˜ÊÜ>ÌiÀʈÃÊÕÃi`ʈ˜ÊˆiÕʜvÊ>˜Ê >˜Ìˆ‡vÀiiâiÊ܏Ṏœ˜]ÊÌ iÊ 7/Ê i>ۈ˜}Ê7>ÌiÀÊ/i“«iÀ>ÌÕÀi®Ê“ÕÃÌÊ LiÊV>VՏ>Ìi`°ÊœÜʓÕÃÌÊLiʓ>ˆ˜Ì>ˆ˜i`Ê̜Ê>ʏiÛiÊÃÕV ÊÌ >ÌÊ Ì iÊ 7/ʈÃʓ>ˆ˜Ì>ˆ˜i`Ê>LœÛiÊ{äÂÊÜ i˜ÊÌ iÊ7ÎʍՓ«iÀʈÃʘœÌÊ Vˆ««i`°Ê/ ˆÃʈÃÊ`ÕiÊ̜ÊÌ iÊ«œÌi˜Ìˆ>ÊœvÊÌ iÊÀivÀˆ}iÀ>˜ÌÊÌi“«iÀ>‡ ÌÕÀiÊLiˆ˜}Ê>ÃʏœÜÊ>ÃÊÎÓÂÊÜˆÌ Ê{äÂÊ 7/]ÊÜ ˆV ʓ>Þʏi>`Ê̜Ê>Ê ˜ÕˆÃ>˜ViÊVÕ̜ÕÌÊ`ÕiÊ̜ÊÌ iÊ>V̈Û>̈œ˜ÊœvÊÌ iÊ œÜÊ/i“«iÀ>ÌÕÀiÊ *ÀœÌiV̈œ˜°Ê7ÎÊà œÕ`ʘiÛiÀÊLiÊVˆ««i`ÊvœÀÊÃÞÃÌi“ÃÊÜˆÌ œÕÌÊ >˜ÌˆvÀiiâi°

25< / JR[fX` L^KRLONN]#VRW^]N 4FC / NW]N[RWP`J]N[]NVYN[J]^[N 5 6?< / `J]N[fX`RWDBPJUUXW\#VRW^]N 40C / NW]N[RWPJR[]NVYN[J]^[N 5JQ[NWQNR] M[bK^UK#`N]K^UK 72 / JR[QNJ]RWPLJYJLR]b

Page 15 of the Heat Controller HTV SERIES user manual — HTV024 & HTD024 Full Load
Pagina 15 · klik om te vergroten
Pagina 15

PERFORMANCE DATA HT024 Full Load

HTV024 & HTD024 Full Load

HTV024, HTD024 & HTH024 Full Load

/6äÓ{ÊՏÊ œ>`

Ratio KW HR EER HWG HC KW HE LAT COP HWG

20 8.0 5.6 10.3 15.0 1.47 10.0 87.4 3.00 2.4

4.0 1.5 2.8 30.6 19.6 0.64 1.02 34.1 30.1 - 17.8 1.53 12.6 90.6 3.41 2.4

30 6.0 3.1 6.5 30.8 19.6 0.64 0.97 34.1 31.8 - 18.6 1.54 13.3 91.5 3.53 2.4

8.0 5.1 9.4 31.0 19.7 0.63 0.95 34.2 32.8 - 19.1 1.55 13.8 92.1 3.60 2.4

4.0 1.3 2.5 30.4 20.0 0.66 1.11 34.2 27.3 - 21.2 1.61 15.8 94.6 3.88 2.5

40 6.0 2.8 5.9 30.7 20.1 0.65 1.06 34.3 29.0 - 22.2 1.63 16.6 95.7 3.99 2.5

8.0 4.5 8.4 30.8 20.1 0.65 1.03 34.3 29.9 - 22.7 1.64 17.1 96.3 4.05 2.4

4.0 1.3 2.3 29.6 20.1 0.68 1.23 33.8 24.2 1.1 24.4 1.69 18.6 98.2 4.24 2.6

50 6.0 2.6 5.5 30.1 20.2 0.67 1.16 34.1 25.9 1.0 25.4 1.71 19.5 99.4 4.35 2.6

8.0 4.3 7.9 30.3 20.2 0.67 1.13 34.2 26.8 0.9 25.9 1.73 20.0 100.0 4.40 2.6

4.0 1.2 2.2 28.4 19.7 0.69 1.35 33.0 21.0 1.5 27.2 1.76 21.2 101.5 4.53 2.8

2.2 2.0

2.8 2.9

60 6.0 2.5 5.1 29.1 19.9 0.68 1.28 33.5 22.8 1.3 28.3 1.80 22.2 102.7 4.62 2.8

8.0 4.0 7.4 29.4 20.0 0.68 1.24 33.7 23.6 1.1 28.8 1.81 22.7 103.4 4.66 2.7

4.0 1.1 2.1 27.0 19.0 0.71 1.50 32.1 18.0 2.0 29.9 1.84 23.6 104.6 4.75 3.7

70 6.0 2.3 4.8 27.8 19.4 0.70 1.42 32.6 19.6 1.8 31.0 1.88 24.6 105.8 4.83 3.0

8.0 3.8 7.0 28.2 19.6 0.69 1.38 32.9 20.5 1.5 31.5 1.89 25.0 106.5 4.87 3.0

4.0 1.0 1.9 25.4 18.3 0.72 1.66 31.0 15.3 2.6 32.3 1.92 25.8 107.4 4.93 3.4

3.4 3.6

80 6.0 2.2 4.5 26.2 18.7 0.71 1.57 31.6 16.7 2.2 33.5 1.96 26.8 108.7 5.01 3.3

8.0 3.5 6.5 26.7 18.9 0.71 1.53 31.9 17.5 1.9 34.0 1.98 27.3 109.4 5.04 3.3

4.0 1.0 1.8 23.7 17.5 0.74 1.84 30.0 12.9 3.2 34.7 2.00 27.9 110.2 5.09 3.6

90 6.0 2.1 4.3 24.5 17.9 0.73 1.75 30.5 14.1 2.8 35.9 2.04 28.9 111.5 5.16 3.5

8.0 3.4 6.2 25.0 18.1 0.72 1.70 30.8 14.7 2.3 36.5 2.06 29.4 112.2 5.19 3.5

4.0 1.0 1.8 22.0 16.7 0.76 2.05 29.0 10.7 4.0

100 6.0 2.0 4.1 22.8 17.1 0.75 1.95 29.5 11.7 3.5

8.0 3.2 6.0 23.3 17.3 0.74 1.89 29.7 12.3 2.8

4.0 0.9 1.7 20.5 16.0 0.78 2.29 28.3 8.9 4.8

110 6.0 1.9 4.0 21.2 16.3 0.77 2.17 28.6 9.8 4.1

8.0 3.1 5.7 21.6 16.5 0.76 2.11 28.8 10.2 3.3

4.0 0.9 1.6 19.1 15.5 0.81 2.55 27.8 7.5 5.7

120 6.0 1.8 3.9 19.7 15.7 0.80 2.43 28.0 8.1 4.8

8.0 3.0 5.5 20.0 15.8 0.79 2.36 28.1 8.5 4.0

†ARI/ASHRAE/ISO 13256-1 (WLHP applications) certified conditions are 86°F EWT, 80.6°F DB / 66.2°F WB Rev: 01/07/07JH

EAT in cooling and 68°F DB / 59°F WB EAT in heating.

All entering air conditions are 80°F DB and 67°F WB in cooling and 70°F DB in heating

All performance data is based upon the lower voltage of dual voltage rated units

See performance correction tables for operating conditions other than those listed above.

œÌi\ œÀʜ«iÀ>̈œ˜Êˆ˜ÊÌ iÊà >`i`Ê>Ài>ÊÜ i˜ÊÜ>ÌiÀʈÃÊÕÃi`ʈ˜ÊˆiÕʜvÊ>˜Ê >˜Ìˆ‡vÀiiâiÊ܏Ṏœ˜]ÊÌ iÊ 7/Ê i>ۈ˜}Ê7>ÌiÀÊ/i“«iÀ>ÌÕÀi®Ê“ÕÃÌÊ LiÊV>VՏ>Ìi`°ÊœÜʓÕÃÌÊLiʓ>ˆ˜Ì>ˆ˜i`Ê̜Ê>ʏiÛiÊÃÕV ÊÌ >ÌÊ Ì iÊ 7/ʈÃʓ>ˆ˜Ì>ˆ˜i`Ê>LœÛiÊ{äÂÊÜ i˜ÊÌ iÊ7ÎʍՓ«iÀʈÃʘœÌÊ Vˆ««i`°Ê/ ˆÃʈÃÊ`ÕiÊ̜ÊÌ iÊ«œÌi˜Ìˆ>ÊœvÊÌ iÊÀivÀˆ}iÀ>˜ÌÊÌi“«iÀ>‡ ÌÕÀiÊLiˆ˜}Ê>ÃʏœÜÊ>ÃÊÎÓÂÊÜˆÌ Ê{äÂÊ 7/]ÊÜ ˆV ʓ>Þʏi>`Ê̜Ê>Ê ˜ÕˆÃ>˜ViÊVÕ̜ÕÌÊ`ÕiÊ̜ÊÌ iÊ>V̈Û>̈œ˜ÊœvÊÌ iÊ œÜÊ/i“«iÀ>ÌÕÀiÊ *ÀœÌiV̈œ˜°Ê7ÎÊà œÕ`ʘiÛiÀÊLiÊVˆ««i`ÊvœÀÊÃÞÃÌi“ÃÊÜˆÌ œÕÌÊ >˜ÌˆvÀiiâi°

25< / JR[fX` L^KRLONN]#VRW^]N 4FC / NW]N[RWP`J]N[]NVYN[J]^[N 5 6?< / `J]N[fX`RWDBPJUUXW\#VRW^]N 40C / NW]N[RWPJR[]NVYN[J]^[N 5JQ[NWQNR] M[bK^UK#`N]K^UK 72 / JR[QNJ]RWPLJYJLR]b

Page 16 of the Heat Controller HTV SERIES user manual — HTV036 & HTD036 Part Load
Pagina 16 · klik om te vergroten
Pagina 16

PERFORMANCE DATA HT036 Part Load

/6äÎÈÊ*>ÀÌÊ œ>`

HTV036 & HTD036 Part Load

HTV036, HTD036 & HTH036 Part Load

Ratio KW HR EER HWG HC KW HE LAT COP HWG

20 8.0 4.7 10.9 17.3 1.46 12.3 90.0 3.48 2.4

4.0 1.2 2.8 29.8 18.9 0.63 0.79 32.5 37.7 - 19.1 1.51 14.0 92.1 3.71 2.4

30 6.0 2.6 6.1 30.1 18.9 0.63 0.75 32.7 40.3 - 19.8 1.51 14.6 92.9 3.84 2.4

8.0 4.5 10.4 30.3 19.0 0.63 0.73 32.8 41.6 - 20.1 1.51 15.0 93.3 3.91 2.4

4.0 1.1 2.5 30.6 20.4 0.67 0.90 33.6 34.0 - 21.8 1.56 16.5 95.2 4.08 2.5

40 6.0 2.6 5.9 30.8 20.4 0.66 0.84 33.7 36.9 - 22.6 1.57 17.3 96.2 4.22 2.5

8.0 4.4 10.2 31.0 20.5 0.66 0.81 33.7 38.3 - 23.1 1.58 17.7 96.7 4.29 2.4

4.0 1.0 2.2 30.3 21.1 0.70 1.03 33.8 29.4 0.8 24.6 1.64 19.0 98.5 4.40 2.6

50 6.0 2.5 5.7 30.7 21.2 0.69 0.95 33.9 32.2 0.7 25.6 1.64 20.0 99.6 4.57 2.6

8.0 4.2 9.7 30.9 21.2 0.69 0.92 34.0 33.7 0.7 26.2 1.65 20.5 100.3 4.64 2.5

4.0 0.9 2.0 29.2 21.2 0.72 1.19 33.3 24.6 1.3 27.5 1.66 21.9 101.9 4.87 2.7

2.5 2.2

2.6 2.7

60 6.0 2.4 5.5 29.9 21.3 0.71 1.09 33.7 27.3 1.2 28.7 1.66 23.0 103.2 5.06 2.7

8.0 4.1 9.5 30.2 21.4 0.71 1.05 33.8 28.7 1.1 29.4 1.67 23.7 104.0 5.16 2.6

4.0 0.8 1.8 27.7 20.6 0.74 1.36 32.3 20.4 1.8 30.5 1.68 24.8 105.3 5.34 2.8

70 6.0 2.3 5.3 28.6 20.9 0.73 1.26 32.9 22.7 1.7 32.0 1.68 26.2 107.0 5.56 2.8

8.0 4.0 9.2 29.0 21.1 0.73 1.21 33.1 24.0 1.5 32.7 1.69 27.0 107.9 5.68 2.8

4.0 0.7 1.7 26.0 19.8 0.76 1.56 31.3 16.7 2.3 33.7 1.70 27.9 109.0 5.82 3.0

3.1 3.2

80 6.0 2.3 5.2 26.9 20.2 0.75 1.45 31.9 18.6 2.1 35.3 1.71 29.5 110.9 6.06 3.0

8.0 3.9 9.0 27.4 20.4 0.75 1.39 32.2 19.7 1.9 36.2 1.71 30.4 111.9 6.20 2.9

4.0 0.6 1.5 24.2 19.0 0.79 1.78 30.3 13.6 2.7 36.9 1.72 31.0 112.7 6.30 3.2

90 6.0 2.1 4.9 25.1 19.4 0.77 1.66 30.8 15.1 2.5 38.8 1.73 32.9 114.9 6.57 3.2

8.0 3.7 8.5 25.6 19.6 0.77 1.60 31.1 16.0 2.2 39.9 1.74 33.9 116.1 6.73 3.1

4.0 0.6 1.4 22.7 18.5 0.81 2.02 29.6 11.2 3.1

100 6.0 2.1 4.8 23.4 18.7 0.80 1.89 29.9 12.4 2.8

8.0 3.6 8.3 23.8 18.9 0.79 1.83 30.1 13.0 2.5

4.0 0.6 1.3 21.5 18.3 0.85 2.30 29.3 9.4 3.5

110 6.0 2.0 4.6 22.0 18.3 0.83 2.16 29.4 10.2 3.1

8.0 3.4 7.9 22.3 18.4 0.82 2.09 29.5 10.7 2.8

4.0 0.5 1.2 20.7 18.0 0.87 2.57 29.4 8.1 3.8

120 6.0 1.9 4.5 21.1 18.3 0.87 2.44 29.5 8.6 3.4

8.0 3.3 7.7 21.3 18.4 0.86 2.40 29.5 8.9 3.1

†ARI/ASHRAE/ISO 13256-1 (WLHP applications) certified conditions are 86°F EWT, 80.6°F DB / 66.2°F WB Rev: 01/07/07JH

EAT in cooling and 68°F DB / 59°F WB EAT in heating.

All entering air conditions are 80°F DB and 67°F WB in cooling and 70°F DB in heating

All performance data is based upon the lower voltage of dual voltage rated units

See performance correction tables for operating conditions other than those listed above.

œÌi\ œÀʜ«iÀ>̈œ˜Êˆ˜ÊÌ iÊà >`i`Ê>Ài>ÊÜ i˜ÊÜ>ÌiÀʈÃÊÕÃi`ʈ˜ÊˆiÕʜvÊ>˜ >˜Ìˆ‡vÀiiâiÊ܏Ṏœ˜]ÊÌ iÊ 7/Ê i>ۈ˜}Ê7>ÌiÀÊ/i“«iÀ>ÌÕÀi®Ê“ÕÃÌ LiÊV>VՏ>Ìi`°ÊœÜʓÕÃÌÊLiʓ>ˆ˜Ì>ˆ˜i`Ê̜Ê>ʏiÛiÊÃÕV ÊÌ >ÌÊ Ì iÊ 7/ʈÃʓ>ˆ˜Ì>ˆ˜i`Ê>LœÛiÊ{äÂÊÜ i˜ÊÌ iÊ7ÎʍՓ«iÀʈÃʘœÌÊ Vˆ««i`°Ê/ ˆÃʈÃÊ`ÕiÊ̜ÊÌ iÊ«œÌi˜Ìˆ>ÊœvÊÌ iÊÀivÀˆ}iÀ>˜ÌÊÌi“«iÀ>‡ ÌÕÀiÊLiˆ˜}Ê>ÃʏœÜÊ>ÃÊÎÓÂÊÜˆÌ Ê{äÂÊ 7/]ÊÜ ˆV ʓ>Þʏi>`Ê̜Ê>Ê ˜ÕˆÃ>˜ViÊVÕ̜ÕÌÊ`ÕiÊ̜ÊÌ iÊ>V̈Û>̈œ˜ÊœvÊÌ iÊ œÜÊ/i“«iÀ>ÌÕÀiÊ *ÀœÌiV̈œ˜°Ê7ÎÊà œÕ`ʘiÛiÀÊLiÊVˆ««i`ÊvœÀÊÃÞÃÌi“ÃÊÜˆÌ œÕÌÊ >˜ÌˆvÀiiâi°

25< / JR[fX` L^KRLONN]#VRW^]N 4FC / NW]N[RWP`J]N[]NVYN[J]^[N 5 6?< / `J]N[fX`RWDBPJUUXW\#VRW^]N 40C / NW]N[RWPJR[]NVYN[J]^[N 5JQ[NWQNR] M[bK^UK#`N]K^UK 72 / JR[QNJ]RWPLJYJLR]b

Page 17 of the Heat Controller HTV SERIES user manual — HTV036, HTD036 & HTH036 Full Load
Pagina 17 · klik om te vergroten
Pagina 17

PERFORMANCE DATA HT036 Full Load

/6äÎÈÊՏÊ œ>`

HTV036, HTD036 & HTH036 Full Load

HTV036 & HTD036 Full Load

Ratio KW HR EER HWG HC KW HE LAT COP HWG

20 9.0 5.9 13.7 26.1 2.30 18.2 90.1 3.32 2.9

4.5 1.7 3.9 43.9 30.7 0.70 1.61 49.4 27.2 - 28.3 2.34 20.3 91.9 3.54 3.0

30 6.8 3.3 7.6 44.1 30.7 0.70 1.51 49.3 29.3 - 29.6 2.37 21.5 92.9 3.66 3.0

9.0 5.7 13.1 44.3 30.7 0.69 1.45 49.2 30.4 - 30.3 2.38 22.2 93.4 3.73 2.9

4.5 1.5 3.5 43.2 30.7 0.71 1.77 49.2 24.4 - 32.3 2.43 24.0 94.9 3.90 3.1

40 6.8 3.2 7.3 43.8 30.8 0.70 1.66 49.4 26.4 - 33.8 2.46 25.4 96.1 4.03 3.0

9.0 5.4 12.5 44.0 30.9 0.70 1.60 49.4 27.5 - 34.7 2.48 26.2 96.8 4.10 3.0

4.5 1.3 3.1 41.9 30.3 0.72 1.93 48.5 21.7 1.4 36.3 2.52 27.7 98.0 4.22 3.3

50 6.8 3.1 7.1 42.9 30.6 0.71 1.81 49.0 23.7 1.2 38.1 2.56 29.4 99.4 4.36 3.3

9.0 5.2 12.0 43.3 30.7 0.71 1.75 49.2 24.7 1.0 39.2 2.59 30.3 100.2 4.43 3.1

4.5 1.2 2.8 40.4 29.6 0.73 2.11 47.6 19.1 1.9 40.4 2.62 31.5 101.2 4.52 3.6

2.6 2.3

4.1 4.2

60 6.8 2.9 6.8 41.5 30.1 0.72 1.98 48.3 20.9 1.6 42.6 2.68 33.4 102.8 4.65 3.5

9.0 5.0 11.6 42.0 30.3 0.72 1.92 48.6 21.9 1.4 43.8 2.71 34.5 103.8 4.73 3.5

4.5 1.1 2.5 38.5 28.7 0.75 2.32 46.4 16.6 2.5 44.7 2.74 35.3 104.5 4.78 3.9

70 6.8 2.9 6.6 39.8 29.3 0.74 2.17 47.2 18.3 2.2 47.2 2.81 37.6 106.4 4.91 3.8

9.0 4.8 11.0 40.4 29.6 0.73 2.10 47.6 19.2 1.8 48.5 2.86 38.8 107.4 4.98 3.8

4.5 1.0 2.3 36.5 27.7 0.76 2.55 45.2 14.3 3.4 49.0 2.87 39.2 107.8 5.01 4.3

5.0 5.2

80 6.8 2.8 6.5 37.9 28.4 0.75 2.39 46.0 15.9 2.9 51.9 2.96 41.8 110.0 5.13 4.2

9.0 4.5 10.4 38.6 28.7 0.75 2.31 46.5 16.7 2.3 53.5 3.01 43.2 111.3 5.20 4.1

4.5 0.9 2.1 34.5 26.7 0.78 2.81 44.1 12.2 4.2 53.6 3.02 43.3 111.3 5.20 4.7

90 6.8 2.6 6.1 35.8 27.4 0.76 2.63 44.8 13.6 3.6 56.8 3.13 46.1 113.8 5.32 4.7

9.0 4.4 10.2 36.5 27.7 0.76 2.55 45.2 14.3 3.0 58.6 3.19 47.7 115.2 5.38 4.6

4.5 0.8 1.9 32.4 25.7 0.79 3.12 43.0 10.4 5.1

100 6.8 2.6 6.0 33.7 26.3 0.78 2.92 43.7 11.5 4.4

9.0 4.2 9.7 34.4 26.7 0.78 2.82 44.0 12.2 3.6

4.5 0.8 1.8 30.4 24.7 0.81 3.49 42.3 8.7 6.1

110 6.8 2.5 5.8 31.6 25.3 0.80 3.25 42.7 9.7 5.2

9.0 4.0 9.2 32.3 25.6 0.79 3.14 43.0 10.3 4.3

4.5 0.7 1.6 28.6 23.8 0.83 3.91 41.9 7.3 7.3

8.2 7.9

120 6.8 2.5 5.8 29.7 24.3 0.82 3.64 42.1 8.2 6.2

9.0 3.8 8.8 30.2 24.6 0.81 3.51 42.2 8.6 5.1

†ARI/ASHRAE/ISO 13256-1 (WLHP applications) certified conditions are 86°F EWT, 80.6°F DB / 66.2°F WB Rev: 01/07/07JH

EAT in cooling and 68°F DB / 59°F WB EAT in heating.

All entering air conditions are 80°F DB and 67°F WB in cooling and 70°F DB in heating

All performance data is based upon the lower voltage of dual voltage rated units

See performance correction tables for operating conditions other than those listed above.

œÌi\ œÀʜ«iÀ>̈œ˜Êˆ˜ÊÌ iÊà >`i`Ê>Ài>ÊÜ i˜ÊÜ>ÌiÀʈÃÊÕÃi`ʈ˜ÊˆiÕʜvÊ>˜Ê >˜Ìˆ‡vÀiiâiÊ܏Ṏœ˜]ÊÌ iÊ 7/Ê i>ۈ˜}Ê7>ÌiÀÊ/i“«iÀ>ÌÕÀi®Ê“ÕÃÌÊ LiÊV>VՏ>Ìi`°ÊœÜʓÕÃÌÊLiʓ>ˆ˜Ì>ˆ˜i`Ê̜Ê>ʏiÛiÊÃÕV ÊÌ >ÌÊ Ì iÊ 7/ʈÃʓ>ˆ˜Ì>ˆ˜i`Ê>LœÛiÊ{äÂÊÜ i˜ÊÌ iÊ7ÎʍՓ«iÀʈÃʘœÌÊ Vˆ««i`°Ê/ ˆÃʈÃÊ`ÕiÊ̜ÊÌ iÊ«œÌi˜Ìˆ>ÊœvÊÌ iÊÀivÀˆ}iÀ>˜ÌÊÌi“«iÀ>‡ ÌÕÀiÊLiˆ˜}Ê>ÃʏœÜÊ>ÃÊÎÓÂÊÜˆÌ Ê{äÂÊ 7/]ÊÜ ˆV ʓ>Þʏi>`Ê̜Ê>Ê ˜ÕˆÃ>˜ViÊVÕ̜ÕÌÊ`ÕiÊ̜ÊÌ iÊ>V̈Û>̈œ˜ÊœvÊÌ iÊ œÜÊ/i“«iÀ>ÌÕÀiÊ *ÀœÌiV̈œ˜°Ê7ÎÊà œÕ`ʘiÛiÀÊLiÊVˆ««i`ÊvœÀÊÃÞÃÌi“ÃÊÜˆÌ œÕÌÊ >˜ÌˆvÀiiâi°

25< / JR[fX` L^KRLONN]#VRW^]N 4FC / NW]N[RWP`J]N[]NVYN[J]^[N 5 6?< / `J]N[fX`RWDBPJUUXW\#VRW^]N 40C / NW]N[RWPJR[]NVYN[J]^[N 5JQ[NWQNR] M[bK^UK#`N]K^UK 72 / JR[QNJ]RWPLJYJLR]b

Page 18 of the Heat Controller HTV SERIES user manual — HTV048 & HTD048 Part Load
Pagina 18 · klik om te vergroten
Pagina 18

PERFORMANCE DATA HT048 Part Load

/6ä{nÊ*>ÀÌÊ œ>`

HTV048 & HTD048 Part Load

HTV048 HTD048 & HTH048 Part Load

Ratio KW HR EER HWG HC KW HE LAT COP HWG

20 11.0 4.0 9.3 22.7 2.14 15.4 90.0 3.12 3.3

5.5 1.1 2.5 37.9 23.6 0.62 1.19 42.0 31.9 - 25.1 2.17 17.7 92.2 3.39 3.4

30 8.3 2.2 5.2 38.1 23.7 0.62 1.12 42.0 34.0 - 26.0 2.18 18.6 93.0 3.49 3.3

11.0 3.9 8.9 38.4 23.6 0.62 1.09 42.1 35.2 - 26.5 2.19 19.1 93.4 3.55 3.3

5.5 1.0 2.3 40.1 25.8 0.64 1.35 44.8 29.7 - 29.0 2.21 21.5 95.6 3.84 3.5

40 8.3 2.1 5.0 40.5 25.8 0.64 1.27 44.8 31.9 - 30.3 2.23 22.7 96.7 3.99 3.4

11.0 3.7 8.6 40.6 25.8 0.64 1.24 44.8 32.7 - 31.0 2.23 23.3 97.3 4.06 3.4

5.5 0.9 2.1 40.1 26.4 0.66 1.48 45.2 27.2 0.9 33.4 2.25 25.7 99.4 4.34 3.6

50 8.3 2.1 4.9 40.5 26.4 0.65 1.40 45.2 28.9 0.8 34.9 2.27 27.2 100.8 4.52 3.5

11.0 3.6 8.3 40.6 26.4 0.65 1.39 45.3 29.2 0.8 35.8 2.27 28.0 101.6 4.62 3.5

5.5 0.9 2.0 39.3 26.7 0.68 1.71 45.2 23.0 1.6 37.9 2.29 30.1 103.4 4.85 3.7

3.5 3.2

60 8.3 2.0 4.7 40.0 26.8 0.67 1.60 45.5 25.0 1.4 39.8 2.31 31.9 105.1 5.06 3.7

11.0 3.5 8.1 40.3 26.8 0.67 1.55 45.5 26.0 1.3 40.8 2.31 32.9 106.0 5.17 3.7

5.5 0.8 1.8 37.6 26.1 0.70 1.92 44.1 19.6 2.2 42.5 2.33 34.6 107.5 5.35 3.8

70 8.3 2.0 4.6 38.6 26.5 0.69 1.80 44.8 21.5 2.0 44.7 2.35 36.6 109.4 5.57 3.8

11.0 3.2 7.5 39.1 26.6 0.68 1.74 45.0 22.4 1.8 45.8 2.36 37.8 110.4 5.69 3.8

5.5 0.7 1.7 35.3 25.3 0.71 2.15 42.7 16.4 2.8 47.1 2.37 39.0 111.5 5.81 4.1

3.7 3.8

80 8.3 1.9 4.5 36.6 25.7 0.70 2.02 43.5 18.1 2.5 49.4 2.40 41.2 113.5 6.02 4.0

11.0 3.2 7.3 37.2 26.0 0.70 1.96 43.9 19.0 2.3 50.6 2.42 42.3 114.6 6.13 4.0

5.5 0.7 1.6 32.8 24.3 0.74 2.41 41.1 13.6 3.3 51.4 2.43 43.1 115.3 6.20 4.4

90 8.3 1.8 4.2 34.1 24.8 0.73 2.27 41.9 15.0 3.0 53.7 2.47 45.3 117.4 6.38 4.3

11.0 3.1 7.2 34.8 25.0 0.72 2.20 42.3 15.8 2.7 54.9 2.49 46.4 118.4 6.47 4.3

5.5 0.6 1.5 30.3 23.3 0.77 2.70 39.6 11.2 3.8

100 8.3 1.8 4.1 31.6 23.8 0.75 2.55 40.3 12.4 3.5

11.0 2.9 6.8 32.2 24.0 0.75 2.48 40.7 13.0 3.1

5.5 0.6 1.5 28.0 22.6 0.81 3.03 38.4 9.3 4.3

110 8.3 1.7 4.0 29.1 22.9 0.79 2.87 38.9 10.2 3.9

11.0 2.9 6.6 29.7 23.1 0.78 2.79 39.2 10.7 3.5

5.5 0.6 1.4 26.2 22.3 0.85 3.41 37.8 7.7 4.7

10.6 10.2

120 8.3 1.6 3.8 27.0 22.4 0.83 3.22 38.0 8.4 4.2

11.0 2.7 6.3 27.4 22.4 0.82 3.14 38.1 8.8 3.8

†ARI/ASHRAE/ISO 13256-1 (WLHP applications) certified conditions are 86°F EWT, 80.6°F DB / 66.2°F WB Rev: 01/07/07JH

EAT in cooling and 68°F DB / 59°F WB EAT in heating.

All entering air conditions are 80°F DB and 67°F WB in cooling and 70°F DB in heating

All performance data is based upon the lower voltage of dual voltage rated units

See performance correction tables for operating conditions other than those listed above.

œÌi\ œÀʜ«iÀ>̈œ˜Êˆ˜ÊÌ iÊà >`i`Ê>Ài>ÊÜ i˜ÊÜ>ÌiÀʈÃÊÕÃi`ʈ˜ÊˆiÕʜvÊ> >˜Ìˆ‡vÀiiâiÊ܏Ṏœ˜]ÊÌ iÊ 7/Ê i>ۈ˜}Ê7>ÌiÀÊ/i“«iÀ>ÌÕÀi®Ê“Õà LiÊV>VՏ>Ìi`°ÊœÜʓÕÃÌÊLiʓ>ˆ˜Ì>ˆ˜i`Ê̜Ê>ʏiÛiÊÃÕV ÊÌ >ÌÊ Ì iÊ 7/ʈÃʓ>ˆ˜Ì>ˆ˜i`Ê>LœÛiÊ{äÂÊÜ i˜ÊÌ iÊ7ÎʍՓ«iÀʈÃʘœÌÊ Vˆ««i`°Ê/ ˆÃʈÃÊ`ÕiÊ̜ÊÌ iÊ«œÌi˜Ìˆ>ÊœvÊÌ iÊÀivÀˆ}iÀ>˜ÌÊÌi“«iÀ>‡ ÌÕÀiÊLiˆ˜}Ê>ÃʏœÜÊ>ÃÊÎÓÂÊÜˆÌ Ê{äÂÊ 7/]ÊÜ ˆV ʓ>Þʏi>`Ê̜Ê>Ê ˜ÕˆÃ>˜ViÊVÕ̜ÕÌÊ`ÕiÊ̜ÊÌ iÊ>V̈Û>̈œ˜ÊœvÊÌ iÊ œÜÊ/i“«iÀ>ÌÕÀiÊ *ÀœÌiV̈œ˜°Ê7ÎÊà œÕ`ʘiÛiÀÊLiÊVˆ««i`ÊvœÀÊÃÞÃÌi“ÃÊÜˆÌ œÕÌÊ >˜ÌˆvÀiiâi°

25< / JR[fX` L^KRLONN]#VRW^]N 4FC / NW]N[RWP`J]N[]NVYN[J]^[N 5 6?< / `J]N[fX`RWDBPJUUXW\#VRW^]N 40C / NW]N[RWPJR[]NVYN[J]^[N 5JQ[NWQNR] M[bK^UK#`N]K^UK 72 / JR[QNJ]RWPLJYJLR]b

Page 19 of the Heat Controller HTV SERIES user manual — HTV048 & HTD048 Full Load
Pagina 19 · klik om te vergroten
Pagina 19

PERFORMANCE DATA HT048 Full Load

/6ä{nÊՏÊ œ>`

HTV048 & HTD048 Full Load

HTV048, HTD048 & HTH048 Full Load

Ratio KW HR EER HWG HC KW HE LAT COP HWG

20 12.0 4.8 11.0 32.1 3.09 21.6 88.6 3.04 3.9

6.0 1.3 2.9 57.6 37.1 0.64 2.24 65.3 25.7 - 35.3 3.12 24.6 90.4 3.31 4.1

30 9.0 2.6 6.1 58.1 37.2 0.64 2.12 65.3 27.5 - 36.9 3.16 26.1 91.3 3.41 4.0

12.0 4.5 10.5 58.4 37.2 0.64 2.05 65.4 28.5 - 37.7 3.19 26.9 91.8 3.47 4.0

6.0 1.2 2.7 57.3 38.1 0.67 2.44 65.7 23.5 - 40.6 3.17 29.8 93.5 3.76 4.2

40 9.0 2.6 5.9 57.9 38.2 0.66 2.31 65.8 25.1 - 42.6 3.21 31.7 94.7 3.89 4.1

12.0 4.4 10.1 58.2 38.2 0.66 2.24 65.8 26.0 - 43.8 3.23 32.7 95.3 3.97 4.1

6.0 1.1 2.5 56.0 38.5 0.69 2.64 65.0 21.2 2.0 46.3 3.16 35.5 96.8 4.29 4.4

50 9.0 2.5 5.7 57.1 38.6 0.68 2.50 65.7 22.9 1.7 48.7 3.22 37.7 98.2 4.43 4.3

12.0 4.2 9.6 57.5 38.7 0.67 2.43 65.8 23.7 1.4 50.1 3.26 39.0 99.0 4.51 4.3

6.0 1.0 2.3 53.9 37.8 0.70 2.85 63.6 18.9 2.9 52.1 3.31 40.8 100.2 4.62 4.7

3.7 3.3

60 9.0 2.4 5.5 55.5 38.3 0.69 2.70 64.7 20.5 2.5 55.1 3.38 43.5 101.9 4.77 4.6

12.0 4.0 9.2 56.1 38.5 0.69 2.63 65.1 21.4 2.1 56.7 3.42 45.0 102.8 4.85 4.6

6.0 1.0 2.2 51.3 36.7 0.72 3.09 61.8 16.6 4.0 58.1 3.46 46.3 103.6 4.92 5.1

5.0 4.5

70 9.0 2.3 5.4 53.2 37.5 0.70 2.92 63.1 18.2 3.3 61.5 3.55 49.4 105.6 5.08 5.1

12.0 3.8 8.8 54.0 37.8 0.70 2.84 63.7 19.0 2.8 63.4 3.61 51.1 106.7 5.16 5.0

6.0 0.9 2.1 48.4 35.4 0.73 3.35 59.8 14.4 5.0 64.3 3.63 51.9 107.2 5.19 5.7

6.1 6.3

80 9.0 2.3 5.2 50.4 36.3 0.72 3.17 61.2 15.9 4.3 68.1 3.74 55.3 109.4 5.33 5.6

12.0 3.6 8.3 51.4 36.7 0.72 3.08 61.9 16.7 3.6 70.2 3.81 57.2 110.6 5.41 5.5

6.0 0.9 2.0 45.2 34.1 0.76 3.66 57.7 12.4 6.4 70.4 3.81 57.4 110.8 5.41 6.3

90 9.0 2.2 5.0 47.3 35.0 0.74 3.45 59.0 13.7 5.4 74.7 3.95 61.2 113.2 5.54 6.2

12.0 3.5 8.1 48.3 35.4 0.73 3.36 59.7 14.4 4.4 77.0 4.03 63.3 114.6 5.60 6.1

6.0 0.8 1.9 42.0 32.9 0.78 4.01 55.6 10.5 7.8

100 9.0 2.1 4.8 44.0 33.7 0.77 3.78 56.9 11.6 6.7

12.0 3.3 7.7 45.0 34.1 0.76 3.67 57.6 12.3 5.4

6.0 0.8 1.8 38.8 31.9 0.82 4.42 53.9 8.8 9.4

110 9.0 2.0 4.7 40.7 32.5 0.80 4.16 54.9 9.8 8.0

12.0 3.2 7.3 41.7 32.8 0.79 4.04 55.5 10.3 6.6

6.0 0.7 1.7 35.9 31.2 0.87 4.90 52.6 7.3 11.2

12.1 11.7

120 9.0 1.9 4.5 37.6 31.6 0.84 4.61 53.3 8.1 9.5

12.0 3.0 7.0 38.5 31.8 0.83 4.47 53.7 8.6 7.8

†ARI/ASHRAE/ISO 13256-1 (WLHP applications) certified conditions are 86°F EWT, 80.6°F DB / 66.2°F WB Rev: 01/07/07JH

EAT in cooling and 68°F DB / 59°F WB EAT in heating.

All entering air conditions are 80°F DB and 67°F WB in cooling and 70°F DB in heating

All performance data is based upon the lower voltage of dual voltage rated units

See performance correction tables for operating conditions other than those listed above.

œÌi\ œÀʜ«iÀ>̈œ˜Êˆ˜ÊÌ iÊà >`i`Ê>Ài>ÊÜ i˜ÊÜ>ÌiÀʈÃÊÕÃi`ʈ˜ÊˆiÕʜvÊ>˜ >˜Ìˆ‡vÀiiâiÊ܏Ṏœ˜]ÊÌ iÊ 7/Ê i>ۈ˜}Ê7>ÌiÀÊ/i“«iÀ>ÌÕÀi®Ê“ÕÃÌÊ LiÊV>VՏ>Ìi`°ÊœÜʓÕÃÌÊLiʓ>ˆ˜Ì>ˆ˜i`Ê̜Ê>ʏiÛiÊÃÕV ÊÌ >ÌÊ Ì iÊ 7/ʈÃʓ>ˆ˜Ì>ˆ˜i`Ê>LœÛiÊ{äÂÊÜ i˜ÊÌ iÊ7ÎʍՓ«iÀʈÃʘœÌÊ Vˆ««i`°Ê/ ˆÃʈÃÊ`ÕiÊ̜ÊÌ iÊ«œÌi˜Ìˆ>ÊœvÊÌ iÊÀivÀˆ}iÀ>˜ÌÊÌi“«iÀ>‡ ÌÕÀiÊLiˆ˜}Ê>ÃʏœÜÊ>ÃÊÎÓÂÊÜˆÌ Ê{äÂÊ 7/]ÊÜ ˆV ʓ>Þʏi>`Ê̜Ê>Ê ˜ÕˆÃ>˜ViÊVÕ̜ÕÌÊ`ÕiÊ̜ÊÌ iÊ>V̈Û>̈œ˜ÊœvÊÌ iÊ œÜÊ/i“«iÀ>ÌÕÀiÊ *ÀœÌiV̈œ˜°Ê7ÎÊà œÕ`ʘiÛiÀÊLiÊVˆ««i`ÊvœÀÊÃÞÃÌi“ÃÊÜˆÌ œÕÌÊ >˜ÌˆvÀiiâi°

25< / JR[fX` L^KRLONN]#VRW^]N 4FC / NW]N[RWP`J]N[]NVYN[J]^[N 5 6?< / `J]N[fX`RWDBPJUUXW\#VRW^]N 40C / NW]N[RWPJR[]NVYN[J]^[N 5JQ[NWQNR] M[bK^UK#`N]K^UK 72 / JR[QNJ]RWPLJYJLR]b

Page 20 of the Heat Controller HTV SERIES user manual — HTV060 & HTD060 Part Load
Pagina 20 · klik om te vergroten
Pagina 20

PERFORMANCE DATA HT060 Part Load

/6äÈäÊ*>ÀÌÊ œ>`

HTV060 & HTD060 Part Load

HTV060, HTD060 & HTH060 Part Load

Ratio KW HR EER HWG HC KW HE LAT COP HWG

20 14.0 4.1 9.4 28.4 2.44 20.0 89.5 3.40 3.4

7.0 0.5 1.1 49.1 34.5 0.70 1.56 54.4 31.4 - 31.3 2.54 22.7 91.5 3.61 3.5

30 10.5 1.9 4.4 50.1 34.9 0.70 1.52 55.2 32.9 - 32.3 2.55 23.6 92.2 3.71 3.5

14.0 3.9 9.0 51.6 35.7 0.69 1.51 56.7 34.3 - 32.8 2.55 24.1 92.5 3.77 3.4

7.0 0.4 0.9 51.9 37.1 0.71 1.71 57.8 30.4 - 35.7 2.66 26.7 94.5 3.94 3.6

2.9 3.0

40 10.5 1.9 4.3 52.3 37.2 0.71 1.63 57.9 32.2 - 37.0 2.68 27.9 95.4 4.05 3.6

14.0 3.7 8.6 52.7 37.2 0.71 1.59 58.1 33.1 - 37.7 2.69 28.5 95.8 4.10 3.5

7.0 0.3 0.7 52.0 37.9 0.73 1.91 58.5 27.3 1.0 40.4 2.82 30.8 97.7 4.19 3.7

50 10.5 1.8 4.1 52.6 37.9 0.72 1.79 58.7 29.4 0.9 41.9 2.83 32.3 98.8 4.34 3.7

14.0 3.5 8.2 52.8 37.9 0.72 1.74 58.7 30.4 0.8 42.8 2.84 33.1 99.3 4.42 3.6

7.0 0.3 0.6 50.2 37.1 0.74 2.15 57.5 23.3 1.7 45.2 2.86 35.5 101.0 4.64 3.9

3.8 3.4

60 10.5 1.7 4.0 51.3 37.6 0.73 2.01 58.2 25.6 1.5 47.0 2.87 37.2 102.2 4.80 3.8

14.0 3.4 7.8 51.8 37.8 0.73 1.94 58.4 26.7 1.4 47.9 2.88 38.1 102.9 4.88 3.8

7.0 0.2 0.5 47.5 35.8 0.75 2.44 55.9 19.5 2.3 50.0 2.90 40.2 104.3 5.06 4.1

70 10.5 1.7 3.9 49.1 36.6 0.75 2.28 56.8 21.5 2.1 52.1 2.92 42.1 105.7 5.23 4.1

14.0 3.2 7.5 49.8 36.9 0.74 2.20 57.3 22.6 1.9 53.1 2.93 43.1 106.4 5.32 3.5

7.0 0.2 0.4 44.5 34.3 0.77 2.78 53.9 16.0 3.0 54.8 2.95 44.8 107.6 5.45 4.4

4.0 4.1

80 10.5 1.6 3.8 46.1 35.1 0.76 2.59 55.0 17.8 2.7 57.0 2.98 46.8 109.1 5.61 4.3

14.0 3.1 7.2 46.9 35.5 0.76 2.51 55.5 18.7 2.4 58.1 3.00 47.9 109.9 5.68 4.3

7.0 0.1 0.3 41.2 32.8 0.79 3.16 52.0 13.0 3.5 59.5 3.02 49.2 110.8 5.77 4.7

90 10.5 1.6 3.6 42.9 33.5 0.78 2.96 53.0 14.5 3.2 61.7 3.06 51.3 112.3 5.91 4.6

14.0 2.9 6.8 43.7 33.9 0.78 2.86 53.5 15.3 2.9 62.9 3.09 52.4 113.1 5.97 4.0

7.0 0.1 0.2 38.1 31.5 0.82 3.59 50.4 10.6 4.1

100 10.5 1.5 3.5 39.6 32.0 0.81 3.38 51.1 11.7 3.7

14.0 2.8 6.5 40.4 32.4 0.80 3.27 51.6 12.4 3.3

7.0 0.1 0.2 35.5 30.7 0.86 4.08 49.4 8.7 4.7

110 10.5 1.4 3.3 36.7 31.0 0.84 3.84 49.8 9.5 4.1

14.0 2.7 6.2 37.3 31.2 0.83 3.73 50.0 10.0 3.7

7.0 0.0 0.1 33.7 30.3 0.90 4.63 49.5 7.3 5.1

11.4 11.0

120 10.5 1.4 3.2 34.4 30.4 0.88 4.36 49.3 7.9 4.6

14.0 2.6 6.0 34.9 30.6 0.88 4.24 49.3 8.2 4.1

†ARI/ASHRAE/ISO 13256-1 (WLHP applications) certified conditions are 86°F EWT, 80.6°F DB / 66.2°F WB Rev: 01/07/07JH

EAT in cooling and 68°F DB / 59°F WB EAT in heating.

All entering air conditions are 80°F DB and 67°F WB in cooling and 70°F DB in heating

All performance data is based upon the lower voltage of dual voltage rated units

See performance correction tables for operating conditions other than those listed above.

œÌi\ œÀʜ«iÀ>̈œ˜Êˆ˜ÊÌ iÊà >`i`Ê>Ài>ÊÜ i˜ÊÜ>ÌiÀʈÃÊÕÃi`ʈ˜ÊˆiÕʜvÊ>˜Ê >˜Ìˆ‡vÀiiâiÊ܏Ṏœ˜]ÊÌ iÊ 7/Ê i>ۈ˜}Ê7>ÌiÀÊ/i“«iÀ>ÌÕÀi®Ê“ÕÃÌÊ LiÊV>VՏ>Ìi`°ÊœÜʓÕÃÌÊLiʓ>ˆ˜Ì>ˆ˜i`Ê̜Ê>ʏiÛiÊÃÕV ÊÌ >ÌÊ Ì iÊ 7/ʈÃʓ>ˆ˜Ì>ˆ˜i`Ê>LœÛiÊ{äÂÊÜ i˜ÊÌ iÊ7ÎʍՓ«iÀʈÃʘœÌÊ Vˆ««i`°Ê/ ˆÃʈÃÊ`ÕiÊ̜ÊÌ iÊ«œÌi˜Ìˆ>ÊœvÊÌ iÊÀivÀˆ}iÀ>˜ÌÊÌi“«iÀ>‡ ÌÕÀiÊLiˆ˜}Ê>ÃʏœÜÊ>ÃÊÎÓÂÊÜˆÌ Ê{äÂÊ 7/]ÊÜ ˆV ʓ>Þʏi>`Ê̜Ê>Ê ˜ÕˆÃ>˜ViÊVÕ̜ÕÌÊ`ÕiÊ̜ÊÌ iÊ>V̈Û>̈œ˜ÊœvÊÌ iÊ œÜÊ/i“«iÀ>ÌÕÀiÊ *ÀœÌiV̈œ˜°Ê7ÎÊà œÕ`ʘiÛiÀÊLiÊVˆ««i`ÊvœÀÊÃÞÃÌi“ÃÊÜˆÌ œÕÌÊ >˜ÌˆvÀiiâi°

25< / JR[fX` L^KRLONN]#VRW^]N 4FC / NW]N[RWP`J]N[]NVYN[J]^[N 5 6?< / `J]N[fX`RWDBPJUUXW\#VRW^]N 40C / NW]N[RWPJR[]NVYN[J]^[N 5JQ[NWQNR] M[bK^UK#`N]K^UK 72 / JR[QNJ]RWPLJYJLR]b

Page 21 of the Heat Controller HTV SERIES user manual — HTV060, HTD060 & HTH060 Full Load
Pagina 21 · klik om te vergroten
Pagina 21

PERFORMANCE DATA HT060 Full Load

HTV060, HTD060 & HTH060 Full Load

HTV060 & HTD060 Full Load

/6äÈäÊՏÊ œ>`

Ratio KW HR EER HWG HC KW HE LAT COP HWG

20 15.0 5.0 11.6 41.6 3.73 28.9 89.3 3.27 4.0

7.5 0.6 1.5 68.0 49.7 0.73 2.99 78.2 22.7 - 45.3 3.83 32.2 91.0 3.47 4.1

30 11.3 2.3 5.3 69.0 50.3 0.73 2.86 78.7 24.2 - 47.1 3.88 33.9 91.8 3.56 4.1

15.0 4.8 11.0 70.4 51.3 0.73 2.80 79.9 25.2 - 48.1 3.90 34.8 92.3 3.61 4.0

7.5 0.5 1.2 69.8 51.5 0.74 3.23 80.8 21.6 - 51.4 3.99 37.8 93.8 3.78 4.3

40 11.3 2.2 5.0 70.7 51.8 0.73 3.07 81.2 23.0 - 53.6 4.05 39.8 94.8 3.88 4.2

15.0 4.5 10.4 71.0 51.9 0.73 2.99 81.2 23.7 - 54.8 4.08 40.9 95.4 3.94 4.1

7.5 0.4 1.0 70.0 52.3 0.75 3.51 82.0 19.9 2.1 57.6 4.15 43.4 96.7 4.06 4.5

50 11.3 2.1 4.8 70.7 52.4 0.74 3.31 82.0 21.3 1.9 60.2 4.22 45.8 97.9 4.18 4.4

15.0 4.3 9.9 71.1 52.4 0.74 3.22 82.1 22.1 1.5 61.6 4.26 47.1 98.5 4.24 4.3

7.5 0.3 0.8 68.0 51.8 0.76 3.83 81.1 17.7 3.0 64.0 4.33 49.2 99.6 4.33 4.8

60 11.3 2.1 4.7 69.5 52.2 0.75 3.60 81.8 19.3 2.6 67.0 4.41 52.0 101.0 4.45 4.7

15.0 4.1 9.4 70.1 52.4 0.75 3.49 82.0 20.0 2.2 68.7 4.46 53.5 101.8 4.52 4.7

7.5 0.3 0.7 65.2 50.8 0.78 4.21 79.5 15.5 4.1 70.5 4.51 55.1 102.7 4.58 5.3

70 11.3 2.0 4.5 67.2 51.5 0.77 3.94 80.7 17.1 3.5 74.1 4.61 58.4 104.3 4.71 5.2

15.0 3.9 8.9 68.1 51.8 0.76 3.81 81.1 17.9 2.9 76.1 4.67 60.1 105.2 4.78 5.1

7.5 0.2 0.5 61.8 49.4 0.80 4.64 77.7 13.3 5.4 77.3 4.71 61.3 105.8 4.82 5.8

6.6 6.9

80 11.3 1.9 4.4 64.2 50.4 0.78 4.34 79.0 14.8 4.5 81.5 4.83 65.0 107.7 4.95 5.7

15.0 3.6 8.4 65.3 50.8 0.78 4.19 79.6 15.6 3.7 83.8 4.90 67.1 108.8 5.02 5.6

7.5 0.2 0.4 58.1 47.8 0.82 5.14 75.6 11.3 6.7 84.4 4.92 67.7 109.1 5.04 6.5

90 11.3 1.8 4.2 60.6 48.9 0.81 4.80 77.0 12.6 5.7 89.2 5.06 72.0 111.3 5.17 6.4

15.0 3.5 8.0 61.9 49.4 0.80 4.63 77.7 13.4 4.8 91.9 5.14 74.4 112.5 5.24 6.3

7.5 0.1 0.3 54.1 46.1 0.85 5.72 73.7 9.5 8.3

100 11.3 1.8 4.1 56.7 47.2 0.83 5.34 74.9 10.6 7.0

15.0 3.3 7.6 58.0 47.8 0.82 5.15 75.6 11.3 5.8

7.5 0.1 0.2 50.2 44.3 0.88 6.40 72.0 7.8 10.0

110 11.3 1.7 4.0 52.7 45.4 0.86 5.96 73.0 8.8 8.5

15.0 3.1 7.2 54.0 46.0 0.85 5.75 73.6 9.4 6.9

7.5 0.0 0.1 46.4 42.7 0.92 7.18 70.9 6.5 11.9

13.1 12.6

120 11.3 1.7 3.9 48.7 43.7 0.90 6.68 71.5 7.3 10.1

15.0 2.9 6.8 49.9 44.2 0.89 6.45 71.9 7.7 8.3

†ARI/ASHRAE/ISO 13256-1 (WLHP applications) certified conditions are 86°F EWT, 80.6°F DB / 66.2°F WB Rev: 01/07/07JH

EAT in cooling and 68°F DB / 59°F WB EAT in heating.

All entering air conditions are 80°F DB and 67°F WB in cooling and 70°F DB in heating

All performance data is based upon the lower voltage of dual voltage rated units

See performance correction tables for operating conditions other than those listed above.

œÌi\ œÀʜ«iÀ>̈œ˜Êˆ˜ÊÌ iÊà >`i`Ê>Ài>ÊÜ i˜ÊÜ>ÌiÀʈÃÊÕÃi`ʈ˜ÊˆiÕʜvÊ>˜Ê >˜Ìˆ‡vÀiiâiÊ܏Ṏœ˜]ÊÌ iÊ 7/Ê i>ۈ˜}Ê7>ÌiÀÊ/i“«iÀ>ÌÕÀi®Ê“ÕÃÌÊ LiÊV>VՏ>Ìi`°ÊœÜʓÕÃÌÊLiʓ>ˆ˜Ì>ˆ˜i`Ê̜Ê>ʏiÛiÊÃÕV ÊÌ >ÌÊ Ì iÊ 7/ʈÃʓ>ˆ˜Ì>ˆ˜i`Ê>LœÛiÊ{äÂÊÜ i˜ÊÌ iÊ7ÎʍՓ«iÀʈÃʘœÌÊ Vˆ««i`°Ê/ ˆÃʈÃÊ`ÕiÊ̜ÊÌ iÊ«œÌi˜Ìˆ>ÊœvÊÌ iÊÀivÀˆ}iÀ>˜ÌÊÌi“«iÀ>‡ ÌÕÀiÊLiˆ˜}Ê>ÃʏœÜÊ>ÃÊÎÓÂÊÜˆÌ Ê{äÂÊ 7/]ÊÜ ˆV ʓ>Þʏi>`Ê̜Ê>Ê ˜ÕˆÃ>˜ViÊVÕ̜ÕÌÊ`ÕiÊ̜ÊÌ iÊ>V̈Û>̈œ˜ÊœvÊÌ iÊ œÜÊ/i“«iÀ>ÌÕÀiÊ *ÀœÌiV̈œ˜°Ê7ÎÊà œÕ`ʘiÛiÀÊLiÊVˆ««i`ÊvœÀÊÃÞÃÌi“ÃÊÜˆÌ œÕÌÊ >˜ÌˆvÀiiâi°

25< / JR[fX` L^KRLONN]#VRW^]N 4FC / NW]N[RWP`J]N[]NVYN[J]^[N 5 6?< / `J]N[fX`RWDBPJUUXW\#VRW^]N 40C / NW]N[RWPJR[]NVYN[J]^[N 5JQ[NWQNR] M[bK^UK#`N]K^UK 72 / JR[QNJ]RWPLJYJLR]b

Page 22 of the Heat Controller HTV SERIES user manual — PERFORMANCE DATA HT048 Part Load
Pagina 22 · klik om te vergroten
Pagina 22
Heat Controller HTV SERIES — PERFORMANCE DATA HT048 Part Load diagram (page 22)
Afb. 26 · PERFORMANCE DATA HT048 Part Load

Ratio KW HR EER HWG HC KW HE LAT COP HWG

20 15.0 10.1 23.3 33.0 3.68 20.4 89.1 2.62 4.1

7.5 1.7 3.9 59.1 42.1 0.71 2.25 66.8 26.3 - 36.9 3.74 24.1 91.3 2.89 4.8

30 11.25 3.9 9.0 60.0 42.5 0.71 2.15 67.3 27.9 - 38.3 3.77 25.4 92.1 2.98 4.8

15.0 6.9 15.9 61.0 43.1 0.71 2.10 68.1 29.0 - 39.0 3.78 26.1 92.6 3.03 4.8

7.5 1.6 3.7 61.1 43.0 0.70 2.46 69.5 24.8 - 43.1 3.84 30.0 94.9 3.29 5.5

40 11.25 3.6 8.3 61.8 43.5 0.70 2.33 69.8 26.6 - 45.0 3.87 31.8 96.0 3.41 5.5

15.0 6.5 15.0 62.5 43.8 0.70 2.27 70.2 27.5 - 46.1 3.88 32.8 96.7 3.48 5.5

7.5 1.5 3.5 61.9 43.5 0.70 2.72 71.2 22.8 2.3 49.9 3.94 36.4 98.9 3.71 6.2

50 11.25 3.4 7.9 62.6 43.9 0.70 2.55 71.3 24.5 2.1 52.3 3.97 38.8 100.3 3.86 6.1

15.0 6.0 13.9 62.9 44.0 0.70 2.48 71.4 25.4 1.9 53.7 3.99 40.1 101.1 3.94 6.1

7.5 1.4 3.2 59.7 42.3 0.71 3.02 70.0 19.8 2.8 56.9 4.04 43.2 103.0 4.13 6.8

60 11.25 3.1 7.2 61.2 43.1 0.70 2.83 70.8 21.6 2.5 59.9 4.09 46.0 104.7 4.30 8.3

15.0 5.4 12.5 61.8 43.4 0.70 2.74 71.1 22.6 2.3 61.6 4.11 47.5 105.6 4.39 6.8

7.5 1.3 3.0 56.8 40.9 0.72 3.36 68.3 16.9 3.4 64.1 4.15 49.9 107.1 4.52 7.4

70 11.25 3.0 6.9 58.6 41.8 0.71 3.15 69.4 18.6 3.1 67.5 4.21 53.1 109.1 4.70 7.4

15.0 5.4 12.5 59.5 42.2 0.71 3.05 69.9 19.5 2.9 69.3 4.24 54.9 110.1 4.79 7.4

7.5 1.3 3.0 53.3 39.4 0.74 3.76 66.2 14.2 4.2 71.1 4.27 56.5 111.1 4.88 8.0

80 11.25 2.8 6.5 55.4 40.3 0.73 3.52 67.4 15.7 3.8 74.7 4.34 59.9 113.2 5.05 8.0

15.0 5.0 11.6 56.4 40.7 0.72 3.41 68.0 16.6 3.5 76.6 4.38 61.7 114.4 5.13 8.0

7.5 1.3 3.0 49.7 37.9 0.76 4.21 64.1 11.8 5.1 77.7 4.40 62.7 115.0 5.18 8.6

90 11.25 2.8 6.5 51.8 38.7 0.75 3.95 65.3 13.1 4.7 81.3 4.48 66.0 117.1 5.32 8.6

15.0 5.0 11.6 52.8 39.1 0.74 3.82 65.9 13.8 4.3 83.1 4.52 67.7 118.1 5.39 8.5

7.5 1.2 2.8 46.1 36.6 0.79 4.73 62.2 9.8 6.1

100 11.25 2.7 6.2 48.1 37.2 0.77 4.44 63.2 10.8 5.7

15.0 4.8 11.1 49.1 37.6 0.77 4.29 63.7 11.4 5.2

7.5 1.1 2.5 42.9 35.7 0.83 5.31 61.0 8.1 7.4

110 11.25 2.5 5.8 44.5 36.1 0.81 4.99 61.6 8.9 6.8

15.0 4.5 10.4 45.5 36.3 0.80 4.83 61.9 9.4 6.2

7.5 1.1 2.5 40.2 35.5 0.88 5.97 60.6 6.7 8.7

120 11.25 2.4 5.5 41.5 35.5 0.85 5.61 60.7 7.4 8.1

15.0 4.3 9.9 42.3 35.6 0.84 5.44 60.8 7.8 7.4

†ARI/ASHRAE/ISO 13256-1 (WLHP applications) certified conditions are 86°F EWT, 80.6°F DB / 66.2°F WB

EAT in cooling and 68°F DB / 59°F WB EAT in heating.

All entering air conditions are 80°F DB and 67°F WB in cooling and 70°F DB in heating

All performance data is based upon the lower voltage of dual voltage rated units

See performance correction tables for operating conditions other than those listed above.

œÌi\ œÀʜ«iÀ>̈œ˜Êˆ˜ÊÌ iÊà >`i`Ê>Ài>ÊÜ i˜ÊÜ>ÌiÀʈÃÊÕÃi`ʈ˜ÊˆiÕʜvÊ>˜Ê >˜Ìˆ‡vÀiiâiÊ܏Ṏœ˜]ÊÌ iÊ 7/Ê i>ۈ˜}Ê7>ÌiÀÊ/i“«iÀ>ÌÕÀi®Ê“ÕÃÌÊ LiÊV>VՏ>Ìi`°ÊœÜʓÕÃÌÊLiʓ>ˆ˜Ì>ˆ˜i`Ê̜Ê>ʏiÛiÊÃÕV ÊÌ >ÌÊ Ì iÊ 7/ʈÃʓ>ˆ˜Ì>ˆ˜i`Ê>LœÛiÊ{äÂÊÜ i˜ÊÌ iÊ7ÎʍՓ«iÀʈÃʘœÌÊ Vˆ««i`°Ê/ ˆÃʈÃÊ`ÕiÊ̜ÊÌ iÊ«œÌi˜Ìˆ>ÊœvÊÌ iÊÀivÀˆ}iÀ>˜ÌÊÌi“«iÀ>‡ ÌÕÀiÊLiˆ˜}Ê>ÃʏœÜÊ>ÃÊÎÓÂÊÜˆÌ Ê{äÂÊ 7/]ÊÜ ˆV ʓ>Þʏi>`Ê̜Ê>Ê ˜ÕˆÃ>˜ViÊVÕ̜ÕÌÊ`ÕiÊ̜ÊÌ iÊ>V̈Û>̈œ˜ÊœvÊÌ iÊ œÜÊ/i“«iÀ>ÌÕÀiÊ *ÀœÌiV̈œ˜°Ê7ÎÊà œÕ`ʘiÛiÀÊLiÊVˆ««i`ÊvœÀÊÃÞÃÌi“ÃÊÜˆÌ œÕÌÊ >˜ÌˆvÀiiâi°

25< / JR[fX` L^KRLONN]#VRW^]N 4FC / NW]N[RWP`J]N[]NVYN[J]^[N 5 6?< / `J]N[fX`RWDBPJUUXW\#VRW^]N 40C / NW]N[RWPJR[]NVYN[J]^[N 5JQ[NWQNR] M[bK^UK#`N]K^UK 72 / JR[QNJ]RWPLJYJLR]b

Page 23 of the Heat Controller HTV SERIES user manual — PERFORMANCE DATA HT048 Part Load
Pagina 23 · klik om te vergroten
Pagina 23
Heat Controller HTV SERIES — PERFORMANCE DATA HT048 Part Load diagram (page 23)
Afb. 27 · PERFORMANCE DATA HT048 Part Load

PERfoRmaNcE Data HTV070 & HTD070 Full Load Performance capacities shown in thousands of Btuh.

Ratio KW HR EER HWG HC KW HE LAT COP HWG

20 17.0 10.1 23.3 45.1 4.67 29.2 89.9 2.8 5.0

8.5 2.2 5.1 74.9 49.2 0.66 3.36 86.4 22.3 - 49.5 4.74 33.3 91.8 3.1 5.9

30 12.8 5.0 11.6 75.4 49.6 0.66 3.23 86.4 23.4 - 51.6 4.78 35.3 92.8 3.2 5.9

17.0 8.9 20.6 76.0 50.0 0.66 3.10 86.6 24.5 - 52.8 4.81 36.4 93.3 3.2 5.8

8.5 2.1 4.9 79.2 51.4 0.65 3.57 91.4 22.2 - 57.4 4.90 40.6 95.3 3.4 6.7

40 12.8 4.7 10.9 79.7 51.8 0.65 3.45 91.5 23.1 - 60.3 4.97 43.4 96.6 3.6 6.7

17.0 8.3 19.2 80.2 52.2 0.65 3.33 91.6 24.1 - 62.0 5.01 44.9 97.3 3.6 6.7

8.5 1.9 4.4 80.1 51.7 0.64 4.08 94.1 19.6 3.7 66.2 5.11 48.7 99.2 3.8 7.5

50 12.8 4.3 9.9 80.8 52.5 0.65 3.93 94.2 20.6 3.4 70.0 5.21 52.2 100.9 3.9 7.5

17.0 7.7 17.8 81.3 53.0 0.65 3.80 94.3 21.4 3.2 72.1 5.26 54.2 101.8 4.0 7.5

8.5 1.7 3.9 78.0 50.8 0.65 4.65 93.9 16.8 4.5 75.4 5.35 57.2 103.3 4.1 8.3

60 12.8 3.9 9.0 78.9 51.4 0.65 4.45 94.1 17.7 4.2 80.1 5.49 61.3 105.3 4.3 8.3

17.0 7.0 16.2 79.7 51.8 0.65 4.37 94.6 18.2 3.8 82.6 5.56 63.6 106.4 4.4 8.3

8.5 1.7 3.9 72.5 50.3 0.69 5.02 89.6 14.4 5.5 84.9 5.63 65.6 107.4 4.4 9.1

70 12.8 3.9 9.0 75.0 50.7 0.68 4.75 91.2 15.8 5.1 90.1 5.80 70.3 109.7 4.6 9.0

17.0 6.9 15.9 76.1 50.8 0.67 4.63 91.9 16.4 4.7 92.9 5.90 72.8 111.0 4.6 9.0

8.5 1.6 3.7 68.1 49.8 0.73 5.47 86.8 12.4 6.8 94.1 5.94 73.8 111.5 4.6 9.8

80 12.8 3.6 8.3 71.2 50.2 0.71 5.15 88.7 13.8 6.3 99.6 6.15 78.6 113.9 4.7 9.8

17.0 6.5 15.0 72.6 50.4 0.69 5.01 89.7 14.5 5.8 102.4 6.26 81.0 115.2 4.8 9.7

8.5 1.6 3.7 63.4 48.8 0.77 6.01 83.9 10.5 8.3 102.7 6.27 81.3 115.3 4.8 10.5

90 12.8 3.6 8.3 66.5 49.5 0.74 5.65 85.8 11.8 7.7 108.0 6.52 85.8 117.6 4.9 10.4

17.0 6.5 15.0 68.1 49.8 0.73 5.47 86.8 12.5 7.0 110.6 6.65 87.9 118.8 4.9 10.4

8.5 1.5 3.5 58.8 47.3 0.80 6.61 81.4 8.9 10.1

100 12.8 3.4 7.9 61.7 48.3 0.78 6.21 82.9 9.9 9.3

17.0 6.1 14.1 63.2 48.8 0.77 6.03 83.8 10.5 8.5

8.5 1.4 3.2 55.1 45.4 0.82 7.28 79.9 7.6 12.0

110 12.8 3.3 7.6 57.3 46.6 0.81 6.86 80.7 8.4 11.1

17.0 5.8 13.4 58.6 47.2 0.81 6.65 81.3 8.8 10.2

8.5 1.4 3.2 52.9 43.3 0.82 8.01 80.2 6.6 14.3

120 12.8 3.1 7.2 54.0 44.6 0.83 7.55 79.8 7.2 13.2

17.0 5.6 12.9 54.9 45.2 0.82 7.33 79.9 7.5 12.1

†ARI/ASHRAE/ISO 13256-1 (WLHP applications) certified conditions are 86°F EWT, 80.6°F DB / 66.2°F WB

EAT in cooling and 68°F DB / 59°F WB EAT in heating.

All entering air conditions are 80°F DB and 67°F WB in cooling and 70°F DB in heating

All performance data is based upon the lower voltage of dual voltage rated units

See performance correction tables for operating conditions other than those listed above.

œÌi\ œÀʜ«iÀ>̈œ˜Êˆ˜ÊÌ iÊà >`i`Ê>Ài>ÊÜ i˜ÊÜ>ÌiÀʈÃÊÕÃi`ʈ˜ÊˆiÕʜvÊ>˜Ê >˜Ìˆ‡vÀiiâiÊ܏Ṏœ˜]ÊÌ iÊ 7/Ê i>ۈ˜}Ê7>ÌiÀÊ/i“«iÀ>ÌÕÀi®Ê“ÕÃÌÊ LiÊV>VՏ>Ìi`°ÊœÜʓÕÃÌÊLiʓ>ˆ˜Ì>ˆ˜i`Ê̜Ê>ʏiÛiÊÃÕV ÊÌ >ÌÊ Ì iÊ 7/ʈÃʓ>ˆ˜Ì>ˆ˜i`Ê>LœÛiÊ{äÂÊÜ i˜ÊÌ iÊ7ÎʍՓ«iÀʈÃʘœÌÊ Vˆ««i`°Ê/ ˆÃʈÃÊ`ÕiÊ̜ÊÌ iÊ«œÌi˜Ìˆ>ÊœvÊÌ iÊÀivÀˆ}iÀ>˜ÌÊÌi“«iÀ>‡ ÌÕÀiÊLiˆ˜}Ê>ÃʏœÜÊ>ÃÊÎÓÂÊÜˆÌ Ê{äÂÊ 7/]ÊÜ ˆV ʓ>Þʏi>`Ê̜Ê>Ê ˜ÕˆÃ>˜ViÊVÕ̜ÕÌÊ`ÕiÊ̜ÊÌ iÊ>V̈Û>̈œ˜ÊœvÊÌ iÊ œÜÊ/i“«iÀ>ÌÕÀiÊ *ÀœÌiV̈œ˜°Ê7ÎÊà œÕ`ʘiÛiÀÊLiÊVˆ««i`ÊvœÀÊÃÞÃÌi“ÃÊÜˆÌ œÕÌÊ >˜ÌˆvÀiiâi°

25< / JR[fX` L^KRLONN]#VRW^]N 4FC / NW]N[RWP`J]N[]NVYN[J]^[N 5 6?< / `J]N[fX`RWDBPJUUXW\#VRW^]N 40C / NW]N[RWPJR[]NVYN[J]^[N 5JQ[NWQNR] M[bK^UK#`N]K^UK 72 / JR[QNJ]RWPLJYJLR]b

Page 24 of the Heat Controller HTV SERIES user manual — '68 4'*+'8/3-466+)8/437 /6,14:911 4'*
Pagina 24 · klik om te vergroten
Pagina 24

*>ÀÌÊ œ>`Ê"«iÀ>̈œ˜

Part Load Cooling Corrections 400 CFM per Ton

911 4'*441/3-466+)8/437 5+6$43

$,5:3.(7

%6;(33.

(7 "6>,9

#,1

ä°nÇÈ ä°nnΠ䰙äΠ䰙Îx 䰙Ǚ 䰙™£ £°äää £°äÎx £°£äx

䰙n£ 䰙nx 䰙n™ 䰙™Î 䰙™n 䰙™™ £°äää £°ääÎ £°ään

ä°n™x ä°™ä£ ä°™£n 䰙{x 䰙nÓ ä°™™Î £°äää £°äÎä £°änn

£°£Çn ä°nә £°£ÓÎ ä°n™x ä°ÈÓÈ ä°{™ä ä°{În

£°Ó™Ó £°äÓ{ ä°ÇÓx

£°änn ä°nxÇ ä°ÇÓn ä°ÈÇÎ ä°xxÓ

£°ä™x £°äΙ £°äää ä°n{Ç ä°xÈÇ

£°ä™x £°äΙ £°äää ä°n{Ç ä°xÈÇ

£°ÓnÎ £°Ó{x £°ä™Ç ä°nÎÎ

£°ÎÎx £°änx £°ÎÓ{

$,5:0)3,*(7(*0;@,8

911 4'*+'8/3-466+)8/437 /6,14:911 4'*

Part Load Heating Corrections Airflow Part Load

+'8/3- 441/3-

;.(7 "6>,9 ,(;6-

6- 6405(3 ;.(7 "6>,9 ,(;6-

$,5:

(7 $% "6>,9 ,(;6-

3.

£°££ä £°£äÇ £°£äÓ £°ä™{ £°än{ £°äÇÎ £°äÈä £°ä{È £°äΣ £°ä£È £°ääÈ £°äää 䰙n{ 䰙Èn

ä°ÈÇ{ ä°ÈÇÈ ä°ÈnÇ ä°ÇäÈ ä°ÇÎÓ ä°ÇÈ{ ä°näÓ ä°n{È ä°n™Î 䰙{x 䰙Çn £°äää £°äxn £°££Ç

£°ÓäÈ £°ÓäÓ £°£™Ó £°£Ç™ £°£È£ £°£{ä £°££Ç £°ä™ä £°äÈ£ £°äΣ £°ä£Î £°äää 䰙Èn 䰙ÎÈ

£°Ó{£ £°£ÈÎ £°££x £°äÇÈ £°ä{Î £°ä£n

ä°nn£ 䰙£x 䰙ÎÇ ä°™xÈ ä°™ÇΠ䰙nn

䰙Óä 䰙{Ó ä°™xÈ ä°™È™ 䰙n£ 䰙™£

ä°Çn£ ä°nÎÓ ä°nÈÇ ä°™ä£ ä°™Î{ 䰙ÈÇ

ä°n{™ ä°nnΠ䰙äÈ ä°™Ó™ 䰙xÓ ä°™ÇÈ

䰙x™ 䰙È{ 䰙ș 䰙Çx 䰙nÓ ä°™™ä

䰙ÓÇ ä°™{È ä°™x™ 䰙Çä 䰙n£ 䰙™£

䰙™ä 䰙nÈ ä°™nΠ䰙n£ 䰙Ǚ

£°ä£ä £°ä£Ç £°äÓ{ £°äÎä £°äÎ{

£°ääÇ £°ä£Î £°ä£n £°äÓ£ £°äÓÎ

£°äÎÎ £°äÈx £°ä™n £°£Î£ £°£x™

£°äÓx £°äx£ £°äǙ £°£än £°£ÎÎ

£°ä££ £°äÓÎ £°äÎÈ £°äx£ £°äÈÎ

£°ään £°ä£x £°äÓ£ £°äÓÈ £°äÎä

ՏÊ œ>`Ê"«iÀ>̈œ˜

'68 4'*441/3-466+)8/437 5+6$43

Full Load Cooling Corrections 400 CFM per Ton

$,5:3.(7

%6;(33.

(7 "6>,9 ,(;6-

#,1 $,5:0)3,*(7(*0;@,8

ä°nÎÓ ä°nxä ä°nnä 䰙ÓÓ ä°™Çx 䰙™ä £°äää £°ä{ä £°££Ç

䰙{È ä°™xΠ䰙È{ 䰙ÇÇ ä°™™Î 䰙™Ç £°äää £°ä££ £°äÎÎ

ä°nxÎ ä°nÇä ä°n™È 䰙ÎÓ ä°™Ç™ 䰙™£ £°äää £°äÎx £°£ä£

£°äÈÈ ä°ÇÎÇ £°££™ ä°n™Ó ä°È{£ ä°x{Ç ä°xäx

£°Ó{È ä°™xn ä°ÈnÈ

£°£äÓ ä°nÈn ä°ÇÈÎ ä°Ç£Ç ä°ÈäÎ

£°ä™Î £°äÎn £°äää ä°nxÇ ä°È£ä

£°£Óä £°äÈx £°äÓÇ ä°nn{ ä°ÈÎÇ

£°ÓÈ£ £°ÓÓÎ £°änä ä°nÎ{

£°ÎäÓ £°äÈÓ £°Ó™È

'68 4'*+'8/3-466+)8/437 /6,14:911 4'*

Full Load Heating Corrections

+'8/3- 441/3-

;.(7 "6>,9 ,(;6-

6- 6405(3 ;.(7 "6>,9 ,(;6-

$,5:

(7 $% "6>,9 ,(;6-

3.

£°ä™n £°än{ £°äÇÓ £°äÈ£ £°äxÓ £°ä{Î £°äÎx £°äÓÇ £°ä£™ £°ä£ä £°ää{ £°äää 䰙n™ 䰙ÇÈ

ä°Çä£ ä°Ç£{ ä°ÇΣ ä°ÇxÎ ä°ÇǙ ä°nän ä°n{£ ä°nÇÇ ä°™£x 䰙xÇ ä°™nÓ £°äää £°ä{x £°ä™Î

£°£™Ç £°£ÇÇ £°£xÇ £°£În £°£Óä £°£äÓ £°än{ £°äÈx £°ä{x £°äÓÎ £°ä£ä £°äää 䰙Ç{ 䰙{È

ä°n™È 䰙Ó{ 䰙{Ó ä°™x™ 䰙Ç{ 䰙nn

䰙Óx 䰙{È ä°™Èä 䰙ÇÓ ä°™nΠ䰙™Ó

ä°Çnn ä°nә ä°nÈ£ ä°n™x 䰙Îä 䰙Èx

ä°nxÓ ä°nÇÈ ä°n™Ç 䰙ӣ 䰙{È ä°™ÇÎ

䰙£Î 䰙ÓÈ ä°™ÎÇ ä°™xä ÈxnÓ ä°™nÓ

䰙ÓÓ ä°™{Ó ä°™xx 䰙Èn 䰙Ǚ 䰙™ä

£°£xÎ £°£äÇ £°äÇn £°äxÎ £°äÎÓ £°ä£{

䰙n™ 䰙nÓ ä°™Ç™ 䰙ÇÇ ä°™Çx

£°ä££ £°ä£™ £°äÓÇ £°äÎÎ £°äÎn

£°ääÇ £°ä£Ó £°ä£È £°ä£n £°ä£™

£°äÎÎ £°äÈ{ £°ä™Ó £°££È £°£ÎÓ

£°äÓÇ £°äxÓ £°äÇx £°ä™È £°££ä

£°äÓä £°ä{Ó £°äÈÈ £°ä™£ £°££Ó

£°ää™ £°ä£n £°äÓx £°äÎÓ £°äÎÇ

Show 25 more labels / short text on this page
,(;6- · ' · ",9 · 5;09 · %6;(3 · ?; · %656- · ?; · (7 · #,1 · 䰙Èä · 䰙Çn 䰙nÈ · £°ä£Ç £°äÓ£ £°äÓ{ · ' · ",9 · 5;09 · %656- · %6;(3 · ?; · ?; · (7 · #,1 · 䰙x™ · 䰙ÇÇ ä°™nx · £°ä£n £°äÓÓ £°äÓÈ
Page 25 of the Heat Controller HTV SERIES user manual — 347D<
Pagina 25 · klik om te vergroten
Pagina 25

Blower Performance Data

Airflow in CFM with wet coil and clean air filter

Max ESP (in. wg)

Cooling Mode Dehumid Mode Heating Mode AUX CFM

Mode Stg 1 Stg 2 Fan Stg 1 Stg 2 Fan Stg 1 Stg 2 Fan

0.50 1/2 4 810 950 475 630 740 475 920 1060 475 4 1060

0.50 1/2 3 725 850 425 560 660 425 825 950 425 3 950

0.50 1/2 2 620 730 370 490 570 370 710 820 370 2 820

0.50 1/2 1 520 610 300 600 690 300 1 690

0.50 1/2 4 1120 1400 700 870 1090 700 1120 1400 700 4 1400

0.50 1/2 3 1000 1250 630 780 980 630 1000 1250 630 3 1350

0.50 1/2 2 860 1080 540 670 840 540 860 1080 540 2 1350

0.50 1/2 1 730 900 450 730 900 450 1 1350

0.75 1 4 1460 1730 870 1140 1350 870 1560 1850 870 4 1850

0.75 1 3 1300 1550 780 1020 1210 780 1400 1650 780 3 1660

0.75 1 2 1120 1330 670 870 1040 670 1200 1430 670 2 1430

0.75 1 1 940 1120 560 1010 1200 560 1 1350

0.75 1 4 1670 2050 1020 1300 1600 1020 1860 2280 1020 4 2280

0.75 1 3 1500 1825 920 1160 1430 920 1650 2050 920 3 2040

0.75 1 2 1280 1580 790 1000 1230 790 1430 1750 790 2 1750

0.75 1 1 1080 1320 660 1200 1470 660 1 1470

0.75 1 4 1620 2190 1050 1270 1650 1050 1690 2230 1050 4 2230

0.75 1 3 1500 1950 980 1170 1520 980 1600 2100 980 3 2100

0.75 1 2 1400 1830 910 1100 1420 910 1400 1850 910 2 1870

0.75 1 1 1320 1700 850 1240 1620 850 1 1670

Factory shipped on Tap Setting 2 During Auxiliary operation (residential units only) the CFM will run at the higher if the heating (delay jumper) or AUX settings Airflow is controlled within +/- 5% up to Max ESP shown with wet coil and standard 1” fiberglass filter Do not select Dehumidification mode if HP CFM is on setting 1 All units ARI/ISO/ASHRAE 13256-1 rated HP (Cooling) Delay (Heating) CFM Setting 3

ECM Control Features

$ 9,;/N,:(0==482<

996482\N]]RWP\.CC CB 6B^WR]\ "0,=482\N]]RWP\.CC CB^WR]\ >A 70;2"0,= \N]]RWP\.CC CB 6B^WR]\

EN[\RXW8 EN[\RXW8 EN[\RXW8 *-&('+$+ *-&('+$+ *-&('+$+ N,: HP CFM N,: DELAY N,: AUX CFM (0==482 L>7:0; (+G (+ (0==482 L>7:0; (+ (+ (0==482 L>7:0; (+H (+ % % >= >= % % >= >= % % >= >= & & >= >55 & & >= >55 & & >= >55 ' ' >55 >= ' ' >55 >= ' ' >55 >= ( ( >55 >55 ( ( >55 >55 ( ( >55 >55 6B^WR]\^\N]QN\JVN\N]]RWP\OX[ CQR\]JKUNWX]^\NMOX[6B^WR]\" AN\RMNW]RJU^WR]\ KX]QLXXURWP WX[VJU 25

EN[\RXW88 %+1$$%-=$%

EN[\RXW88 %+1$$%-=$% KM(@4=.3 KM(@4=.3

EN[\RXW88 %+1$$%-=$%

N,: (0==482

N,: (0==482

N,: (0==482

KM(@4=.3

% & ' (

% & ' (

% & ' (

6B^WR]\^\ KX]QLXXURWP

CQR\]JKUNW

AN\RMNW]RJ

!$ /P><=\N]]RWP\.CC CB 6B^WR]\ 03>7$9/0\N]]RWP\.CC CB 6B^WR]\

ʘÌiÀv>ViÊ >ޜÕÌ

$*0;<498KKK8=0;1,.0#,B9>=

EN[\RXW8 EN[\RXW8 *-&('+$+ *-&('+$+ N,: CFM Adj N,: Dehumid (0==482 L>7:0; (+I (+ (0==482 L>7:0; C4BC % >= >= =>A< YRW\% & & >= >55 3NQ^VRM YRW\& ' F ' >55 >= =>A< ( >55 >55

EN[\RXW88

EN[\RXW88 %+1$$%-=$%

KM(@4=.3 %+1$$%-=$%

N,: (0==482

KM(@4=.3

N,: (0==482

£É{»Ê-«>`i œ˜˜iV̈œ˜Ã ÌœÊ 8 Ê œ>À`

GE(:,/0 9880.=498<

=9 O$9; O$ 9,;/

N30;79<=,= K8:>=# <

(+

F

C4BC

=>A< 3NQ^VRM

A 2 j& j% 6 > F 2 A 37 0;% 0 0 0;%

6 A

F =>A<

C1%

!$ 9>8=0; G16,<3:0;G !$

N30;79<=,= 9880.=498<

$$9=9; #9@*96=,20 9880.=9;

03>74/414.,=498

BF% BF& BF' BF( BF) BF* BF+ BF, BF- >55 >=

347D<

B%

!,8(:00/(060.=498 KM(@4=.3

Show 14 more labels / short text on this page
Residential · Units Only · Fan Motor · Tap Setting · Aux/ Emerg · (hp) · j% · j& · > · >= >55 · 25< · j · # · 9%
Page 26 of the Heat Controller HTV SERIES user manual — œ˜ÃՏÌÊ>ˆÀyœÜÊëiVˆwV>̈œ˜ÃÊvœÀÊÌ iÊëiVˆwVÊ՘ˆÌʓœ`iÊÌœÊ VœÀÀi>ÌiÊëii`ÊÌ>«ÊÃiÌ̈˜}Ê̜Ê>ˆÀyœÜʈ˜Ê  °
Pagina 26 · klik om te vergroten
Pagina 26

.H7DGK?B?JOW ' EDJHEB!;7JKH;I

CQN42<OJWR\LXW][XUUNMKbJWRW]N[OJLNKXJ[M]QJ] LXW_N[]\]QN[VX\]J]RWY^]\JWMeNUM\NUNL]JKUN25< \N]]RWP\]X\RPWJU\^\NMKb]QN42<VX]X[LXW][XUUN["

!$ /P><=\N]]RWP\.CQN25

5JW\YNNM\J[N\NUNL]NM `R]QS^VYN[\_RJJWRWNYX\R]RXW38?\`R]LQ CX]JTNO^UUJM_JW]JPNXO]QN42<VX]X[ ONJ]^[N\ JV^U]R!\]JPN]QN[VX\]J]\QX^UMKN^\NM &!\]JPN QNJ]#&!\]JPNLXXUX['!\]JPNQNJ]#&!\]JPNLXXU "

vi>ÌÕÀiÃ]Ê>ʓՏ̈‡ÃÌ>}iÊÌ iÀ“œÃÌ>ÌÊÃÕV Ê>ÃÊÇnää‡Óä£Êà œÕ`Ê LiÊÕÃi`ÊӇÃÌ>}iÊ i>ÌÉӇÃÌ>}iÊVœœÊœÀÊ·ÃÌ>}iÊ i>ÌÉӇÃÌ>}iÊ Vœœ®°

03>74/4Q.,=498$9/0\N]]RWP\.CQNMNQ^VRMReLJ]RXW VXMN\N]]RWPY[X_RMN\eNUM\NUNL]RXWXOQ^VRMR]bLXW][XU" FQNWXYN[J]RWPRW]QNWX[VJUVXMN ]QNLXXURWPJR[fX` \N]]RWP\J[NMN]N[VRWNMKb]QNLXXURWP]JY\N]]RWPJKX_N" FQNWMNQ^VRMReLJ]RXWR\NWJKUNM]QN[NR\J[NM^L]RXWRW JR[fX`RWLXXURWP]XRWL[NJ\N]QNVXR\]^[N[NVX_JUXO]QN QNJ]Y^VY"2XW\^U]\^KVR]]JUMJ]JX[\YNLReLJ]RXW\LJ]JUXP OX[]QN\YNLReL^WR]\N[RN\JWMVXMNU]XLX[[NUJ]N\YNNM ]JY]XJR[fX`RW25

%9=0J ?X`N[V^\]KNXOO]X]QN^WR]OX[J]UNJ\]]Q[NN \NLXWM\KNOX[N]QN42<VX]X[`RUU[NLXPWRcNJ\YNNM LQJWPN"CQNVX]X[`RUU[NLXPWRcNJLQJWPNRW]QN25< 0MS^\]X[MNQ^VRMReLJ]RXWVXMN\N]]RWP\`QRUN]QN^WR] R\YX`N[NM"

i>ÌʫՓ«°Ê œ˜ÃՏÌÊ>ˆÀyœÜÊëiVˆwV>̈œ˜ÃÊvœÀÊÌ iÊëiVˆwVÊ՘ˆÌÊ “œ`iÊ̜ÊVœÀÀi>ÌiÊëii`ÊÌ>«ÊÃiÌ̈˜}Ê̜Ê>ˆÀyœÜʈ˜Ê °Ê/ iÊ `i Փˆ`ˆwV>̈œ˜Ê“œ`iÊV>˜ÊLiÊi˜>Li`ʈ˜ÊÌܜÊÜ>Þð

CQN[NJ[NOX^[MROON[NW]JR[fX`\N]]RWP\O[XVUX`N\]JR[fX` [J]N \YNNM]JY% ]X]QNQRPQN\]JR[fX`[J]N \YNNM]JY( " CQNLQJ[]\KNUX`RWMRLJ]N\N]]RWP\OX[KX]Q_N[\RXW\XO]QN 42<RW]N[OJLNKXJ[M OXUUX`NMKbMN]JRUNMRWOX[VJ]RXWOX[ NJLQ\N]]RWP"

MNQ^VRMReLJ]RXWVXMNR\\NUNL]NM _RJ38?\`R]LQX[ S^VYN[\N]]RWP ]QN42

996482 \N]]RWP\.CQNLXXURWP\N]]RWPMN]N[VRWN\]QN LXXURWP WX[VJU 25<OX[JUU^WR]\`R]Q42<VX]X[" 2XXURWP WX[VJU \N]]RWPR\^\NM`QNW]QN^WR]R\WX]RW MNQ^VRMReLJ]RXWVXMN"

CJY%R\]QNUX`N\]25<\N]]RWP `QRUN]JY(R\]QNQRPQN\] 25<\N]]RWP"CX J_XRMJR[LXRUO[NNcN!^Y ]JY%VJbWX]KN^\NMRO]QN MNQ^VRMReLJ]RXWVXMNR\\NUNL]NM"2XW\^U]\^KVR]]JUMJ]J X[\YNLReLJ]RXW\LJ]JUXPOX[]QN\YNLReL^WR]\N[RN\JWM VXMNU]XLX[[NUJ]N\YNNM]JY\N]]RWP]XJR[fX`RW25<"

ÊÃiÌ̈˜}°Ê/œÊ>ۜˆ`Ê>ˆÀÊVœˆÊvÀiiâi‡Õ«]ÊÌ>«Ê£Ê“>ÞʘœÌÊLiÊ ÕÃi`ʈvÊÌ iÊ`i Փˆ`ˆwV>̈œ˜Ê“œ`iʈÃÊÃiiVÌi`°Ê œ˜ÃՏÌÊ>ˆÀyœÜÊ Ã«iVˆwV>̈œ˜ÃÊvœÀÊÌ iÊëiVˆwVÊ՘ˆÌʓœ`iÊ̜ÊVœÀÀi>ÌiÊëii`Ê Ì>«ÊÃiÌ̈˜}Ê̜Ê>ˆÀyœÜʈ˜Ê °

"0,=482 \N]]RWP\.CQNQNJ]RWP\N]]RWPMN]N[VRWN\]QN QNJ]RWP25<OX[ %$,90,:<50;: CJY%R\]QNUX`N\]25<\N]]RWP `QRUN]JY(R\]QNQRPQN\] 25<\N]]RWP"2XW\^U]\^KVR]]JUMJ]JX[\YNLReLJ]RXW\ LJ]JUXPOX[]QN\YNLReL^WR]\N[RN\JWMVXMNU]XLX[[NUJ]N \YNNM]JY\N]]RWP]XJR[fX`RW25<"

/>«Ê£ÊˆÃÊÌ iʏœÜiÃÌÊ ÊÃiÌ̈˜}]ÊÜ ˆiÊÌ>«Ê{ʈÃÊÌ iÊ ˆ} iÃÌÊ ÊÃiÌ̈˜}°Ê œ˜ÃՏÌÊ>ˆÀyœÜÊëiVˆwV>̈œ˜ÃÊvœÀÊÌ iÊëiVˆwVÊ՘ˆÌÊ “œ`iÊ̜ÊVœÀÀi>ÌiÊëii`ÊÌ>«ÊÃiÌ̈˜}Ê̜Ê>ˆÀyœÜʈ˜Ê °

>A464,;B 70;208.B"0,=\N]]RWP\.CQNJ^aRURJ[b# NVN[PNWLbQNJ]\N]]RWPMN]N[VRWN\]QN25

œ˜ÃՏÌÊ>ˆÀyœÜÊëiVˆwV>̈œ˜ÃÊvœÀÊÌ iÊëiVˆwVÊ՘ˆÌʓœ`iÊÌœÊ VœÀÀi>ÌiÊëii`ÊÌ>«ÊÃiÌ̈˜}Ê̜Ê>ˆÀyœÜʈ˜Ê °

Page 27 of the Heat Controller HTV SERIES user manual — Single 80.0 69.3 100.0 86.6 100 90 2 100
Pagina 27 · klik om te vergroten
Pagina 27

Heat Controller GeoMax 2 Geothermal Heat Pump Systems

Auxiliary Electric Heat

Auxiliary Heat Ratings

Heat Controller HTV SERIES — Heat Controller GeoMax 2 Geothermal Heat Pump Systems diagram (page 27)
Afb. 28 · Heat Controller GeoMax 2 Geothermal Heat Pump System…

CFM Required 024 036 048 060 070 230V 208V 230V 208V

Grey area denotes compatibility

Auxiliary Heat Electrical Data

Heat Controller HTV SERIES — Auxiliary Heat Electrical Data diagram (page 27)
Afb. 29 · Auxiliary Heat Electrical Data

Heater Amps Minimum Circuit Amps Maximum Fuse Supply Wire

230V 208V 230V 208V 230V 208V Min AWG Max Ft

AGM5A Single 20.0 17.3 25.0 21.6 25 25 10 70

AGM8A Single 31.7 27.5 39.6 34.4 40 35 8 70

AGM10A Single 40.0 34.7 50.0 43.4 50 45 6 90

Single 47.5 41.2 59.4 51.5 60 60 6 70

31.7 15.8 27.5 13.7 39.6 19.8 34.4 17.1 40 20 35 20 8 12 70 50

AGL10A Single 40.0 34.7 50.0 43.4 50 45 6 80

Single 60.0 52.0 75.0 65.0 80 70 6 50

40.0 20.0 34.7 17.3 50.0 25.0 43.4 21.6 50 25 45 25 6 10 80 70

Single 80.0 69.3 100.0 86.6 100 90 2 100

40.0 40.0 34.7 34.7 50.0 50.0 43.4 43.4 50 50 45 45 6 6 80 80

All heaters rated single phase 208-230V 60Hz Wire length based on one way measurement with 2% voltage drop Wire size based on 60°C (90*C)copper conductor Part numbers with “H” included are for horizontal units only All models 12kW or larger feature internal circuit breakers All Fuses UL Class K general purpose

Page 28 of the Heat Controller HTV SERIES user manual — PERFORMANCE DATA HT048 Part Load
Pagina 28 · klik om te vergroten
Pagina 28

Typical Wiring Diagram HTV/HTD/HTH Units with CXM Board and ECM Fan Motor (single phase)

Heat Controller HTV SERIES — PERFORMANCE DATA HT048 Part Load diagram (page 28)
Afb. 30 · PERFORMANCE DATA HT048 Part Load
Page 29 of the Heat Controller HTV SERIES user manual — 08/2011
Pagina 29 · klik om te vergroten
Pagina 29
Heat Controller HTV SERIES — PERFORMANCE DATA HT048 Part Load diagram (page 29)
Afb. 31 · PERFORMANCE DATA HT048 Part Load
Heat Controller HTV SERIES — PERFORMANCE DATA HT048 Part Load diagram (page 29)
Afb. 32 · PERFORMANCE DATA HT048 Part Load
Heat Controller HTV SERIES — PERFORMANCE DATA HT048 Part Load diagram (page 29)
Afb. 33 · PERFORMANCE DATA HT048 Part Load
Heat Controller HTV SERIES — PERFORMANCE DATA HT048 Part Load diagram (page 29)
Afb. 34 · PERFORMANCE DATA HT048 Part Load
Heat Controller HTV SERIES — PERFORMANCE DATA HT048 Part Load diagram (page 29)
Afb. 35 · PERFORMANCE DATA HT048 Part Load
Heat Controller HTV SERIES — PERFORMANCE DATA HT048 Part Load diagram (page 29)
Afb. 36 · PERFORMANCE DATA HT048 Part Load
Heat Controller HTV SERIES — PERFORMANCE DATA HT048 Part Load diagram (page 29)
Afb. 37 · PERFORMANCE DATA HT048 Part Load

08/2011

Bronnen

Referenties en links

Pagina's waarnaar wordt verwezen in deze handleiding — fabrikant, ondersteuning en downloads.

Vraag stellen over de Heat Controller HTV SERIES

Eigenaren en ons team reageren doorgaans binnen een dag — en uw vraag helpt ook de volgende persoon.

Add your email to get notified when it’s answered — no spam, ever.

0 questions
Nog geen vragen over de Heat Controller HTV SERIES

Stel als eerste een vraag — andere eigenaren of ons team geven antwoord.

Origineel document

Heat Controller HTV SERIES handleiding-pdf

29 pagina's·6.1 MB·Warmtepomp·PDF
Klik op een bovenstaande pagina om deze hier te openen
Pagina 1 / …
100%
Pagina's laden…