TGC SERIES HIGH EFFICIENCY 13-SEER
NOMINAL SIZES 3-5 TONS
C VINTAGE



Engineering Features 4
Introduction 5
Selection Procedure 6
General Data 7-10
Performance Data 11-12
Airflow Performance 13-16
Electrical Data 17
Dimensional Data 18-20
Accessories 21-28
Typical Wiring 29-35

MODEL NOMENCLATURE - TGC SERIES
T G C
K
Heating Input (BTUH) 120 = 120,000 135 = 135,000
Drive Package K = Direct Drive
Electrical Designation 1 = 208-230 V, 1 PH, 60 Hz 4 = 460 V, 3 PH, 60 Hz 3 = 208-230 V, 3 PH, 60 Hz
Cooling Capacity (BTUH Nominal) 036 = 36,000 042 = 42,000 048 = 48,000 060 = 60,000

ENGINEERING FEATURES TGC Series Package Gas Electric Units
1. All models feature Copeland® Scroll® compressors offering maximum reliability, efficiency, and quiet operation. 2. Aluminized steel heat exchanger with in-shot burners helps eliminate corrosion. 3. Integrated blower/burner control board with built-in diagnostic capability permits on-site trouble shooting. 4. One-piece top over the indoor section with drip lip, drawn painted base pan, and 1" raised flanges for supply/return air connections provides superior water management. 5. Convertible horizontal and vertical airflow design allows maximum field flexibility and minimizes inventory requirements. 6. Standard full perimeter forkable 14 gauge baserail with lifting holes for easier maneuvering and installations. 7. Factory installed one-inch throw away filter with provisions for two-inch filter. 8. Direct drive blowers to accommodate a wide range of design conditions. 9. Easily removable filter, blower, gas heat, and compressor/control access panels permits prompt service. 10. Number and color coded wiring helps facilitate service and maintenance. 11. Common cabinet and components allows for installation flexibility and fewer parts to inventory. 12. Standard freezestat control offers evaporator coil freeze protection. 13. Optional field installed high and low pressure controls. 14. Externally mounted refrigerant gauge ports for easy service diagnostics. 15. Side and base electric power and gas connection entry helps minimize roof penetrations. 16. Quick assembly common roof curbs helps save field labor and maximize size flexibility. 17. Easy to install, plug-in, slip-in, 100% fully modulating economizers. 18. Quality powder paint finish offers long lasting protection against extreme weather conditions and is able to withstand 1000 HR salt spray test.

These quality features are included in the Heat Controller Package Gas Electric Unit

Heating Compartment Access Blower Access

Total cooling capacity 43,600 BTUH Sensible cooling capacity 34,000 BTUH Heating capacity 96,000 BTUH Condenser entering air 95°F Evaporator entering air 63°F wbt/76°F dbt Indoor air flow 1600 CFM External static pressure 0.6 in wg Required efficiency 13 SEER
Watts 635
Total capacity 47,300 BTUH Power input 3.5 kW And also, at 76°F db indoor entering air, and using the formula at the bottom of the table:
Sensible capacity 41,708 BTUH

Gross Cooling Capacity Btuh 37400 37400 37400 EER/SEER2 11.7/13 11.7/13 11.7/13 Nominal CFM/ARI Rated CFM 1200/1200 1200/1200 1200/1200 ARI Net Cooling Capacity Btuh 36000 36000 36000 Net Sensible Capacity Btuh 26400 26400 26400 Net Latent Capacity Btuh 9600 9600 9600 Net System Power kW 3.08 3.08 3.08 Heating Performance (Package Gas/Electric) 3
Heating Input Btuh 120000 120000 120000 Heating Output Btuh 94500 97200 97200 Temperature Rise ºF 50-80 50-80 50-80 AFUE (%) 80 80 80 Steady State Efficiency (%) 81 81 81 Qty of Burners 6 6 6 Qty of Stages 1 1 1 Gas Connection Pipe Size, in. .5 .5 .5 Compressor Qty/Type Outdoor Sound Rating (dB) 78 78 78 Outdoor Coil—Fin Type Tube Type Rifled Rifled Rifled Tube Size in. OD 0.375 0.375 0.375 Face Area sq. ft. 16.91 16.91 16.91 Rows / Fins per inch 1/22 1/22 1/22 Indoor Coil—Fin Type Tube Type Rifled Rifled Rifled Tube Size in. 0.375 0.375 0.375 Face Area sq. ft. 5.17 5.17 5.17 Rows / Fins per inch 2/17 2/17 2/17 Refrigerant Control TXV TXV TXV Drain Connection Qty/Size, in. 1/0.75 1/0.75 1/0.75 Outdoor Fan—Type Qty Used/Diameter in. 1/24 1/24 1/24 Drive Type/Speeds Direct/1 Direct/1 Direct/1 CFM 3680 3680 3680 Qty Motors-HP 1-1/3 1-1/3 1-1/3 Motor RPM 1075 1075 1075 Indoor Fan—Type Qty Used/Diameter in. 1/10x10 1/10x10 1/10x10 Drive Type/Speeds Direct/3 Direct/3 Direct/3 Motor Qty 1 1 1 Motor HP 1/2 1/2 1/2 Motor RPM 1075 1075 1075 Motor Frame Size 48 48 48 Filter—Type Furnished Yes Yes Yes (Qty) Size Recommended in. (2)16x25x1 (2)16x25x1 (2)16x25x1 Refrigerant Charge Oz. 93 93 93 Weights Net Weight lbs. 543 543 543 Ship Weight lbs. 550 550 550
1. Cooling performance is rated at 95ºF ambient, 80ºF/67ºF entering dry bulb/wet bulb temperatures. Gross capacity does not include the effect of fan motor heat. ARI capacity is net and includes the effect of fan motor heat. Units are suitable for operation to plus or minus 20% of nominal cfm. Units are certified and rated per ARI Standard 210/240. 2. EER/SEER are rated ARI condition and accordance with DOE test procedures. 3. Heating performance limit settings and rating data were established and approved under laboratory test conditions using American National Standard Institute standards. Ratings shown are for elevations up to 2000 feet. For elevations above 2000 feet, rating should be resuced 4% for each 1000 feet above sea level.

Gross Cooling Capacity Btuh 43000 43000 43000 EER/SEER2 11.45/13 11.45/13 11.45/13 Nominal CFM/ARI Rated CFM 1400/1450 1400/1450 1400/1450 ARI Net Cooling Capacity Btuh 41000 41000 41000 Net Sensible Capacity Btuh 30000 30000 30000 Net Latent Capacity Btuh 11000 11000 11000 Net System Power kW 3.59 3.59 3.59 Heating Performance (Package Gas/Electric) 3
Heating Input Btuh 120000 120000 120000 Heating Output Btuh 94500 97200 97200 Temperature Rise ºF 50-80 50-80 50-80 AFUE (%) 80 80 80 Steady State Efficiency (%) 81 81 81 Qty of Burners 6 6 6 Qty of Stages 1 1 1 Gas Connection Pipe Size, in. .5 .5 .5 Compressor Qty/Type Outdoor Sound Rating (dB) 78 78 78 Outdoor Coil—Fin Type Tube Type Rifled Rifled Rifled Tube Size in. OD 0.375 0.375 0.375 Face Area sq. ft. 16.91 16.91 16.91 Rows / Fins per inch 1.53/22 1.53/22 1.53/22 Indoor Coil—Fin Type Tube Type Rifled Rifled Rifled Tube Size in. 0.375 0.375 0.375 Face Area sq. ft. 5.17 5.17 5.17 Rows / Fins per inch 3/13 3/13 3/13 Refrigerant Control TXV TXV TXV Drain Connection Qty/Size, in. 1/0.75 1/0.75 1/0.75 Outdoor Fan—Type Qty Used/Diameter in. 1/24 1/24 1/24 Drive Type/Speeds Direct/1 Direct/1 Direct/1 CFM 3680 3680 3680 Qty Motors-HP 1-1/3 1-1/3 1-1/3 Motor RPM 1075 1075 1075 Indoor Fan—Type Qty Used/Diameter in. 1/10x10 1/10x10 1/10x10 Drive Type/Speeds Direct/3 Direct/3 Direct/3 Motor Qty 1 1 1 Motor HP 1/2 1/2 1/2 Motor RPM 1725 1725 1725 Motor Frame Size 48 48 48 Filter—Type Furnished Yes Yes Yes (Qty) Size Recommended in. (2)16x25x1 (2)16x25x1 (2)16x25x1 Refrigerant Charge Oz. 117 117 117 Weights Net Weight lbs. 579 579 579 Ship Weight lbs. 586 586 586
1. Cooling performance is rated at 95ºF ambient, 80ºF/67ºF entering dry bulb/wet bulb temperatures. Gross capacity does not include the effect of fan motor heat. ARI capacity is net and includes the effect of fan motor heat. Units are suitable for operation to plus or minus 20% of nominal cfm. Units are certified and rated per ARI Standard 210/240. 2. EER/SEER are rated ARI condition and accordance with DOE test procedures. 3. Heating performance limit settings and rating data were established and approved under laboratory test conditions using American National Standard Institute standards. Ratings shown are for elevations up to 2000 feet. For elevations above 2000 feet, rating should be resuced 4% for each 1000 feet above sea level.

Gross Cooling Capacity Btuh 49000 49000 49000 EER/SEER2 11.4/13.1 11.4/13.1 11.4/13.1 Nominal CFM/ARI Rated CFM 1600/1550 1600/1550 1600/1550 ARI Net Cooling Capacity Btuh 47000 47000 47000 Net Sensible Capacity Btuh 33600 33600 33600 Net Latent Capacity Btuh 13400 13400 13400 Net System Power kW 4.15 4.15 4.15 Heating Performance (Package Gas/Electric) 3
Heating Input Btuh 135000 135000 135000 Heating Output Btuh 106500 109400 109400 Temperature Rise ºF 50-80 50-80 50-80 AFUE (%) 80 80 80 Steady State Efficiency (%) 81 81 81 Qty of Burners 6 6 6 Qty of Stages 1 1 1 Gas Connection Pipe Size, in. .5 .5 .5 Compressor Qty/Type Outdoor Sound Rating (dB) 78 78 78 Outdoor Coil—Fin Type Tube Type Rifled Rifled Rifled Tube Size in. OD 0.375 0.375 0.375 Face Area sq. ft. 16.56 16.56 16.56 Rows / Fins per inch 2/22 2/22 2/22 Indoor Coil—Fin Type Tube Type Rifled Rifled Rifled Tube Size in. 0.375 0.375 0.375 Face Area sq. ft. 5.17 5.17 5.17 Rows / Fins per inch 3/15 3/15 3/15 Refrigerant Control TXV TXV TXV Drain Connection Qty/Size, in. 1/0.75 1/0.75 1/0.75 Outdoor Fan—Type Qty Used/Diameter in. 1/24 1/24 1/24 Drive Type/Speeds Direct/1 Direct/1 Direct/1 CFM 3680 3680 3680 Qty Motors-HP 1-1/3 1-1/3 1-1/3 Motor RPM 1075 1075 1075 Indoor Fan—Type Qty Used/Diameter in. 1/10x10 1/10x10 1/10x10 Drive Type/Speeds Direct/3 Direct/3 Direct/3 Motor Qty 1 1 1 Motor HP 1/2 1/2 1/2 Motor RPM 1075 1075 1075 Motor Frame Size 48 48 48 Filter—Type Furnished Yes Yes Yes (Qty) Size Recommended in. (2)16x25x1 (2)16x25x1 (2)16x25x1 Refrigerant Charge Oz. 167 167 167 Weights Net Weight lbs. 585 585 585 Ship Weight lbs. 592 592 592
1. Cooling performance is rated at 95ºF ambient, 80ºF/67ºF entering dry bulb/wet bulb temperatures. Gross capacity does not include the effect of fan motor heat. ARI capacity is net and includes the effect of fan motor heat. Units are suitable for operation to plus or minus 20% of nominal cfm. Units are certified and rated per ARI Standard 210/240. 2. EER/SEER are rated ARI condition and accordance with DOE test procedures. 3. Heating performance limit settings and rating data were established and approved under laboratory test conditions using American National Standard Institute standards. Ratings shown are for elevations up to 2000 feet. For elevations above 2000 feet, rating should be resuced 4% for each 1000 feet above sea level.

Gross Cooling Capacity Btuh 60000 60000 60000 EER/SEER2 11.6/13 11.6/13 11.6/13 Nominal CFM/ARI Rated CFM 2000/1900 2000/1900 2000/1900 ARI Net Cooling Capacity Btuh 58000 58000 58000 Net Sensible Capacity Btuh 42000 42000 42000 Net Latent Capacity Btuh 16000 16000 16000 Net System Power kW 5 5 5 Heating Performance (Package Gas/Electric) 3
Heating Input Btuh 135000 135000 135000 Heating Output Btuh 106500 109400 109400 Temperature Rise ºF 40-70 40-70 40-70 AFUE (%) 80 80 80 Steady State Efficiency (%) 81 81 81 Qty of Burners 6 6 6 Qty of Stages 1 1 1 Gas Connection Pipe Size, in. .5 .5 .5 Compressor Qty/Type Outdoor Sound Rating (dB) 83 78 78 Outdoor Coil—Fin Type Tube Type Rifled Rifled Rifled Tube Size in. OD 0.375 0.375 0.375 Face Area sq. ft. 16.56 16.56 16.56 Rows / Fins per inch 2/22 2/22 2/22 Indoor Coil—Fin Type Tube Type Rifled Rifled Rifled Tube Size in. 0.375 0.375 0.375 Face Area sq. ft. 5.17 5.17 5.17 Rows / Fins per inch 3/15 3/15 3/15 Refrigerant Control TXV TXV TXV Drain Connection Qty/Size, in. 1/0.75 1/0.75 1/0.75 Outdoor Fan—Type Qty Used/Diameter in. 1/24 1/24 1/24 Drive Type/Speeds Direct/1 Direct/1 Direct/1 CFM 3930 3930 3930 Qty Motors-HP 1-1/3 1-1/3 1-1/3 Motor RPM 1075 1075 1075 Indoor Fan—Type Qty Used/Diameter in. 1/10x10 1/10x10 1/10x10 Drive Type/Speeds Direct/3 Direct/3 Belt/Variable Motor Qty 1 1 1 Motor HP 1 1 3/4 Motor RPM 1075 1075 1725 Motor Frame Size 48 48 56 Filter—Type Furnished Yes Yes Yes (Qty) Size Recommended in. (2)16x25x1 (2)16x25x1 (2)16x25x1 Refrigerant Charge Oz. 160 160 160 Weights Net Weight lbs. 597 597 597 Ship Weight lbs. 604 604 604
1. Cooling performance is rated at 95ºF ambient, 80ºF/67ºF entering dry bulb/wet bulb temperatures. Gross capacity does not include the effect of fan motor heat. ARI capacity is net and includes the effect of fan motor heat. Units are suitable for operation to plus or minus 20% of nominal cfm. Units are certified and rated per ARI Standard 210/240. 2. EER/SEER are rated ARI condition and accordance with DOE test procedures. 3. Heating performance limit settings and rating data were established and approved under laboratory test conditions using American National Standard Institute standards. Ratings shown are for elevations up to 2000 feet. For elevations above 2000 feet, rating should be resuced 4% for each 1000 feet above sea level.
![Page 11 of the Heat Controller Gas Furnace (TGC048C-1K-135) user manual — [ ] Designates Metric Conversions](/cdn/reader/15/152ed9642243c465edf805cad7380cb7bafb085b89f94cfaed3e341ebf3d91ca/images/page-11.webp?w=400)


DR —Depression ratio dbE —Entering air dry bulb wbE—Entering air wet bulb
Total —Total capacity x 1000 BTUH Sens —Sensible capacity x 1000 BTUH Power—KW input
capacity from the table by adding [1.10 x CFM x (1 – DR) x (dbE – 80)].
![Page 12 of the Heat Controller Gas Furnace (TGC048C-1K-135) user manual — [ ] Designates Metric Conversions](/cdn/reader/15/152ed9642243c465edf805cad7380cb7bafb085b89f94cfaed3e341ebf3d91ca/images/page-12.webp?w=400)


DR —Depression ratio dbE —Entering air dry bulb wbE—Entering air wet bulb
Total —Total capacity x 1000 BTUH Sens —Sensible capacity x 1000 BTUH Power—KW input
capacity from the table by adding [1.10 x CFM x (1 – DR) x (dbE – 80)].
![Page 13 of the Heat Controller Gas Furnace (TGC048C-1K-135) user manual — [ ] Designates Metric Conversions](/cdn/reader/15/152ed9642243c465edf805cad7380cb7bafb085b89f94cfaed3e341ebf3d91ca/images/page-13.webp?w=400)
0.8 [.20]
0.1 [.02] 0.2 [.05] 0.3 [.07] 0.4 [.10] 0.5 [.12] 0.6 [.15] 0.7 [.17]
Low CFM 1210 [571] 1193 [563] 1175 [555] 1155 [545] 1125 [531] 1075 [507] 1015 [479]
Med CFM 1515 [715] 1500 [708] 1475 [696] 1450 [684] 1405 [663] 1350 [637] 1275 [602]
High CFM 1680 [793] 1650 [779] 1625 [767] 1580 [746] 1530 [722] 1460 [689] 1390 [656]
Low CFM 1210 [571] 1193 [563] 1175 [555] 1155 [545] 1125 [531] 1075 [507] 1015 [479]
Med CFM 1515 [715] 1500 [708] 1475 [696] 1450 [684] 1405 [663] 1350 [637] 1275 [602]
High CFM 1680 [793] 1650 [779] 1625 [767] 1580 [746] 1530 [722] 1460 [689] 1390 [656]
Low CFM 1210 [571] 1193 [563] 1175 [555] 1155 [545] 1125 [531] 1075 [507] 1015 [479]
Med CFM 1515 [715] 1500 [708] 1475 [696] 1450 [684] 1405 [663] 1350 [637] 1275 [602]
High CFM 1680 [793] 1650 [779] 1625 [767] 1580 [746] 1530 [722] 1460 [689] 1390 [656]
Low CFM 1575 [743] 1536 [725] 1496 [706] 1457 [688] 1417 [669] 1377 [650] 1338 [631]
Med CFM 1985 [937] 1954 [922] 1919 [906] 1876 [885] 1824 [861] 1759 [830] 1679 [792]
High CFM 2431 [1147] 2372 [1119] 2306 [1088] 2228 [1051] 2138 [1009] 2032 [959] 1907 [900]
Watts 970 981 964 926 872 806 736
Watts 450 400 395 385 380 375 370
Watts 525 515 510 505 490 475 460
Watts 650 640 630 610 580 560 545
Low 80,000 [23.45] Watts 450 400 395 385 380 375 370
Watts 525 515 510 505 490 475 460
Watts 650 640 630 610 580 560 545
Low 80,000 [23.45] Watts 450 400 395 385 380 375 370
Watts 525 515 510 505 490 475 460
Watts 650 640 630 610 580 560 545
Low 100,000 [29.31] Watts 297 314 330 347 364 381 397
Watts 535 553 574 593 606 609 599
CFM [L/s] Air Delivery/RPM/Watts—208 Volts Blower Size/
External Static Pressure—Inches W.C. [kPa]
10x10 1/2 HP [373] 3 Speed Motor
10x10 1/2 HP [373] 3 Speed Motor
10x10 1/2 HP [373] 3 Speed Motor
10x10 1 HP [745] 3 Speed Motor
TGC048 Med 1400/1800
80,000 [23.45]
Med 120,000 [35.17]
Med 120,000 [35.17]
100,000 [29.31]
135,000 [39.56]
High 135,000 [39.56]
Unit Model Motor Speed
![Page 14 of the Heat Controller Gas Furnace (TGC048C-1K-135) user manual — [ ] Designates Metric Conversions](/cdn/reader/15/152ed9642243c465edf805cad7380cb7bafb085b89f94cfaed3e341ebf3d91ca/images/page-14.webp?w=400)
0.8 [.20]
0.1 [.02] 0.2 [.05] 0.3 [.07] 0.4 [.10] 0.5 [.12] 0.6 [.15] 0.7 [.17]
Low CFM 1400 [661] 1375 [649] 1360 [642] 1335 [630] 1305 [616] 1255 [592] 1210 [571]
Med CFM 1685 [795] 1620 [765] 1580 [746] 1550 [732] 1500 [708] 1430 [675] 1350 [637]
1660 [783] 1580 [746] 1500 [708]
Low CFM 1400 [661] 1375 [649] 1360 [642] 1335 [630] 1305 [616] 1255 [592] 1210 [571]
Med CFM 1685 [795] 1620 [765] 1580 [746] 1550 [732] 1500 [708] 1430 [675] 1350 [637]
High CFM 1870 [883] 1830 [864] 1790 [845] 1730 [816] 1660 [783] 1580 [746] 1500 [708]
Low CFM 1400 [661] 1375 [649] 1360 [642] 1335 [630] 1305 [616] 1255 [592] 1210 [571]
Med CFM 1685 [795] 1620 [765] 1580 [746] 1550 [732] 1500 [708] 1430 [675] 1350 [637]
High CFM 1870 [883] 1830 [864] 1790 [845] 1730 [816] 1660 [783] 1580 [746] 1500 [708]
Low CFM 1575 [743] 1536 [725] 1496 [706] 1457 [688] 1417 [669] 1377 [650] 1338 [631]
Med CFM 1985 [937] 1954 [922] 1919 [906] 1876 [885] 1824 [861] 1759 [830] 1679 [792]
2431 [1147] 2372 [1119] 2306 [1088] 2228 [1051] 2138 [1009] 2032 [959] 1907 [900]
Watts 470 460 455 450 440 435 425
Watts 635 600 580 570 550 535 505
Watts 780 760 740 700 660 635 600
600 580 570 550 535 505
Watts 780 760 740 700 660 635 600
Low 80,000 [23.45] Watts 470 460 455 450 440 435 425
Watts 635 600 580 570 550 535 505
Watts 780 760 740 700 660 635 600
Low 100,000 [29.31] Watts 297 314 330 347 364 381 397
Watts 535 553 574 593 606 609 599
Watts 970 981 964 926 872 806 736
CFM [L/s] Air Delivery/RPM/Watts—230 Volts Blower Size/
External Static Pressure—Inches W.C. [kPa]
Low 80,000 [23.45] Watts 470 460 455 450 440 435
High CFM 1870 [883] 1830 [864] 1790 [845] 1730 [816]
10x10 1/2 HP [373] 3 Speed Motor
10x10 1/2 HP [373] 3 Speed Motor
10x10 1/2 HP [373] 3 Speed Motor
10x10 1 HP [745] 3 Speed Motor
80,000 [23.45]
120,000 [35.17]
120,000 [35.17] Med
100,000 [29.31] Med
135,000 [39.56] High
135,000 [39.56] High
![Page 15 of the Heat Controller Gas Furnace (TGC048C-1K-135) user manual — [ ] Designates Metric Conversions](/cdn/reader/15/152ed9642243c465edf805cad7380cb7bafb085b89f94cfaed3e341ebf3d91ca/images/page-15.webp?w=400)
0.8 [.20] Cool Heat
0.1 [.02] 0.2 [.05] 0.3 [.07] 0.4 [.10] 0.5 [.12] 0.6 [.15] 0.7 [.17]
Low CFM 1400 [661] 1375 [649] 1360 [642] 1335 [630] 1305 [616] 1255 [592] 1210 [571]
Med CFM 1685 [795] 1620 [765] 1580 [746] 1550 [732] 1500 [708] 1430 [675] 1350 [637]
1660 [783] 1580 [746] 1500 [708]
Low CFM 1400 [661] 1375 [649] 1360 [642] 1335 [630] 1305 [616] 1255 [592] 1210 [571]
Med CFM 1685 [795] 1620 [765] 1580 [746] 1550 [732] 1500 [708] 1430 [675] 1350 [637]
High CFM 1870 [883] 1830 [864] 1790 [845] 1730 [816] 1660 [783] 1580 [746] 1500 [708]
Low CFM 1400 [661] 1375 [649] 1360 [642] 1335 [630] 1305 [616] 1255 [592] 1210 [571]
Med CFM 1685 [795] 1620 [765] 1580 [746] 1550 [732] 1500 [708] 1430 [675] 1350 [637]
High CFM 1870 [883] 1830 [864] 1790 [845] 1730 [816] 1660 [783] 1580 [746] 1500 [708]
Watts 470 460 455 450 440 435 425
Watts 635 600 580 570 550 535 505
Watts 780 760 740 700 660 635 600
600 580 570 550 535 505
Watts 780 760 740 700 660 635 600
Watts 470 460 455 450 440 435 425
Watts 635 600 580 570 550 535 505
Watts 780 760 740 700 660 635 600
CFM [L/s] Air Delivery/RPM/Watts—460 Volts Blower Size/
External Static Pressure—Inches W.C. [kPa]
Watts 470 460 455 450 440 435
High CFM 1870 [883] 1830 [864] 1790 [845] 1730 [816]
10x10 1/2 HP [373] 3 Speed Motor
10x10 1/2 HP [373] 3 Speed Motor
10x10 1/2 HP [373] 3 Speed Motor
80,000 [23.45]
120,000 [35.17]
80,000 [23.45]
120,000 [35.17]
100,000 [29.31]
135,000 [39.56]
Unit Model Motor Speed
![Page 16 of the Heat Controller Gas Furnace (TGC048C-1K-135) user manual — [ ] Designates Metric Conversions](/cdn/reader/15/152ed9642243c465edf805cad7380cb7bafb085b89f94cfaed3e341ebf3d91ca/images/page-16.webp?w=400)
1400 [661] — 780 370 815 385 875 425 930 460 970 490 1030 540 1065 570 1105 595 1150 615 1195 645 1235 660 1300 705 1340 745 1500 [708] — 795 405 840 415 895 440 945 500 995 540 1045 595 1080 615 1135 650 1165 675 1215 700 1255 735 1320 775 1355 805 1600 [755] — — 780 390 805 425 870 470 915 510 965 560 1015 600 1060 640 1105 680 1145 705 1180 730 1225 750 1275 790 1340 840 1365 880 1700 [802] — — 795 450 840 490 895 530 940 570 990 605 1035 640 1075 680 1120 725 1160 755 1200 790 1245 815 1300 855 1355 905 1375 940 1800 [850] 780 455 815 470 870 540 915 560 965 615 1010 660 1055 710 1100 760 1140 785 1175 810 1225 850 1260 880 1320 930 1365 985 1390 1020 1900 [897] 800 485 850 530 895 590 945 640 995 675 1035 720 1070 775 1120 810 1160 850 1200 890 1245 915 1290 960 1335 1000 1375 1050 1405 1100 2000 [944] 830 550 880 605 930 655 970 700 1015 730 1055 790 1105 830 1145 875 1180 910 1225 950 1260 980 1320 1035 1350 1075 1385 1120 — —
1.5 [.37]
RPM W RPM W RPM W RPM W RPM W RPM W RPM W RPM W RPM W RPM W RPM W RPM W RPM W RPM W RPM W
2100 [991] 860 615 915 655 955 705 1005 760 1040 820 1090 870 1130 910 1170 950 1210 995 1250 1020 1290 1060 1335 1100 1370 1150 1400 1200 — —
2500 [1179] 1015 910 1040 935 1095 1040 1145 1100 1170 1140 1200 1175 1260 1215 1305 1270 1360 1350 1400 1395 — 1225 1140 1260 1175 1300 1210 1340 1255 1370 1315 1400 1375 —
1.4 [.35]
2200 [1038] 895 680 945 735 995 780 1030 830 1060 880 1120 940 1155 980 1195 1020 1240 1055 1275 1100 1320 1140 1360 1180 1385 1225 — —
2300 [1085] 940 755 975 795 1015 830 1065 910 1100 965 1150 105 1180 1050 1225 1095 1265 1125 1310 1175 1350 1230 1375 1260 1405 1320 —
1.3 [.32]
1.2 [.30]
1.1 [.27]
1.0 [.25]
External Static Pressure—Inches of Water [kPa]
0.9 [.22]
0.8 [.20]
0.7 [.17]
0.6 [.15]
Motor H.P. [W] 3/4 [559] Blower Sheave 6.4" Pitch Diameter Motor Sheave 2.8"-3.8" Pitch Diameter—Adj. Turns Open 0 1 2 3 4 5 6 RPM 1095 1040 995 940 890 835 780
0.5 [.12]
0.4 [.10]
Capacity 5 Ton [17.6 kW]—13 SEER Voltage 460—3 Phase
0.3 [.07]
0.2 [.05]
0.1 [.02]

ELECTRICAL DATA
Unit Operating Voltage Range 187-253 187-253 414-506 187-253 187-253 414-506 Minimum Circuit Ampacity 24/24 18/18 11 30/30 21/21 11 Max. Overcurrent Protection Device Size 35/35 25/25 15 45/45 30/30 15
Quantity 1 Volts 208/230 208/230 460 208/230 208/230 460 Phase 1 3 3 1 3 3 HP 3 1/2 3 1/2 3 1/2 RPM 3450 Amps (RLA) 14.4/14.4 9.6/9.6 5.8 19.2/19.2 12.2/12.2 5.8 Amps (LRA) 77/77 88/88 38 104/104 88/88 44 Condenser Fan Motor
Quantity 1 Volts 208/230 208/230 460 208/230 208/230 460 Phase 1 HP 1/3 Amps (FLA) 1.5 1.5 1.0 1.5 1.5 1.0 Amps (LRA) 3.0 3.0 1.9 3.0 3.0 1.9 Evaporator Fan Motor
Quantity 1 Volts 208/230 208/230 460 208/230 208/230 460 Phase 1 HP 1/2 Amps (FLA) 4.0 4.0 2.0 4.0 4.0 2.0 Amps (LRA) 6.7 6.7 3.6 6.7 6.7 3.6
Unit Operating Voltage Range 187-253 187-253 414-506 187-253 187-253 414-506 Minimum Circuit Ampacity 31/31 21/21 11 42/42 30/30 12 Max. Overcurrent Protection Device Size 50/50 30/30 15 60/60 40/40 15
Quantity 1 Volts 208/230 208/230 460 208/230 208/230 460 Phase 1 3 3 1 3 3 HP 4 4 4 5 5 5 RPM 3450 Amps (RLA) 20.2/20.2 12.2/12.2 6.1 25.3/25.3 15.4/15.4 7.1 Amps (LRA) 137/137 80.8/80.8 41 141/141 110/110 52 Condenser Fan Motor
Quantity 1 Volts 208/230 208/230 460 208/230 208/230 460 Phase 1 HP 1/3 Amps (FLA) 1.5 1.5 1.0 2.2 2.2 1.0 Amps (LRA) 3.0 3.0 1.9 4.9 4.9 1.9 Evaporator Fan Motor
Quantity 1 Volts 208/230 208/230 460 208/230 208/230 460 Phase 1 3 HP 1/2 1/2 1/2 1 1 3/4 Amps (FLA) 4.0 4.0 2.0 7.6 7.6 1.6 Amps (LRA) 6.7 6.7 3.6 0 0 8.4

TGR036C-TGR060C MODELS
UNIT DIMENSIONS PACKAGE GAS ELECTRIC UNITS



UNIT DIMENSIONS PACKAGE GAS ELECTRIC UNITS


![Page 20 of the Heat Controller Gas Furnace (TGC048C-1K-135) user manual — Recommended Clearance in. [mm] Location](/cdn/reader/15/152ed9642243c465edf805cad7380cb7bafb085b89f94cfaed3e341ebf3d91ca/images/page-20.webp?w=400)
WEIGHTS
Accessory
lbs [kg] lbs [kg] Shipping Operating
Economizer with Single Enthalapy 70 [32] Power Exhaust 19 [9] Fresh Air Damper (Manual) 11 [5] 9 [4] 16 [7] 60 [27]
381/4 [972] 253/4 [654] 3-5 [10.6-17.6] Capacity Tons [kW] A in. [mm] B in. [mm]
Fresh Air Damper (Motorized) 13 [6] Roof Curb 14" 92 [42] 88 [40] 11 [5]
Roof Curb 24" 108 [49] 104 [47] Concentric Diffuser 18" Flush 37 [17] 26 [12] Concentric Diffuser 20" Flush 54 [24] 42 [19]
Corner Weights by Percentage
A B C D 22% 27% 23% 28%
3-5 [10.6-17.6]
Side Discharge Concentric Diffuser RXRN-FA60 35 [16] 20 [9] Side Discharge Concentric Diffuser RXRN-FA65 55 [25] 40 [18]
CLEARANCES (3 to 5 Ton [10.6 to 17.6 kW] Models) The following minimum clearances are recommended for proper unit performance and serviceability.
![Heat Controller Gas Furnace (TGC048C-1K-135) — Capacity Tons [kW] diagram (page 20)](/cdn/reader/15/152ed9642243c465edf805cad7380cb7bafb085b89f94cfaed3e341ebf3d91ca/images/rimg-9.webp)
48 [1219] A - Front 18 [457] B - Condenser Coil 12 [305] C - Duct Side 36 [914] D - Evaporator End 60 [1524] E - Above
*Without Economizer. 57" [1448 mm] With Economizer
![Heat Controller Gas Furnace (TGC048C-1K-135) — Recommended Clearance in. [mm] Location diagram (page 20)](/cdn/reader/15/152ed9642243c465edf805cad7380cb7bafb085b89f94cfaed3e341ebf3d91ca/images/rimg-10.webp)

ACCESSORY EQUIPMEN TFIELD INSTALLED
Accessory Model No.
3 to 5 Ton
Roofcurb 14" RXKG-BAD14 Roofcurb 24" RXKG-BAD24
Economizer with Single Enthalpy ➁ RXRD-KECM3
Dual Enthalpy Kit RXRX-AV02 CO2 Sensor Only RXRX-AR02 Power Exhaust RXRX-BFF04C
Fresh Air Damper Manual RXRF-FBA1 Fresh Air Damper Motorized RXRF-FBB1 Rectangular to Round 18" Duct Adapters for Concentric Diffuser RXMC-CB03
Rectangular to Round 20" Duct Adapters for Concentric Diffuser RXMC-CB04
Concentric Diffuser 18" Step RXRN-FA60 Concentric Diffuser 18" Flush RXRN-FA70
Rectangular to Round 16" Side RXMC-BB01 Louver Kit (3 Sides) RXRX-AAD01B
High Pressure RXAB-A02 Low Pressure RXAC-A02
Low Ambient Control to 0°F [-18°C] RXRZ-A18
LP Conversion Kits for use with
White Rodgers Gas Valve ➀ RXGJ-EP84W
LP Conversion Kits for use with
Honeywell Gas Valve ➀ RXGJ-EP85H
Canadian High Altitude Kit
(for Natural Gas Only) ➀ RXRX-AH01
*Voltage 1 = 208/230 VAC-1PH-60HZ 4 = 460 VAC-3PH-60HZ 3 = 208/230 VAC-3PH-60HZ NOTES: ➀ If a particular unit is to be converted to operate on LP (propane) for elevations above 2000 ft. in Canada, the existing Natural Gas to LP Conversion Kits for the
subject models already contain the necessary orifices and instructions to de-rate the input for 2000-4500 ft. Canadian applications. ➁ Economizer is designed for downflow or horizontal applications.
Time Delay RXMD-B01


I This roofcurb design can be utilized on
3 through 5 ton models.
24" for ALL models.
I Quick assembly corners for simple and fast assembly.
“Thru the Curb” electrical connection opening provided on the unit base pan.
I 2" x 4" Nailer provided.
I Insulating panels provided.
with Roofcurb.
I Packaged for easy field assembly.
Roofcurb Model Height of Curb RXKG-BAD14 14" [356 mm] RXKG-BAD24 24" [610 mm]




ECONOMIZERS
RXRX-AV02— D ual Enthalpy Kit
RXRX-AR02—CO 2 Sensor

I Field installed accessory
I Gear Driven Direct Drive Actuator
I Fully Modulating (0-100%)
I Low Leakage Dampers
I Horizontal or Downflow Applications
I Slip-In Design for Easy Installations
I Plug-In Polarized 9-pin Electrical Connections
I Pre-configuring—No Field Adjustments Necessary
I Standard Barometric Relief Damper Provided
I Single Enthalpy with Dual Enthalpy upgrade kit
I CO 2 Input Sensor Available
I Economizer slips in complete for downflow or
horizontal duct applications
I Field assembled hood ships with Economizer
I Optional Remote minimum position
I Field installed power exhaust available.


INTEGRAL POWER EXHAUST FOR ECONOMIZER

I For Honeywell economizer.
I Downflow or horizontal applications.
with disconnect.
power exhaust at 95% outside air position.
I Polarized plug connects power exhaust relay to economizer.
Model No. No. of Fans Volts Phase Watts (ea.)
FLA (ea.) LRA (ea.)
RXRX-BFF04C 1 208-230 1 240 2600 1700 1.06 1.9 CFM ➀ RPM
➀ CFM is at 0" W.C. external static pressure.
FRESH AIR DAMPER
Illustration ST-A0903-01

DUCT ADAPTERS
Rectangular to Round Transitions (Downflow)
RXMC-CB03 sizes available 18" fit all units. Drops into and secures to RXKG- Series Roofcurbs. For use with Concentric Diffusers.


SIDE DISCHARGE CONCENTRIC DIFFUSER

DIMENSIONAL DATA
Model No. A B C D E F G H I J K Duct Size
RXRN-FA60 475/8" [1210 mm]
235/8" [600 mm]
113/8" [289 mm]
211/2" [546 mm]
451/2" [1156 mm]
221/2" [572 mm]
111/2" [292 mm]
103/4" [273 mm]
451/2" [1156 mm]
211/2" [546 mm]
71/8" [181 mm] 18RD
Throw
Neck
Jet Vel.
Feet
Vel.
1000 [472] .14 10-17 351 351 20 1200 [566] .17 11-18 421 421 20 1400 [661] .20 12-19 491 491 20 1600 [755] .24 12-20 561 561 20 1800 [850] .30 13-21 632 632 20 2000 [944] .36 14-23 702 702 20 2200 [1038] .40 16-25 772 772 20

FLUSH MOUNT CONCENTRIC DIFFUSER

DIMENSIONAL DATA
RXRN-FA70 475/8" [1210 mm]
235/8" [600 mm]
131/2" [343 mm]
221/2" [572 mm]
111/4" [286 mm]
101/2" [267 mm] 18RD
Throw
Neck
Jet Vel.
Feet
Vel.
1000 [472] .14 15-20 391 694 20 1200 [566] .17 16-22 469 833 25 1400 [661] .20 17-24 547 972 30 1600 [755] .24 18-25 625 1111 30 1800 [850] .30 20-28 703 1250 35 2000 [944] .36 21-29 781 1389 40 2200 [1038] .40 22-30 859 1528 40
21" [533 mm] · 45" [1143 mm]

THERMOSTATS GAS/ELECTRIC
Single Stage Cool w/o Economizer Two Stage Cool w/Economizer Maple Chase—Model #0970 Honeywell—Model #T7300-A1005 Honeywell—Model #T8602C Honeywell—Model #T874D-1959 Maple Chase—Model #0960 White Rodgers—Model #1F91-59 Robertshaw—Model #CM64A-USAJ













subject to change without notice.

www.heatcontroller.com
04/04/07