Gebruiksaanwijzing /service van het product H-IM-FL1A van de fabrikant Heatcraft Refrigeration Products
Ga naar pagina of 24
H-IM-FL1A December , 2004 Part No. 25006901 Installation and Operation Manual T able of Contents General Safety Information ...................................................... 2 Inspection ...........................................................
2 © 2004, Heatcraft Refrigeration Products LLC General Safety Information 1. Installation and maintenance to be performed only by qualified personnel who are familiar with this type of equipment. 2. Some units are pressurized with dry air or inert gas.
3 The most important consideration which must be taken into account when deciding upon the location of air-cooled equipment is the provision for a supply of ambient air to the condenser , and removal of heated air from the condensing unit or remote condenser area.
4 Figure 2. Solid Mount for Mobile or Deep Sump Application. Condensing Unit Rigging and Mounting Rigging holes are provided on all units. Caution should be exercised when moving these units. T o prevent damage to the unit housing during rigging, cables or chains used must be held apart by spacer bars.
5 Suction Filters, Driers, Sight Glasses There are two types of suction and liquid filter/driers used on Heatcraft Refrigeration Products units. Replaceable core and/or sealed units are used, dependent upon the option package ordered.
6 Mineral Oils The BR and Scroll compressors use Sontex 200, a “white oil”. This oil is not suitable for low temperature applications nor is it available through the normal refrigeration wholesalers.
7 Phase Loss Monitor The combination phase sequence and loss monitor relay protects the system against phase loss (single phasing), phase reversal (improper sequence) and low voltage (brownout). When phase sequence is correct and full line voltage is present on all three phases, the relay is energized as the normal condition indicator light glows.
8 Liquid Lines Liquid lines should be sized for a minimum pressure drop to prevent “flashing”. Flashing in the liquid lines would create additional pressure drop and poor expansion valve operation.
9 T able 5. Equivalent Feet of Pipe Due to V alve and Fitting Friction Copper T uber, O.D., Type “L” 1/2 5/8 7/8 1 1/8 1 3/8 1 5/8 2 1/8 2 5/8 3 1/8 3 5/8 4 1/8 5 1/8 6 1/8 Globe V alve (Open) 14 .
10 T able 6. Weight of Refrigerants in Copper Lines During Operation (Pounds per 100 lineal feet of type “L” tubing). Line Size Suction Line at Suction T emperature O.D. Liquid Hot Gas in Inches Refrigerant Line Line -40˚F -20˚F 0˚F +20˚F +40˚F 134a 4.
1 1 Line Insulation After the final leak test, refrigerant lines exposed to high ambient conditions should be insulated to reduce heat pickup and prevent the formation of flash gas in the liquid lines. Suction lines should be insulated with 3/4" wall Armstrong “Armaflex” or equal.
12 Field Wiring W ARNING: All wiring must be done in accordance with applicable codes and local ordinances. The field wiring should enter the areas as provided on the unit. The wiring diagram for each unit is located on the inside of the electrical panel door .
13 NOTE: All adjustable controls and valves must be field adjusted to meet desired operation. There are no factory preset controls or valve adjustments. System Balancing - Compressor Superheat IMPORT ANT : In order to obtain the maximum capacity from a system, and to ensure trouble- free operation, it is necessary to balance each and every system.
14 T able 7. System T roubleshooting Chart PROBLEM POSSIBLE CAUSES POSSIBLE CORRECTIVE STEPS Compressor will not run 1. Main switch open. 1. Close switch. 2. Fuse blown. 2. Check electrical circuits and motor winding for shorts or grounds. Investigate for possible overloading.
15 Preventive Maintenance Air Cooled Condensing Units Quarterly 1) Visually inspect unit • Look for signs of oil stains on interconnection piping and condenser coil. Pay close attention to areas around solder joints, building penetrations and pipe clamps.
16 Wiring Diagram for BACU51D2CHPQ 208V 14 AWG COMPRESSOR 1 M7 M8 FAN ARRANGEMENT COMP- 1 ALL COMPRESSORS THERMALLY PROTECTED COMPRESSOR 3 SEE COMPRESSOR ELECTRIC BOX COVERS FOR PROPER CONNECTION M4 M.
17 Wiring Diagram for BACU59D2CHPQ 208V 14 AWG COMPRESSOR 1 M7 M8 FAN ARRANGEMENT COMP-1 ALL COMPRESSORS THERMALLY PROTECTED COMPRESSOR 3 SEE COMPRESSOR ELECTRIC BOX COVERS FOR PROPER CONNECTION M4 M3.
18 Control Circuit Wiring Diagram for BACU51 and BACU59.
19 Submittal.
20 Submittal.
21 System Reference Data The following information should be filled out and signed by Refrigeration Installation Contractor at time of start-up. Date System Installed: _______________________________.
22 Notes.
23 Notes.
H EA TCRAFT R EFRIGERA TION P RODUCTS LLC 2175 W EST P ARK P LACE B OULEV ARD • S TONE M OUNT AIN , GA 30087 USA 770-465-5600 • F AX : 770-465-5990 WWW . HEA TCRAFTRPD . COM S inc e produc t im provem e nt i s a c ontinui n g ef for t , we re s er v e th e ri g ht to mak e c han g e s in sp e c i fi c ation s wi tho u t n o tice .
Een belangrijk punt na aankoop van elk apparaat Heatcraft Refrigeration Products H-IM-FL1A (of zelfs voordat je het koopt) is om de handleiding te lezen. Dit moeten wij doen vanwege een paar simpele redenen:
Als u nog geen Heatcraft Refrigeration Products H-IM-FL1A heb gekocht dan nu is een goed moment om kennis te maken met de basisgegevens van het product. Eerst kijk dan naar de eerste pagina\'s van de handleiding, die je hierboven vindt. Je moet daar de belangrijkste technische gegevens Heatcraft Refrigeration Products H-IM-FL1A vinden. Op dit manier kan je controleren of het apparaat aan jouw behoeften voldoet. Op de volgende pagina's van de handleiding Heatcraft Refrigeration Products H-IM-FL1A leer je over alle kenmerken van het product en krijg je informatie over de werking. De informatie die je over Heatcraft Refrigeration Products H-IM-FL1A krijgt, zal je zeker helpen om een besluit over de aankoop te nemen.
In een situatie waarin je al een beziter van Heatcraft Refrigeration Products H-IM-FL1A bent, maar toch heb je de instructies niet gelezen, moet je het doen voor de hierboven beschreven redenen. Je zult dan weten of je goed de alle beschikbare functies heb gebruikt, en of je fouten heb gemaakt die het leven van de Heatcraft Refrigeration Products H-IM-FL1A kunnen verkorten.
Maar de belangrijkste taak van de handleiding is om de gebruiker bij het oplossen van problemen te helpen met Heatcraft Refrigeration Products H-IM-FL1A . Bijna altijd, zal je daar het vinden Troubleshooting met de meest voorkomende storingen en defecten #MANUAl# samen met de instructies over hun opplosinge. Zelfs als je zelf niet kan om het probleem op te lossen, zal de instructie je de weg wijzen naar verdere andere procedure, bijv. door contact met de klantenservice of het dichtstbijzijnde servicecentrum.