Gebruiksaanwijzing /service van het product DSE-5 THRU DSE-120 van de fabrikant A.O. Smith
Ga naar pagina of 24
1 • Installation • Operation • Maintenance • Checklist • Limited W arranty CAUTION TEXT PRINTED OR OUTLINED IN RED CONT AINS INFORMA TION RELA TIVE TO YOUR SAFETY . PLEASE READ THOROUGHL Y BEFORE INST ALLING AND USING THIS APPLIANCE. KEEP THIS MANUAL WITH THE HEA TER FOR FUTURE REFERENCE.
2 ST ANDARD BTU/ 3 0 ° 4 0 ° 5 0 ° 6 0 ° 7 0 ° 8 0 ° 9 0 ° 100° 1 10° 120° 130° 140° KW I N PU T HOUR 3 10,239 41 31 24 20 17 15 13 12 1 1 10 10 9 6 20,478 82 62 49 41 35 31 27 25 22 21 1 .
3 CONTENTS P AGE ROUGH-IN-DIMENSIONS . . . . . . . . . . . . . . . . ...................... 2 RECOVERY CAP ACITY ....................................... 2 FOREWORD ......................................................... 3 APPROV ALS ................
4 GETTING T O KNOW YOUR W A TER HEA TER Below is an illustration of the water heater with its features called out. The text of this manual will refer to the items shown.
5 GENERAL SAFETY INFORMA TION INSULA TION BLANKETS Insulation blankets available to the general public for external use on electric water heaters are not approved for use on your A.O. Smith water heater . The purpose of an insulation blanket is to reduce the standby heat loss encountered with storage tank water heaters.
6 RELIEF DEVICES An unplugged 3/4” relief valve opening is provided for installing temperature and pressure relief valve. CAUTION: TO REDUCE THE RISK OF EXCESSIVE PRESSURES AND TEMPERA TURE IN THIS .
7 PIPING DIAGRAM ONE OR TWO TEMPERA TURE - ONE HEA TER ONE OR TWO TEMPERA TURE - TWO HEA TER DANGER : TEMPERA TURE SETTING SHOULD NOT EXCEED SAFE USE TEMPERA TURE A T FIXTURES.
8 ONE OR TWO TEMPERA TURE - THREE HEA TERS ONE OR TWO TEMPERA TURE - FOUR HEA TERS CAUTION: IF BUILDING COLD W A TER SUPPL Y HAS A BACK-FLOW PREVENTER, CHECK V AL VE OR W A TER METER WITH CHECK V AL VE, PROVISIONS FOR THERMAL EXP ANSION OF W A TER IN THE HOT W A TER SYSTEM MUST BE PROVIDED.
9 MEDIUM TEMPERA TURE - ONE HEA TER VERTICAL STORAGE T ANK MEDIUM TEMPERA TURE - ONE HEA TER HORIZONT AL STORAGE T ANK *PIPE RELIEF V AL VE TO OPEN DRAIN. †T ANK TEMPERA TURE CONTROL SET A T DESIRED TEMPERA TURE (MAX. 170°). HEA TER THERMOST A T SET A T LEAST 5° HIGHER.
10 MEDIUM TEMPERA TURE - TWO HEA TERS HORIZONT AL STORAGE T ANK MEDIUM TEMPERA TURE - TWO HEA TERS VERTICAL ST ORAGE T ANK RETURN LINE FROM FIXTURE CIRCULA TING LOOP (IF USED) SHOULD CONNECT TO ANY OPENING NEAR BOTTOM OF T ANK. * PIPE RELIEF V A L VE TO OPEN DRAIN.
11 MEDIUM TEMPERA TURE - THREE HEA TERS HORIZONT AL ST ORAGE T ANK MEDIUM TEMPERA TURE - THREE HEA TERS VERTICAL STORAGE T ANK * PIPE RELIEF V AL VE TO OPEN DRAIN † T ANK TEMPERA TURE CONTROL SET A T DESIRED TEMPERA TURE (MAX. 170°). HEA TER THERMOST A T SET A T LEAST 5° HIGHER.
12 MEDIUM TEMPERA TURE - FOUR HEA TERS HORIZONT AL STORAGE T ANK MEDIUM TEMPERA TURE - FOUR HEA TERS VERTICAL STORAGE T ANK CAUTION: IF BUILDING COLD WA TER SUPPL Y HAS A BACK-FLOW PREVENTER, CHECK V A LVE OR W A TER METER WITH CHECK V AL VE, PROVISIONS FOR THERMAL EXP ANSION OF W A TER IN THE HOT W A TER SYSTEM MUST BE PROVIDED.
13 ELECTRICAL GENERAL The installation must conform to these instructions, the local code authority having jurisdiction, and the requirements of the power company .
14 AMPERAGE T ABLE/OVERCURRENT PROTECTION This table provides the total connected heating element load in amperes for branch circuit conductor and over current protection sizing. Single-phase heaters are two wire circuits. Three-phase heaters are three wire circuits.
15 SMALL COMMERCIAL WIRE DIAGRAM 208-240V / 3PH SMALL COMMERCIAL WIRE DIAGRAM 208-240V / 3-1PH.
16 3-1 PHASE CONVERSIONS In the case where the unit is phase convertible and it has only one contactor , jumper wires (provided) must be added according to the phase of the supply voltage. See the diagram below . For single-phase connection, jumpers A-C and B-D must be added.
17 SMALL COMMERCIAL WIRE DIAGRAM SINGLE PHASE SMALL COMMERCIAL WIRE DIAGRAM 300-600V / 3PH.
18 OPERA TION GENERAL Never operate the heating elements without being certain the water heater is filled with water , and a temperature and pressure relief valve is installed in the relief valve opening. FILLING 1. T urn off the electrical disconnect switch.
19 MAINTENANCE Always close the front access door after making a temperature adjustment. T urn on electricity . DRAINING The water heater must be drained if it is to be shut down and exposed to freezing temperatures. Maintenance and service procedures may also require draining the heater .
20 5. Remove the bolts from each element. 6. Remove the elements from the openings. • Use a twisting, pulling action to remove elements scaled beyond size of the tank openings. • Brush loose scale from elements. 7. Lime scale removal. • Place limed ends of heating elements into UN•LIME delimer and allow scale to dissolve.
21 When such a condition is encountered, local codes or inspection agency should be consulted to determine which system is acceptable in your area. These may consist of: • Installation of a second relief valve set to lower than the primary safety relief valve.
22 LEAKAGE CHECKPOINTS INSTRUCTIONS: USE THIS ILLUSTRA TION AS A GUIDE WHEN CHECKING FOR SOURCES OF W A TER LEAKAGE. YOU OR YOUR DEALER MA Y BE ABLE TO CORRECT WHA T APPEARS T O BE A PROBLEM. Water on side of the tank may be condensation due to the panel or insulation not being in place.
23 MODEL DSE LIMITED W ARRANTY A.O. Smith Corporation, the warrantor , extends the following LIMITED W ARRANTY to the owner of this water heater: 1. THE T ANK If the glass-lined tank in this water hea.
24 5621 W . 1 15TH STREET , ALSIP , IL 60803 Phone: 800-433-2545 Fax: 800-433-2515 w w w.hotwater .com E-Mail: parts@hotwater .com REPLACEMENT P ARTS.
Een belangrijk punt na aankoop van elk apparaat A.O. Smith DSE-5 THRU DSE-120 (of zelfs voordat je het koopt) is om de handleiding te lezen. Dit moeten wij doen vanwege een paar simpele redenen:
Als u nog geen A.O. Smith DSE-5 THRU DSE-120 heb gekocht dan nu is een goed moment om kennis te maken met de basisgegevens van het product. Eerst kijk dan naar de eerste pagina\'s van de handleiding, die je hierboven vindt. Je moet daar de belangrijkste technische gegevens A.O. Smith DSE-5 THRU DSE-120 vinden. Op dit manier kan je controleren of het apparaat aan jouw behoeften voldoet. Op de volgende pagina's van de handleiding A.O. Smith DSE-5 THRU DSE-120 leer je over alle kenmerken van het product en krijg je informatie over de werking. De informatie die je over A.O. Smith DSE-5 THRU DSE-120 krijgt, zal je zeker helpen om een besluit over de aankoop te nemen.
In een situatie waarin je al een beziter van A.O. Smith DSE-5 THRU DSE-120 bent, maar toch heb je de instructies niet gelezen, moet je het doen voor de hierboven beschreven redenen. Je zult dan weten of je goed de alle beschikbare functies heb gebruikt, en of je fouten heb gemaakt die het leven van de A.O. Smith DSE-5 THRU DSE-120 kunnen verkorten.
Maar de belangrijkste taak van de handleiding is om de gebruiker bij het oplossen van problemen te helpen met A.O. Smith DSE-5 THRU DSE-120 . Bijna altijd, zal je daar het vinden Troubleshooting met de meest voorkomende storingen en defecten #MANUAl# samen met de instructies over hun opplosinge. Zelfs als je zelf niet kan om het probleem op te lossen, zal de instructie je de weg wijzen naar verdere andere procedure, bijv. door contact met de klantenservice of het dichtstbijzijnde servicecentrum.