HAL100PID HITACHI INVERTER PID CONTROL USERS ’ GUIDE After reading this manual, keep it for future reference Hitachi America, Ltd. SJ/L100/300 SERIES.
SJ100/L100 / PID / 2 CONTENTS 1. OVERVIEW 3 2. PID CONTROL ON SJ100/L100 INVERTERS 3 2-1 PID Control 3 (1) P : Proportional Control 4 (2) I : Integral Control 5 (3) D : Differential Control 5 (4) PID Control 5 2-2 PID Gain Adjustments & Control Characteristics 6 3.
SJ100/L100 / PID / 3 1. OVERVIEW SJ100/L100 series inverters have an integrated PID control function as standard. They can be used for controls, such as constant flow control for fan & pump applications, and they have the following features.
SJ100/L100 / PID / 4 SJ100/L100 series inverters have integrated PID control, which is indicated by the dotted line in Fig. 2-1. You can use PID control by setting a target value and providing a feedback signal. The example in Fig. 2-2 shows a connection diagram for ventilation flow control in a fan application.
SJ100/L100 / PID / 5 (2) I: Integral Control This is a control to correct the output frequency by integrating the deviation. In the case of proportional adjustment, a large deviation will result in a large output frequency adjustment, but if the deviation is small, then the resulting adjustment of output frequency will also be small.
SJ100/L100 / PID / 6 2-2 PID Gain Adjustments & Control Characteristics The optimal gain factors of PID vary from condition to condition, and from system to system. That means it is necessary to set those parameters by taking into account the individual control characteristics of your particular system.
SJ100/L100 / PID / 7 3. HOW TO USE 3-1 Structure & Parameters (1) Control Mode Integrated operator A71 : 00 / 01 DOP, DRW F43 : PID SW ON / OFF SJ100/L100 series inverters feature the following two control modes: l Frequency control mode l PID control mode These can be selected by “ PID function selection (A71) ” .
SJ100/L100 / PID / 8 (3) Deviation Calculation Every calculation in PID control in the SJ100/L100 is based on “ % ” so that it can be used with various applications and units of measure, such as pressure (N/m 2 ), flow (m 3 /min), temperature (degrees) and so on.
SJ100/L100 / PID / 9 As you can see from Fig 3-3, if you set parameters A11 and A12 other than “0”, you should set the target value inside the valid range of the vertical axis. Otherwise it is not possible to achieve stable performance because there is no feedback value.
SJ100/L100 / PID / 10 3-2 Summary of Parameters for PID Control On the SJ100/L100 series inverters, the same function numbers are used for both frequency control mode and PID control mode. The function name for each function is based on frequency control mode, which is normally used for general application.
SJ100/L100 / PID / 11 3-3 Example of Set Up (1) Parameter Set Up under Frequency Control Mode Before driving the system in PID mode, you set up each required parameter under frequency control mode. Pay particular attention to the following items. l Acceleration ramp and Deceleration ramp The output of the PID calculation (refer to Fig.
SJ100/L100 / PID / 12 (3) Scale Conversion Factor Setting Set this factor according to your application, e.g. flow, pressure, temperature and so on. For a detailed explanation, please refer to item (6) on page 9.
SJ100/L100 / PID / 13 3-4 Example of Each Gain Adjustment ( K p & T i ) l Check the response of feedback signal or the output frequency of the inverter when making a step change in the target.
SJ100/L100 / PID / 14 4. EXAMPLE OF ACTUAL APPLICATION You can find in this chapter some typical setting examples for actual applications. 4-1 Constant Flow Control In this case (targets are 150m 3 /m.
SJ100/L100 / PID / 15 4-2 Constant Temperature Control In the case of constant flow control shown in the previous section, output frequency of the inverter increases if the feedback value is smaller than target value, and output frequency of the inverter decreases if the feedback value is bigger than the target value.
SJ100/L100 / PID / 16 5. INDEX - A - - R - acceleration ramp 11 response 6 AVR function 13 - S - - C - scale conversion 9 control mode 7, 10 steady state deviation 6 - D - - T - damped oscillation 6 t.
Een belangrijk punt na aankoop van elk apparaat Hitachi L100 300 (of zelfs voordat je het koopt) is om de handleiding te lezen. Dit moeten wij doen vanwege een paar simpele redenen:
Als u nog geen Hitachi L100 300 heb gekocht dan nu is een goed moment om kennis te maken met de basisgegevens van het product. Eerst kijk dan naar de eerste pagina\'s van de handleiding, die je hierboven vindt. Je moet daar de belangrijkste technische gegevens Hitachi L100 300 vinden. Op dit manier kan je controleren of het apparaat aan jouw behoeften voldoet. Op de volgende pagina's van de handleiding Hitachi L100 300 leer je over alle kenmerken van het product en krijg je informatie over de werking. De informatie die je over Hitachi L100 300 krijgt, zal je zeker helpen om een besluit over de aankoop te nemen.
In een situatie waarin je al een beziter van Hitachi L100 300 bent, maar toch heb je de instructies niet gelezen, moet je het doen voor de hierboven beschreven redenen. Je zult dan weten of je goed de alle beschikbare functies heb gebruikt, en of je fouten heb gemaakt die het leven van de Hitachi L100 300 kunnen verkorten.
Maar de belangrijkste taak van de handleiding is om de gebruiker bij het oplossen van problemen te helpen met Hitachi L100 300 . Bijna altijd, zal je daar het vinden Troubleshooting met de meest voorkomende storingen en defecten #MANUAl# samen met de instructies over hun opplosinge. Zelfs als je zelf niet kan om het probleem op te lossen, zal de instructie je de weg wijzen naar verdere andere procedure, bijv. door contact met de klantenservice of het dichtstbijzijnde servicecentrum.