Gebruiksaanwijzing /service van het product L2002 van de fabrikant Hitachi
Ga naar pagina of 304
L200 2 Series In ver ter Instruction Man ual • Single-phase Input 200V Class • Three-phase Input 200V Class • Three-phase Input 400V Class After reading this manual, keep it handy f or future reference. Hitachi Industrial Equipment Systems Co., Ltd.
.
L200 2 Inverter i Saf ety Messa ges For the best results with the L200 2 Series in v erter , carefully read this manual and all of the warning labels attached to the in v erter before installing and operating it, and follo w the instructions exactly .
ii General Precautions - Read These Fir st! W ARNING: This equipment should be installed, adjusted, and serviced by qualified electrical maintenance personnel familiar w ith the construction and operation of the equipment and the hazards in volv ed. Failure to observe this precaution could result in bodily injury .
L200 2 Inverter iii W ARNING: Rotating shafts and above -ground electr ical potentials can be hazardous. Therefore, it is strongly recommended that all electrical work conform to the National Electrical Codes and local regulations. Inst allation , alignment and maintenance should be performed only by qualified p ersonnel.
iv Inde x to W arnings and Cautions in This Manual Cautions and W arnings for Orie ntation and Mounting Pr ocedures Wiring - W arnings for Electrical Practices and Wire Specifications CA UTION: Hazard of ele ctrical shock. Disconnect incoming po wer before working on this control.
L200 2 Inverter v Wiring - Cautions f or Electrical Practices W ARNING: “Suitable for use on a circui t capable of deli vering not more than 100,000 rms symmetrical amperes, 480 V maximum. ” For models with suf fix H. .... 2–16 HIGH V OL T A GE: Be sure to ground the unit.
vi P owerup T est Caution Messages CA UTION: Be sure not to connect an A C power supply to the output terminals. Otherwise, there is the po ssibility of damage to the in verter and the danger of injury and/or f ire.
L200 2 Inverter vii W arnings for Configuring Drive P arameters Cautions f or Configuring Drive P arameters W arnings for Operations and Monitoring W ARNING: When parameter B012, lev e l of electronic.
viii Cautions f or Operations and Monitoring W ARNING: Be sure not to touch the insi de of the energized in verter or to put any conducti ve object into it.
L200 2 Inverter ix W arnings and Cautions for T roub leshooting and Maintenance General W arnings and Cautions W ARNING: Nev er modify the unit. Otherwise, there is a danger of electric shock and/ or injury .
x CA UTION: Do not stop operation by switching OFF electromagnetic contactors on the primary or secondary sides of the in verter . When there has been a sudden po wer failure whil e an operation instruction is acti ve, then the unit may restart operation aut omatically afte r the power failure has ended.
L200 2 Inverter xi CA UTION: EFFECTS OF PO WER DIST RIBUT ION SYSTEM ON INVER TER In the cases belo w in volving a general-purpos e in verter , a lar ge peak current can flo w on the po wer supply side, sometimes destroying the con verter module: 1. The unbalance factor of the po wer supply is 3% or higher .
xii CA UTION: When the EEPR OM error E08 occurs, be sure to conf irm the setting v alues again. CA UTION: When using normally closed acti ve state settings (C011 to C015) for e xter- nally commanded F.
L200 2 Inverter xiii T erminal Tightening T or que and Wire Size The wire size range and tightening torque fo r f ield wiring terminals are presented in the tables below . Wire Connectors W ARNING: Field wiring connections must be made by a UL Listed and CSA Certified ring lug terminal connector sized for the wire gauge being used.
xiv Fuse and Cir cuit Breaker Sizes The in verter’ s input po wer wiring must include UL Listed, dual-element, 600V fuses, or UL Listed, in verse-time, 600V circuit breakers.
xv L200 2 Inverter Safety Messages Hazardous High Voltage i General Precautions - Read These Fi rst! ii Index to Warnings and Cautions in This Manual iv General Warnings and Cautions ix UL ® Cautions.
xvi Chapter 4: Operations and Monitoring Introduction 4–2 Connecting to PLCs and Other Devices 4–4 Control Logic Signal Specifications 4–6 Intelligent Terminal Listing 4–7 Using Intelligent In.
L200 2 Inverter xvii Revisions Revision History T able No. Revision Comments Date of Issue Operation Manual No. Initial release of manual NB675X Sept. 2006 NB675X.
xviii Contact Inf ormation NO TE: T o receive technical support for the Hita chi in verter you purchased, contact the Hitachi in verter deal er from whom you purchased the unit, or the sales of fice or f actory contact listed abov e. Please be prepared to provide the follo wing in verter nameplate information: 1.
Getting Star ted In This Chapter ... p age — Introduction ................. .................... ................ 2 — Inverter S pecifications ..................... ................ 5 — Introduction to V ariable-Frequency Drives .... 18 — Frequently Asked Questions .
Introduction Getting Star ted 1–2 Intr oduction Main Features Congratulations on your purchase of an L200 2 Series Hitachi in verter! This in verter dri ve features state-of -the-art circuitry and components to provide high performance. The housing footprint is e xceptionally small, gi ven the size of the corresponding motor .
L200 2 Inverter Getting Star ted 1–3 Operator Interface Options The L200 2 in verter can connect to an e xternal digital operator via the front panel serial port connector . The separate ke ypad is shown to the right (part no. OPE–SRmini). This allo ws you to operate the in verter remotely , as shown (belo w left).
Introduction Getting Star ted 1–4 In ver ter Specifications Label The Hitachi L200 2 in verters hav e product labels loca ted on the right side of the housing, as pictured belo w . Be sure to verify that the specifications on the labels match your power source, motor , and application safety requirements.
L200 2 Inverter Getting Star ted 1–5 In ver ter Specifications Model-specific tables f or 200V and 400V class in ver ters The follo wing tables are specif ic to L200 2 in verters for the 200V and 400V class model groups. Note that “ General Specif ications ” on page 1–10 apply to both voltage class groups.
Inverter Specifications Getting Star ted 1–6 Footnotes for the preceding table and the tables that follo w: Note 1: The protection method conforms to JEM 1030.
L200 2 Inverter Getting Star ted 1–7 L200 2 In verter Specif ications, continued... Item 200V Class Specif ications, continued L200 2 in verters, 200V models EU types 015NFEF2 015NFE2 022NFEF2 022NFE2 ——— USA type 015NFU2 022NFU2 037LFU2 055LFU2 075LFU2 Applicable motor size *2 kW 1.
Inverter Specifications Getting Star ted 1–8 Item 400V Class Specif ications L200 2 in verters, 400V models EU types 004HFEF2 004HFE2 007HFEF2 007HFE2 015HFEF2 015HFE2 022HFEF2 022HFE2 USA type 004HFU2 007H FU2 015HFU2 022HFU2 Applicable motor size *2 kW 0.
L200 2 Inverter Getting Star ted 1–9 Item 400V Class Specif ications, continued L200 2 in verters, 400V models EU types 030HFEF2 030HFE2 040HFEF2 040HFE2 055HFEF2 055HFE2 075HFEF2 075HFE2 USA type — 040HFU2 055HFU2 075HFU2 Applicable motor size *2 kW 3.
Inverter Specifications Getting Star ted 1–10 General Specifications The follo wing table applies to all L200 2 in verters. Item General Specif ications Protectiv e housing *1 IP20 Control method Sinusoidal Pulse W idth Modulation (PWM) control Carrier frequency 2kHz to 14kH z (default setting: 5kHz) Output frequency range *4 0.
L200 2 Inverter Getting Star ted 1–11 Signal Ratings Detailed ratings are in “ Control Logic Signal Specifications ” on page 4–6 . Other functions A VR function, curved accel/ decel prof ile, .
Inverter Specifications Getting Star ted 1–12 Derating Curves The maximum av ailable in verter current output is limited by the carrier frequency and ambient temperature. The carrier frequency is the in verter’ s internal power switching frequency , settable from 2 kHz to 14 kHz.
L200 2 Inverter Getting Star ted 1–13 Derating curves: 2468 1 0 1 2 1 4 70% 80% 90% 100% 95% 85% 75% % of rated output current Carrier frequency kHz L200–002NFE(F)2/NFU2 2468 1 0 1 2 1 4 70% 80% 9.
Inverter Specifications Getting Star ted 1–14 Derating curves, continued... 2468 1 0 1 2 1 4 70% 80% 90% 100% 95% 85% 75% % of rated output current Carrier frequency kHz 2468 1 0 1 2 1 4 70% 80% 90%.
L200 2 Inverter Getting Star ted 1–15 Derating curves, continued... 2468 1 0 1 2 1 4 40% 60% 80% 100% 90% 70% 50% % of rated output current Carrier frequency kHz 2468 1 0 1 2 1 4 40% 60% 80% 100% 90.
Inverter Specifications Getting Star ted 1–16 Derating curves, continued... 2468 1 0 1 2 1 4 40% 60% 80% 100% 90% 70% 50% % of rated output current Carrier frequency kHz 2468 1 0 1 2 1 4 40% 60% 80%.
L200 2 Inverter Getting Star ted 1–17 Derating curves, continued... 2468 1 0 1 2 1 4 40% 60% 80% 100% 90% 70% 50% % of rated output current Carrier frequency kHz 2468 1 0 1 2 1 4 40% 60% 80% 100% 90.
Introduction to Varia ble-Frequency Drives Getting Star ted 1–18 Intr oduction to V ariable-Frequency Drives The Purpose of Motor Speed Contr ol for Industry Hitachi in verters provide speed control fo r 3-phase A C induction motors. Y ou connect A C power to the in verter , and connect the in verter to the motor .
L200 2 Inverter Getting Star ted 1–19 T orque and Constant V olts/Her tz Operation In the past, A C variab le speed dri ves used an open loop (scalar) technique to control speed. The constant-volts-per -hertz operation maintains a constant ra tio between the applied voltage and the applied frequenc y .
Introduction to Varia ble-Frequency Drives Getting Star ted 1–20 In ver ter Output to the Motor The A C motor must be connected only to the in verter’ s output terminals. The output terminals are uniquely labeled (to dif ferentiate them from the input terminals) with the designations U/T1, V/T2, and W/T3.
L200 2 Inverter Getting Star ted 1–21 Intelligent Functions and P arameters Much of this manual is de voted to describ ing how to use in ve rter functions and how to conf ig- ure in verter parameters. The in verter is micro- processor- controlled, and has many indepen dent functions.
Introduction to Varia ble-Frequency Drives Getting Star ted 1–22 V elocity Pr ofiles The L200 2 in verter is capable of sophisticated speed control. A graphi cal representation of that capability will help you understand and conf igure the associated parameters.
L200 2 Inverter Getting Star ted 1–23 Frequentl y Asked Questions Q. What is the main advantage in using an in verter to dri ve a motor , c ompared to alternativ e solutions? A. An in verter can vary the motor speed wi th very little loss of eff iciency , unlike mechanical or hydraulic speed control solutions.
Frequently Asked Qu estions Getting Star ted 1–24 Q. Why doesn’ t the motor hav e a neutral connection as a return to the in verter? A. The motor theoretically represent s a “balanced Y” load if all three sta tor windings ha ve the same impedance.
L200 2 Inverter Getting Star ted 1–25 Q. Ho w will I kno w if my application will require resistiv e braking? A. For ne w applications, it may be dif f icult to tell before you actually test a motor/driv e solution.
.
In ver ter Mounting and Installation In This Chapter .... p age — Orientation to Inverter Features ...................... 2 — Basic System Description .................. ............. 7 — S tep-by-S tep Basic Installation .......................
Orientation to I nverter Features In v er t er Mounting and Installation 2–2 Orientation to In ver ter Features Unpack ing and Inspection Please take a fe w moments to unpack your new L200 2 in verter and perform these steps: 1. Look for any damage that may ha ve occurred during shipping.
L200 2 Inverter In v er t er Mounting and Installation 2–3 Fr ont Housing Co ver HIGH V OL T A GE: Hazard of electrical shock. Di sconnect incoming power before working on this control. W ait fi ve (5) minutes before remo ving the front cover . T o remove the cover , f ollow the steps below (applies to all in verter models): 1.
Orientation to I nverter Features In v er t er Mounting and Installation 2–4 Logic Connector Intr oduction After removing the front housing co ver , take a moment to become familiar with the connectors, as sho wn below .
L200 2 Inverter In v er t er Mounting and Installation 2–5 DIP Switch Intr oduction The in verter has three (3) internal DIP switch es, located to the right of the logic connec- tors as sho wn belo w . This section provid es an introduction, and refers you to other chapters that discuss each DIP switch in depth.
Orientation to I nverter Features In v er t er Mounting and Installation 2–6 Po wer Wiring Access - First, ensure no power source of an y kind is connected to the in verter . If power has been connected, w ait fi ve minutes after po werdown and ve rify the Po wer LED is OFF to proceed.
L200 2 Inverter In v er t er Mounting and Installation 2–7 Basic System Description A motor control system will obviously include a motor and in verter , as well as a breaker or fuses for safety . If you are connecting a motor to the in verter on a test bench just to get started, that’ s all you may need for now .
Step-by-St ep Ba sic Installation In v er t er Mounting and Installation 2–8 W ARNING: In the cases below in volving a gene ral-purpose in verter , a large peak current can flo w on the power supply side , sometimes destro ying the con verter module: 1.
L200 2 Inverter In v er t er Mounting and Installation 2–9 Choosing a Mounting Location Step 1: Study the follo wing caution messages associated with mounting the in verter . This is the time when mistakes are most likely to occur that will result in expensi ve re work, equipment damage, or personal injury .
Step-by-St ep Ba sic Installation In v er t er Mounting and Installation 2–10 Ensure Adequate V e ntilation Step 2: T o summarize the caution messages—you wi ll need to find a solid, non-flamma- ble, vertical surface that is in a relati vely clean and dry en vironment.
L200 2 Inverter In v er t er Mounting and Installation 2–11 Check In ver ter Dimensions Step 4: Locate the applicable drawing on th e follo wing pages for your in verter . Dimensions are gi ven in millimeters (inches) format. NO TE: Some in verter housings require tw o moun ting scre ws, while others require four .
Step-by-St ep Ba sic Installation In v er t er Mounting and Installation 2–12 Dimensional drawings, continued... 2- φ 5(0.20) 11 8 (4.64) H=1 3 0(5.1 3 0) H=155(6.10) 1 3 0(5.1 3 0) 155(6.10) 155(6.10) -004HFU2 -004HFEF2 -007NFEF2 H Model 9 8 ( 3 .
L200 2 Inverter In v er t er Mounting and Installation 2–13 Dimensional drawings, continued ... 2- φ 5(0.20) 11 8 (4.64) H=1 3 0(5.1 3 0) H=155(6.10) 1 3 0(5.1 3 0) 155(6.10) H Model 9 8 ( 3 . 8 6) 110(4. 33 ) 7(0.16) 5(0.20) 6(0.24) 129(5.0 8 ) 4(0.
Step-by-St ep Ba sic Installation In v er t er Mounting and Installation 2–14 Dimensional drawings, continued... 2- φ 5(0.20) 11 8 (4.64) H=1 3 0(5.1 3 0) H=155(6.10) 1 3 0(5.12) 1 3 0(5.12) 1 3 0(5.12) 1 3 0(5.12) 1 3 0(5.12) 1 3 0(5.12) 1 3 0(5.12) 155(6.
L200 2 Inverter In v er t er Mounting and Installation 2–15 Dimensional drawings, continued... 2- φ 5(0.20) 205( 8 .07) H=220( 8 .66) H=250(9. 8 4) 205( 8 .07) 205( 8 .07) 205( 8 .07) 205( 8 .07) 250(9. 8 4) 250(9. 8 4) -055LFU2 -055HFU2 -075LFU2 -075HFU2 -055HFEF2 -075HFEF2 H Model 164(6.
Step-by-St ep Ba sic Installation In v er t er Mounting and Installation 2–16 Prepare for Wiring Step 5: It is very important to perform the wi ring steps carefully and correctly . Before proceeding, please study the cauti on and warning messages belo w .
L200 2 Inverter In v er t er Mounting and Installation 2–17 Determining Wire and Fuse Sizes The maximum motor currents in your app lication determines the recommended wire size.
Step-by-St ep Ba sic Installation In v er t er Mounting and Installation 2–18 T erminal Dimensions and T or que Specs The terminal scre w dimensions for all L200 2 in verters are listed in table belo w . This information is useful in sizing spade lug or ring lug connectors for wire terminations.
L200 2 Inverter In v er t er Mounting and Installation 2–19 Please use the terminal arrangement belo w corresponding to your in verter model. NO TE: An in verter powered by a portable po wer generator may recei ve a distorted power w a veform, o verheating the generator .
Step-by-St ep Ba sic Installation In v er t er Mounting and Installation 2–20 CA UTION: Be sure that the input v oltage matc hes the in verter specif ications: • Single/Three phase 200 to 240 V 50/60 Hz (up to 2.2kW) for NFEF/NFU models • Three phase 200 to 240V 50/ 60Hz (abov e 2.
L200 2 Inverter In v er t er Mounting and Installation 2–21 Wire the In ver ter Output to Motor Step 7: The process of motor selection is be yond the scope of this manual. Ho wev er , it must be an A C induction motor with three pha ses. It should also come with a chassis ground lug.
Powerup Test In v er t er Mounting and Installation 2–22 Uncover the In ver ter V ents Step 8: After mounting and wiring the in verter , remov e any cov e rs from the in verter housing. This includes material over th e side v entilation ports. W ARNING: Make sure the input po wer to the in verter is OFF .
L200 2 Inverter In v er t er Mounting and Installation 2–23 Pre-test and Operational Precautions The follow ing instructions apply to the powerup test, or to an y time the in verter is powered and operating. Please study the follo wing instructions and messages before proceeding with the po werup test.
Using the Front Panel Keypad In v er t er Mounting and Installation 2–24 Using the Fr ont P anel K eypad Please take a moment to fa miliarize yourself with the keypad layout sho wn in the figure belo w . The display is used in programming th e in verter’ s parameters, as well as monitor- ing specif ic parameter va lues during operation.
L200 2 Inverter In v er t er Mounting and Installation 2–25 Ke ys, Modes, and Parameter s The purpose of the ke ypad is to provide a way to change modes and parameters. The term function applies to b oth monitoring modes and parameters. These are all accessible through function codes that are primarily 4-character codes.
Using the Front Panel Keypad In v er t er Mounting and Installation 2–26 Ke ypad Navigational Map The L200 2 Series in verter dri ves ha ve many programmable functions and parameters. Chapter 3 will cov er these in detail, but you need to access just a fe w items to perform the po werup test.
L200 2 Inverter In v er t er Mounting and Installation 2–27 Selecting Functions and Editing P arameters T o prepare to run the motor in the po werup te st, this section will sho w ho w to configure the necessary parameters: 1. Conf irm the TM/PRG DIP switch setting.
Using the Front Panel Keypad In v er t er Mounting and Installation 2–28 If the Potentiometer Enable LED is OFF , follow the steps belo w . Select the K eypad f or the R UN Command - The R UN command causes the i n verter to accelerate the motor to the selected speed.
L200 2 Inverter In v er t er Mounting and Installation 2–29 Set the Motor Base Fr equency - The motor is designed to operate at a specif ic A C frequency . Most commercial motors are designed for 50/60 Hz operation. First, check the motor specifications.
Using the Front Panel Keypad In v er t er Mounting and Installation 2–30 Set the Moto r Curr ent - The in verter has thermal o verload protection that is designed to protect the in verter and motor from o verheating due to an e xcessi ve lo ad. The in verter’ s uses the motor’ s current rating to calculate the time-based heating effect.
L200 2 Inverter In v er t er Mounting and Installation 2–31 Set the Number of Motor Poles - The motor’ s internal winding arrangement deter- mines its number of magnetic poles. The specifications label on the motor usually indicates the number of poles .
Using the Front Panel Keypad In v er t er Mounting and Installation 2–32 Monitoring P arameters with the Displa y After using the ke ypad for parameter editing, it’ s a good idea to switch the in verter from Program Mode to Monitor Mode. The PRG LED will be OFF , and the Hertz or Ampere LED indicates the display units.
L200 2 Inverter In v er t er Mounting and Installation 2–33 P owerup T est Obser vations and Summary Step 10: Reading this section will he lp you make some useful observ ations when first running the motor .
.
Configuring Drive P arameter s In This Chapter .... p age — Choosing a Programming Device ................... 2 — Using Keypad Devices .................... ................ 3 — “D” Group: Monitoring Functions ..................... 6 — “F” Group: Main Profile Parameters .
Choosing a Programmin g Device Configuring Drive P arameters 3–2 Choosing a Pr ogramming Device Intr oduction Hitachi v ariable frequenc y dri ves (in verte rs) use the latest electronics technology for getting the right A C wav eform to the motor at the right time.
L200 2 Inverter Configuring Drive P arameters 3–3 Using K e ypad De vices The L200 2 Series in verter front k eypad contains all th e elements for both monitoring and programming parameters. The ke ypad layout is pictured belo w . All other programming de vices for the in verter hav e a s imilar ke y arrangement and function.
Using Keypad Devices Configuring Drive P arameters 3–4 Ke ypad Navigational Map Y ou can use the inv erter’ s front panel keypad to na vigate to any parameter or fun ction. The diagram below sho ws the basic navigational map to access these items.
L200 2 Inverter Configuring Drive P arameters 3–5 Operational Modes The R UN and PRG LEDs tell just part of the story; Run Mode and Program Modes are independent modes, not opposite modes. In the state diagram to the right, Run alternates with Stop, and Program Mode alternates with Monitor Mode.
“D” Group: Monitoring Fun ctions Configuring Drive P arameters 3–6 “D” Gr oup: Monitoring Functions Y ou can access important system paramete r values with the “D” Group monitoring functions, whether the in verter is in R un Mode or Stop Mode.
L200 2 Inverter Configuring Drive P arameters 3–7 T rip Event and Histor y Monitoring The trip e vent and history monitoring featur e lets you cycle through related information using the ke ypad. See “ Monitoring T rip Events, History , & Conditions ” on page 6–5 for more details.
“D” Group: Monitoring Fun ctions Configuring Drive P arameters 3–8 Local Monitoring During Network Operation The L200 2 in verter’ s serial port may be connected to a network or to an external digital operator . During those times, the in verter ke ypad keys will not function (e xcept for the Stop ke y).
L200 2 Inverter Configuring Drive P arameters 3–9 “F” Gr oup: Main Profile P arameters The basic frequency (speed) prof ile is defined by parameters contained in the “F” Group as show n to the right.
“A” Group: Standard Function s Configuring Drive P arameters 3–10 “A” Gr oup: Standard Functions Contr ol Source Settings The in verter provides fle xibility in ho w you control Run/Stop operation and set the output frequency (motor sp eed).
L200 2 Inverter Configuring Drive P arameters 3–11 Run Command Source Setting - F or parameter A002, the follo wing table provides a further description of each option, and a refe rence to other pag.
“A” Group: Standard Function s Configuring Drive P arameters 3–12 The in verter has other control sources that can temporarily ove rride the parameter A001 setting, forcing a dif ferent output frequenc y source. The follo wing table lists all frequency source setting methods and their relati ve priority (“1” is the highest priority).
L200 2 Inverter Configuring Drive P arameters 3–13 Basic P arameter Settings These settings af fect the most fundamental be ha vior of the in verter—the outputs to the motor . The frequency of the in verter’ s A C output determines the motor speed.
“A” Group: Standard Function s Configuring Drive P arameters 3–14 Analog Input Settings The in verter has the capability to accept an external analog input that can command the output frequency to the motor . V oltage i nput (0 –10V) and current input (4–20mA) are av ailable on separate terminal s ([O] and [OI], respecti vely).
L200 2 Inverter Configuring Drive P arameters 3–15 A016: External Frequency Filter Time Constant – This filter smooths the analog input signal for the in verter’ s output frequency reference. • A016 sets the f ilter range n=1 to 16. This is a simple moving a verage calculation, where n (number of samples) is va riable.
“A” Group: Standard Function s Configuring Drive P arameters 3–16 The example graph belo w shows a typical an alog input wa veform. The filter remo ves the noise spikes. When a speed change (such as le vel increase) occurs, the filter naturally has a delayed response.
L200 2 Inverter Configuring Drive P arameters 3–17 NO TE: When setting function A039 = 01, the actu al jogging deceleration time depends on the standard Deceleration T ime Setting F003/F203.
“A” Group: Standard Function s Configuring Drive P arameters 3–18 T orque Contr ol Algorithms The in verter generates the motor output according to the V/f algorithm selected. Parameter A044 selects the in verter algorithm for generating the frequency output, as sho wn in the diagram to the right (A244 for 2nd motor).
L200 2 Inverter Configuring Drive P arameters 3–19 Be aw are that running the motor at a lo w speed for a long time can cause motor ov erheating. This is particularly true when manual torque boost is ON, or if the motor relies on a built-in f an for cooling.
“A” Group: Standard Function s Configuring Drive P arameters 3–20 A244 V/f characteristic curv e selection, 2nd motor T wo av ailable V/f curves; three select codes: 00... Constant to rque 01... Reduced torque ✘ ✘ 00 00 — 2CTRL C-TRQ A045 V/f gain setting Set s voltage ga in of the in verter , range is 20.
L200 2 Inverter Configuring Drive P arameters 3–21 DC Braking Settings The DC braking feature can provide additional stopping torque when compared to a normal deceleration to a stop. DC braking is particularly useful at low speeds when normal decelera- tion torque is minimal.
“A” Group: Standard Function s Configuring Drive P arameters 3–22 Frequency-related Functions Frequency Limits – Upper and lo wer limits can be imposed on the inv erter output frequency . These limit s will apply regard less of the source of the speed refer- ence.
L200 2 Inverter Configuring Drive P arameters 3–23 Jump Fr equencies – Some motors or machines exhi bit resonances at particular speed(s), which can be destructi ve for prolonged running at those speeds. The in verter has up to three jump fr equencies as sho wn in the graph.
“A” Group: Standard Function s Configuring Drive P arameters 3–24 PID Contr ol When enabled, the built-in PID loop calculates an ideal in verter output v alue to cause a loop feedback process v ariable (PV) to move closer in v alue to the setpoint (SP).
L200 2 Inverter Configuring Drive P arameters 3–25 A utomatic V oltage Regulation (A VR) Function The automatic voltage re gulation (A VR) featur e keeps the in verter output wav eform at a relati vely constant amplitude during po wer input fluctuations.
“A” Group: Standard Function s Configuring Drive P arameters 3–26 Second Acceleration and Deceleration Functions The L200 2 in verter features two-stage accelera tion and deceleration ramps.
L200 2 Inverter Configuring Drive P arameters 3–27 NO TE: F or A095 and A096 (and for 2nd motor settings), if you set a very rapid Acc1 or Dec1 time (less than 1.0 second), the inv erter ma y not be able to change rates to Acc2 or Dec2 before reaching the target frequenc y .
“A” Group: Standard Function s Configuring Drive P arameters 3–28 Accel/Decel Standard acceleration and deceleration is linear . The in verter CPU can also calculate an S-curve acceleration or deceleration curve as sho wn. This profile is useful for fa voring the load characteristics in particu- lar applications.
L200 2 Inverter Configuring Drive P arameters 3–29 Additional Analog Input Settings Input Range Settings – The parameters in the following table adjust the input charac- teristics of the analog current input.
“A” Group: Standard Function s Configuring Drive P arameters 3–30 Analog Input Calculate Function – The in verter can mathematically combine two input sources into one value. The Calculate function can either add, subtract, or multiply the two selected sources.
L200 2 Inverter Configuring Drive P arameters 3–31 ADD Fr equency – The in verter can add or subtract an of fset value to the output frequency setting which is specif ied by A001 (will work with any of the f ive possible sources). The ADD Frequency is a v alue you can store in parameter A145.
“A” Group: Standard Function s Configuring Drive P arameters 3–32 A154 Pot. input active range end current The output frequency corre- sponding to th e potentiometer range ending point, range is 0.0 to 100.0 ✘ ✔ 0.0 0.0 % POT EXS%E 0. 0 A155 Pot.
L200 2 Inverter Configuring Drive P arameters 3–33 “B” Gr oup: Fine T uning Functions The “B” Group of functions and parameters adju st some of the more subtle b ut useful aspects of motor control and system configuration.
“B” Group: Fine Tuning Fun ctions Configuring Drive P arameters 3–34 Instantaneous P ower F ailure / Under-v oltage Alarm Use parameter B004 to disable or enable th e instantaneous po wer failure / undervoltage alarm.
L200 2 Inverter Configuring Drive P arameters 3–35 Electr onic Thermal Overload Alarm Setting The thermal ov erload detection protects the in verter and motor from ov erheating due to an excessi ve load. It uses a current/in verse time curve to determine the trip point.
“B” Group: Fine Tuning Fun ctions Configuring Drive P arameters 3–36 Note 1: For in verter models 005NFE(F), 011NFE(F), and 030HFE(F), the ov erload- related parameter settings are differ ent from the rated ampe res. Therefore, be sure to set the electronic thermal overload according to the actual motor dri ven by the particular in verter .
L200 2 Inverter Configuring Drive P arameters 3–37 Overload Restriction If the in verter’ s output current e xceeds a preset current le vel you specify during acceleration or constant speed, the ov e rload restriction feature automatically reduces the output frequenc y to restrict the ov erload.
“B” Group: Fine Tuning Fun ctions Configuring Drive P arameters 3–38 “B” Function Run Mode Edit Lo Hi Defaults Func. Code Name / SR W Display Description –FE(F) (EU) –FU (USA) Units B021 Overload restriction operation mode Select the operating mode during overload conditions, three options, option codes: 00.
L200 2 Inverter Configuring Drive P arameters 3–39 Software Loc k Mode The software lock function keeps personnel from accidentally ch anging parameters in the in verter memory . Use B031 to select from various protection le vels. The table below lists all comb inations of B031 option codes and the ON/OFF state of the [SFT] input.
“B” Group: Fine Tuning Fun ctions Configuring Drive P arameters 3–40 NO TE: T o disable parameter editing when us ing B031 lock modes 00 and 01, assign the [SFT] function to one of the intelligent input terminals. See “ Software Lock ” on page 4–22 .
L200 2 Inverter Configuring Drive P arameters 3–41 Miscellaneous Settings The miscellaneous settings include scaling factor s, initialization modes, and others.
“B” Group: Fine Tuning Fun ctions Configuring Drive P arameters 3–42 B091/B088: Stop Mode / Restart Mode Conf iguration – Y ou can conf igure ho w the in verter performs a standard stop (each time Run FWD and REV signals turn OFF).
L200 2 Inverter Configuring Drive P arameters 3–43 In most applications a controlled decelera tion is desirable, corresponding to B091=00. Ho we ver , applications such as HV AC f a n control will often use a free-run stop (B091=01). This practice decreases dynamic stress on system components, prolonging system life.
“B” Group: Fine Tuning Fun ctions Configuring Drive P arameters 3–44 B089: Monitor display select f or networked in verter – When the L200 2 in verter is controlled via network, the in verter’ s ke ypad display can still provide Monitor Mode.
L200 2 Inverter Configuring Drive P arameters 3–45 The graph belo w shows an in verter output prof ile that starts decel erating to a stop. At two dif ferent points during the deceleration, regenerati ve v oltage ele vates the DC bus le vel, e xceeding the LADSTOP threshold set by B131.
“B” Group: Fine Tuning Fun ctions Configuring Drive P arameters 3–46 B150: Carrier Mode – If B083 Carrier Frequency setti ng is greater than 4 kHz, then the B150 Carrier Mode function (if enabled) will reduce the actual carrier frequency downw ard to 4 kHz as the in verter’ s internal termperature increas es.
L200 2 Inverter Configuring Drive P arameters 3–47 “C” Gr oup: Intellig ent T erminal Functions The f iv e input terminals [ 1] , [ 2] , [ 3] , [ 4] , and [ 5] can be conf igured for any of 19 dif ferent functions. The next tw o tables sho w how to co nfigure the f iv e terminals.
“C” Group: Intelligent Terminal Functions Configuring Drive P arameters 3–48 The input logic con vention is programmable fo r each of the f iv e inputs. Most inputs default to normally open (acti ve high), b ut you ca n select normally closed (active lo w) in order to in vert the sense of the logic.
L200 2 Inverter Configuring Drive P arameters 3–49 NO TE: An input terminal conf igured for opt ion code 18 ([RS] Reset command) cannot be configured fo r normally closed operation. Intelligent Input T erminal Overview Each of the fi ve intelligent terminals may be assigned any of the options in the following table.
“C” Group: Intelligent Terminal Functions Configuring Drive P arameters 3–50 Input Function Summary T able – This table show s all twenty-four intelligent input functions at a glance.
L200 2 Inverter Configuring Drive P arameters 3–51 12 EXT External T rip ON When assigned input transitions OFF to ON, in verter latches trip e vent and displays E12 OFF No trip ev ent for ON to OFF.
“C” Group: Intelligent Terminal Functions Configuring Drive P arameters 3–52 23 PID PID Disable ON T emporarily disables PID loop control. Inv erter output turns OFF as long as PID Enable is activ e (A071=01). OFF Has no effect on PID loop operation, which operates normally if PI D Enable is activ e (A071=01).
L200 2 Inverter Configuring Drive P arameters 3–53 Note 1: When using the Multi-speed Select settings CF1 to CF4, do not display parameter F001 or change the v alue of F 001 while the in verter is in Run Mode (motor running). If it is necessary to check the v alue of F001 during Run Mode, please monitor D001 instead of F001.
“C” Group: Intelligent Terminal Functions Configuring Drive P arameters 3–54 Output T erminal Configuration The in verter provides conf iguration for logi c (discrete) and analog outputs, shown in the table belo w . The output logic con vention is programmabl e for terminals [11], [12], and the alarm relay terminals.
L200 2 Inverter Configuring Drive P arameters 3–55 Output Function Summary T able – This table sho ws all ele ven functions for the logical outputs (terminals [11], [12]) at a glance.
“C” Group: Intelligent Terminal Functions Configuring Drive P arameters 3–56 Analog Function Summary T able – This table shows both functions for the analog voltage output [AM] terminal, conf igured by C028. More information on using and calibrating the [AM] output terminal is in “ Analog Output Operation ” on page 4–55 .
L200 2 Inverter Configuring Drive P arameters 3–57 The Error for the PID loop is the magni- tude (absolute v alue) of the dif ference between the Setpoint (desired v alue) and Process V a riable (actual v alue).
“C” Group: Intelligent Terminal Functions Configuring Drive P arameters 3–58 Netw ork Communication Settings The following table lists parameters that c onfigure the inverter’s serial communications port.
L200 2 Inverter Configuring Drive P arameters 3–59 Analog Signal Calibration Settings The functions in the follo wing table confi gure the signals for the analog output termi- nals. Note that these settings do not change the current/v oltage or sink/source character- istics—only the zero and span (scaling) of the signals.
“C” Group: Intelligent Terminal Functions Configuring Drive P arameters 3–60 Miscellaneous Functions The follo wing table contains miscellaneous functions not in other function groups.
L200 2 Inverter Configuring Drive P arameters 3–61 Output Logic and Timing Logic Output Function – The in verter has a b uil t-in logi c output feature.
“C” Group: Intelligent Terminal Functions Configuring Drive P arameters 3–62 Output Sign al ON/OFF Delay Function - Intelligent outputs including terminals [11], [12], and the output relay, have configurable signal transition delays. Each output can delay either the OFF-to-ON or ON-to-OFF tr ansitions, or both.
L200 2 Inverter Configuring Drive P arameters 3–63 “H” Gr oup: Motor Constants Functions The “H” Group parameters configure the in verter for the motor characteristics. You must manually set H003 and H004 values to match the motor. Parameter H006 is factory- set.
“P” Group: Expansion Card Functions Configuring Drive P arameters 3–64 “P” Gr oup: Expansion Card Functions The (optional) expan sion card for the L200 2 in verter has assiciated conf iguration data. The follo wing table def ines the functions a nd their va lue ranges.
Operations and Monitoring In This Chapter .... p age — Introduction ................. .................... ................ 2 — Connecting to PLCs and Other Devices ......... 4 — Control Logic Signal S pecifications ................. 6 — Intelligent T ermina l Listing .
Introduction Operations and Monitoring 4–2 Intr oduction The pre vious material in Chapter 3 ga ve a reference listing of all the programmable functions of the in verter . W e suggest that you f irst scan through the listing of in verter functions to gain a general familiarity .
L200 2 Inverter Operations and Monitoring 4–3 W arning Messages for Operating Pr ocedures Before continuing, please read the follo wing W arning messages. W ARNING: Be sure to turn ON the input po wer supply only after closing the front case. While the in verter is energized, be sure not to open the front case.
Connecting to PLCs and Other Devices Operations and Monitoring 4–4 Connecting to PLCs and Other De vices Hitachi in verters (dri ves) are useful in many types of applications . During installation, the in verter ke ypad (or other programming de vice) will facilitate the initial configura- tion.
L200 2 Inverter Operations and Monitoring 4–5 Example Wiring Diagram The schematic diagram below pro vides a gene ral example of logic connector wirin g, in addition to basic po wer and motor wiring co ve red in Chapter 2.
Control Logic Signal Specifications Operations and Monitoring 4–6 Contr ol Logic Signal Specifications Specifications for th e logic connection terminals are in the follo w ing table: Note 1: The two terminals [L] are electrically c onnected together inside the in verter .
L200 2 Inverter Operations and Monitoring 4–7 Intelligent T erminal Listing Intelligent Inputs Use the follo wing table to locate pages for in telligent i nput material in this chapter .
Intelligent Terminal Listing Operations and Monitoring 4–8 Intelligent Outputs Use the follo wing table to locate pages for in telligent output material in this chapter .
L200 2 Inverter Operations and Monitoring 4–9 Using Intelligent Input T erminals T erminals [1], [2], [3], [4], and [5] are identical, programmable inputs for general use. The input circuits can use the in verter’ s in ternal (isolated) +24V field supply or an external po wer supply .
Using Intelligent Input Terminals Operations and Monitoring 4–10 The two diagrams belo w show input wiring circ uits using the in verter’ s internal +24V supply . Each diagram shows the connection for simple switch es, or for a field de vice with transistor outputs.
L200 2 Inverter Operations and Monitoring 4–11 The two diagrams belo w sho w input wiring circ uits using an ex ternal supply . If using the upper wiring diagram, be sure to use a diode wi th the external supply . This will prev ent a power supply contention in case the SR/SK switch is accidentally placed in the incorrect position.
Using Intelligent Input Terminals Operations and Monitoring 4–12 Forwar d Run/Stop and Re verse Run/Stop Commands: When you input the Run command via the terminal [FW], the in verter ex ecutes the Forw ard Run command (high) or Stop command (lo w).
L200 2 Inverter Operations and Monitoring 4–13 Multi-Speed Select The in verter can store up to 16 dif ferent target frequencies (speeds) that the motor output uses for steady-state run condition. These speeds are acces- sible through programming f our of the intelligent terminals as binary-encoded inputs CF1 to CF4 per the table to the right.
Using Intelligent Input Terminals Operations and Monitoring 4–14 While using the multi-speed capability, you can monitor the present frequency with monitor function D001 during each se gment of a mul ti-speed operation.
L200 2 Inverter Operations and Monitoring 4–15 Jogging Command The Jog input [JG] is used to command the motor to rotate slowly in small increments for manual operation. The speed is limited to 10 Hz. The frequency for the jogging opera- tion is set by parameter A038.
Using Intelligent Input Terminals Operations and Monitoring 4–16 External Signal f or DC Braking When the terminal [DB] is turned ON, the DC braking feature is enabled. Set the follow- ing parameters when the external DC braking terminal [DB] is to be used: • A053 – DC braking delay time setting.
L200 2 Inverter Operations and Monitoring 4–17 Set Second Motor and Special-Set Second Motor If you assign the [SET] or [S-ST] function to an intelligent input terminal, you can select between two sets of motor parameters. The se cond parameters store an alternate set of motor characteristics.
Using Intelligent Input Terminals Operations and Monitoring 4–18 T wo-sta ge Acceleration and Deceleration When terminal [2CH] i s turned ON, the in verter changes the rate of acceleration and deceleration from the initial settings (F002 and F003) to use the second set of accelera- tion/deceleration v alues.
L200 2 Inverter Operations and Monitoring 4–19 Free-run Stop When the terminal [FRS] is turned ON, the in verter stops the output and the motor enters the free-run state (coasting). If terminal [F RS] is turned OFF , the output resumes sending power to the motor if the Run command is s till acti ve.
Using Intelligent Input Terminals Operations and Monitoring 4–20 External T rip When the terminal [EXT] is turned ON, the in verter enters the trip state, indicates error code E12, and stops the output. This is a gene ral purpose interrupt type feature, and the meaning of the error depends on what you conn ect to the [EXT] terminal.
L200 2 Inverter Operations and Monitoring 4–21 Unattended Start Protection If the Run command is already set when po wer is turned ON, the in verter starts running immediately after po werup. The Unattended Start Protection (USP) function prev ents that automatic startup, so that the in verter will not run without outside intervention.
Using Intelligent Input Terminals Operations and Monitoring 4–22 Software Loc k When the terminal [SFT] is turned ON, the data of all the parameters and functions (except the output frequenc y , depending on the setting of B031) is locked (prohibited from editing).
L200 2 Inverter Operations and Monitoring 4–23 Analog Input Current/V oltage Select The [AT] terminal selects whet her the inverter uses the volta ge [O] or current [OI] input terminals for external frequency control. Wh en intelligent input [A T] is ON, you can set the output frequency by applyin g a current inpu t signal at [OI]-[L].
Using Intelligent Input Terminals Operations and Monitoring 4–24 Reset In ver ter The [RS] terminal causes the inverter to execute the reset operati on. If the inverter is in Trip Mode, the reset cancels the Trip state. When the signal [RS] is turned ON and OFF, the inverter executes the reset operation.
L200 2 Inverter Operations and Monitoring 4–25 Thermistor Thermal Pr otection Motors that are equipped with a PTC thermistor can be protected from overheating.
Using Intelligent Input Terminals Operations and Monitoring 4–26 Three-wire Interface Operation The 3-wire interface is an industry standard motor control interf ace. This function uses two inputs for momen tary contact start/stop cont rol, and a third for selecting forward or re verse direction.
L200 2 Inverter Operations and Monitoring 4–27 The diagram belo w sho ws the use of 3-wire cont rol. ST A (Start Motor) is an edge-sensi- ti ve input; an OFF-to-ON transition gi ves the Start command. The control of direction is le vel-sensiti ve, and the direction may be cha nged at any time.
Using Intelligent Input Terminals Operations and Monitoring 4–28 PID ON/OFF and PID Clear The PID loop function is useful for controll ing motor speed to achie ve constant flo w , pressure, temperature, etc. in many proc ess applications. The PID Disable function temporarily suspends PID loop ex ecution via an intelligent input terminal.
L200 2 Inverter Operations and Monitoring 4–29 Remote Contr ol Up and Down Functions The [UP] [D WN] terminal functions can adju st the output frequenc y for remote control while the motor is running. The acceleration ti me and deceleration time of this function is same as normal operation A CC1 and DE C1 (2A CC1,2DEC1).
Using Intelligent Input Terminals Operations and Monitoring 4–30 It is possible for the inv e rter to retain th e frequency set from the [UP] and [D WN] termi- nals through a po wer loss. Parameter C101 enab les/disables the memory . If disabled, the in verter retains the last frequenc y befo re an UP/D WN adjustment.
L200 2 Inverter Operations and Monitoring 4–31 For ce Operation from Digital Operator This function permits a digital operator interface to ov erride the following two settings in the in verter: •.
Using Intelligent Input Terminals Operations and Monitoring 4–32 ADD Frequency Enab le The in verter can add or subtract an of fset v alue to the output frequenc y setting which is specified by A001 (will w ork with an y of the fi ve possible sources).
L200 2 Inverter Operations and Monitoring 4–33 For ce T erminal Mode The purpose of this intelligent input is to allo w a device to force the in verter to allo w control of the follo wing two para m.
Using Intelligent Input Terminals Operations and Monitoring 4–34 Quick Start Enable When the [RD Y] input is ON, the in verter is alw ays in Run Mode, e ven when the motor rotation has stopped. The pupose of the quick star t feature is to improv e (decrease) the startup time of the motor in response to a Run Command.
L200 2 Inverter Operations and Monitoring 4–35 Using Intelligent Output T erminals The intelligent output terminals are programma ble in a similar way to the intelligent input terminals. The in verter has se veral output functions that you can assign individu- ally to three physical logic outputs.
Using Intelligent Output Terminals Operations and Monitoring 4–36 Internal Rela y Output The in verter has an internal relay output with normally open and normally closed contacts (T ype 1 form C). The output signal that controls the relay is configurable; the Alarm Signal is the def ault setting.
L200 2 Inverter Operations and Monitoring 4–37 Output Signal ON/OFF Delay Function Intelligent outputs including terminals [11], [12] , and the output relay , hav e configurable signal transition delays. Each output can de lay either the OFF-to-ON or ON-to-OFF transitions, or both.
Using Intelligent Output Terminals Operations and Monitoring 4–38 Run Signal When the [R UN] signal is selected as an intelligent output terminal, the in verter outputs a signal on that terminal when it is in Run Mode. The output logic is acti ve lo w , and is the open collector type (switch to ground).
L200 2 Inverter Operations and Monitoring 4–39 Frequency Arriv al Signals The F requency Arrival group of outpu ts help coordinate external systems with the current velocity prof ile of the in verter . As the name implies, output [F A1] turns ON when the output fr equency arrives at the standard set frequency (parameter F001).
Using Intelligent Output Terminals Operations and Monitoring 4–40 Frequency arri val output [F A1] uses the standard output frequency (parameter F001) as the threshold for switching. In the figure to the right, Frequenc y Arriv al [F A1] turns ON when the output frequency gets within 0.
L200 2 Inverter Operations and Monitoring 4–41 Overload Adv ance Notice Signal When the output cur rent exce eds a preset value, the [OL] terminal signal turns ON. The parameter C041 sets the ov erload threshold. The ov erload detection circuit operates during po wered motor opera- tion and during regenerati ve braking.
Using Intelligent Output Terminals Operations and Monitoring 4–42 Output Deviation f or PID Control The PID loop error is defined as the magnitude (absolute va lue) of the dif fer- ence between the Setpoint (target v alue) and the Process V a riab le (actual v alue).
L200 2 Inverter Operations and Monitoring 4–43 Alarm Signal The in verter alar m signal is acti ve when a f ault has occurred and it is in the T rip Mode (refer to the diagram at right).
Using Intelligent Output Terminals Operations and Monitoring 4–44 The alarm relay output can be c onf igured in two main w ays: • T rip/Power Loss Alarm – The alarm relay is conf igured as normally closed (C036=1) by default, sho w n belo w (left).
L200 2 Inverter Operations and Monitoring 4–45 Analog Input Disconnect Detect This feature is useful when the in verter re cei ves a speed reference fr om an ex ternal de vice. Upon input signal loss at either the [O ] or [OI] terminal, the in verter normally just decelerates the motor to a stop.
Using Intelligent Output Terminals Operations and Monitoring 4–46 PID Second Stage Output The in verter has a built-in PID loop feature for two-sta ge contr ol, useful for certain applications such as building v entilation or heating and cooling (HV A C).
L200 2 Inverter Operations and Monitoring 4–47 T o use the PID Second Stage Output feature, you will need to choose upper and lower limits for the PV , via C053 and C052 respecti vely . As the timing diagram below sho ws, these are the thresholds Stage #1 in verter uses to turn ON or OFF Stage #2 in verter via the [FBV] output.
Using Intelligent Output Terminals Operations and Monitoring 4–48 Option Code T erminal Symbol Function Name Output State Description 07 FBV Feedback V alue Check ON • T ransitions to ON when the .
L200 2 Inverter Operations and Monitoring 4–49 Netw ork Detection Signal The Network Detection Signal output indicates the general status of network co mmuni- cations. The in verter has a programmable wa tchdog timer to monitor netw ork activity . Parameter C077 sets th e time-out period.
Using Intelligent Output Terminals Operations and Monitoring 4–50 Logic Output Function The Logic Output Function uses the in verter’ s built-in logic feature. Y ou can select any two of the other nine intelligent output opti ons for internal inputs (use C141 and C142).
L200 2 Inverter Operations and Monitoring 4–51 Option Code T erminal Symbol Function Name Output State Description 09 LOG Logic Output Function ON when the Boolean operation specified by C143 has a .
Using Intelligent Output Terminals Operations and Monitoring 4–52 Option Car d Detection Signal The expansion card pro vides a CANopen network interf ace for the in verter . When the card is installed, you can configure an intelli gent input to indicate the netw ork status.
L200 2 Inverter Operations and Monitoring 4–53 Analog Input Operation The L200 2 in verters pro vide for analog input to command the in verter frequency output va lue. The analog input terminal group includes the [L], [OI], [O], and [H] terminals on the control connector , which provide for V oltage [O] or Current [OI] input.
Analog Input Oper ation Operations and Monitoring 4–54 The follo wing table sho w s the av ailable an alog input settings. Parameter A005 and the input terminal [A T] determine the External Frequency Command input terminals that are av ailable, and how the y function.
L200 2 Inverter Operations and Monitoring 4–55 Analog Output Operation In in verter applications it is useful to monitor the in verter operation from a remote location or from the front panel of an in verter enclo sure. In some cases, this requi res only a panel-mounted volt meter .
PID Loop Operation Operations and Monitoring 4–56 PID Loop Operation In standard operation, the in verter uses a reference source sel ected by parameter A001 for the output frequency , which may be a fi x ed v alue (F001), a v ariable set by the front panel potentiometer , or value from an analog input (v oltage or current).
L200 2 Inverter Operations and Monitoring 4–57 PID Loop Configuration The in verter’ s PID loop algorithm is conf igurable for v arious applications.
Configuring the Inver ter for Multiple Motors Operations and Monitoring 4–58 Configuring the In ver ter f or Multiple Motors Simultaneous Connections For some app lications, you may need to connect two or more motors (wired in parallel) to a single in verter’ s output.
L200 2 Inverter Operations and Monitoring 4–59 Having tw o motor profiles lets you store two “per sonalities” for motors in one in verter’ s memory . The in verter allo ws the final selec tion between the two motor ty pes to be made in the f ield through the use of an intelligent input terminal function [SET].
.
In ver ter System Accessories In This Chapter .... p age — Introduction ................. .................... ................ 2 — Component Descriptions .................... ............. 3 — Dynamic Braking ...................................
Introduction Motor Control Accessories 5–2 Intr oduction A motor control system will obviously include a motor and in verter , as well as fuses for safety . If you are connecting a motor to the in verter on a test bench just to get started, that’ s all you may need for no w .
L200 2 Inverter Motor Control Accessories 5–3 Component Descriptions A C Reactors, Input Side This is useful in suppressing harmonics i nduced on the po wer supply lines, or when the main po wer voltage imbalance exceed s 3% (and po wer source capacity is more than 500 kV A), or to smooth out line fluctuations.
Component D escriptions Motor Control Accessories 5–4 Zer o-phase Reactor (RF Noise Filter) The zero-phase reactor helps reduce radiated noise from the in verter wiring. It can be used on the input or output side of the in verter . The example zero-phase reactor sho wn to the right comes with a mounting bracket.
L200 2 Inverter Motor Control Accessories 5–5 Dynamic Braking Intr oduction The purpose of dynamic braking is to improv e th e ability of the in vert er to stop (deceler- ate) the motor and load.
Dynamic Braking Motor Control Accessories 5–6 Use one BRD–E2 braking unit for the braki ng torque listed in th e follo wing table. Note the column meanings in the tables: • Column “ A ” = A verage braking torque from 60 Hz to 3 Hz.
L200 2 Inverter Motor Control Accessories 5–7 400V Class In verters – The follo wing tables specify the braking options for 400V class L200 2 in verters and the braking torque for each option. Y ou can c onnect a single braking unit to the in verter , or two braking units for additional braking torque.
.
T r oub leshooting and Maintenance In This Chapter .... p age — T roubleshooting .......................... ..................... 2 — Monitoring T rip Events , History , & Conditions . 5 — Restoring Factory Default Settings .................
Troubleshooting T roubleshooting and Maintenance 6–2 T r oubleshooting Safety Messages Please read the followin g safety messages before troubleshooting or performing mainte- nance on the in verter and motor system.
L200 2 Inverter T roubleshooting and Maintenance 6–3 T roub leshooting Tips The table below lists typical symptoms and the corresponding solution(s). Symptom/condition Probable Cause Solution The motor will not run. The in verter outputs [U], [V], [W] are not supplying voltage.
Troubleshooting T roubleshooting and Maintenance 6–4 The motor speed will not reach the target frequenc y (desired speed). • If using the analog input, is the current or voltage at [O] or [OI]? • Check the wiring. • Check the potentiometer or signal generating de vice.
L200 2 Inverter T roubleshooting and Maintenance 6–5 Monitoring T rip Events, History , & Conditions Fa ult Detection and Clearing The microprocessor in the in verter detects a v ariety of fault conditions and captures the e vent, record- ing it in a history table.
Monitoring Trip Events , History, & C onditions T roubleshooting and Maintenance 6–6 NO TE: If an EEPR OM error (E08) occurs, be sure to conf irm the parameter data v a lues are still correct. If the po wer is turned OFF while the [RS] (Reset) intelligent input terminal is ON, an EEPR OM error will occur when po wer is restored.
L200 2 Inverter T roubleshooting and Maintenance 6–7 T rip Histor y and In ver ter Status W e recommend that you first f ind the cause of the fault before clearing it. When a fault occurs, the in verter stores important performa nce data at the moment of the fault.
Restoring Factory Default Settings T roubleshooting and Maintenance 6–8 Restoring F actor y Default Settings Y ou can restore all inv erter parameters to th e original factory (default) settings for the intended country of use. After initializing the in verter , use the po werup test in Chapter 2 to get the motor running again.
L200 2 Inverter T roubleshooting and Maintenance 6–9 Maintenance and Inspection Monthly and Y early Inspection Char t Note 1: The life of a capacitor is affected by the ambient te mperature. See “ Capacitor Life Curve ” on p age 6–11 . Note 2: The in verter must be cleaned periodica lly .
Maintenan ce and Inspecti on T roubleshooting and Maintenance 6–10 Megger T est The me gger is a piece of test equipment that us es a high v oltage to determine if an insulation degradation has occurred. F or in vert ers, it is important that the po wer termi- nals be isolated from the Earth GND terminal via the proper amount of insulation.
L200 2 Inverter T roubleshooting and Maintenance 6–11 Spare par ts W e recommend that you stock spare parts to reduce down time, including these parts: Capacitor Life Curve The DC b us inside the in verter uses a large capacitor as sho wn in the diagram below .
Maintenan ce and Inspecti on T roubleshooting and Maintenance 6–12 General In ver ter Electrical Measurements The follow ing table specifies ho w t o measur e ke y system electrical parameters. The diagrams on the ne xt page sho w in verter-mot or systems and the location of measurement points for these parameters.
L200 2 Inverter T roubleshooting and Maintenance 6–13 The figu res belo w show measurement locations for v oltage, c urrent, and po wer measure- ments listed in the table on the pre vious page. The v oltage to be measured is the funda- mental wa ve ef fecti ve v oltage.
Maintenan ce and Inspecti on T roubleshooting and Maintenance 6–14 In ver ter Output V oltage Measurement T echniques T aking voltage measurements around dri ves equipment requires the right equipment and a safe approach. Y ou are working with high voltages and high-frequenc y switching wa veforms that are not pure sinusoids.
L200 2 Inverter T roubleshooting and Maintenance 6–15 IGBT T est Method The follo wing procedure will check the in verter transistors (IGBTs) and diodes: 1. Disconnect input po wer to terminals [R, S, and T] and motor terminals [U, V , and W]. 2. Disconnect any wires from terminals [+ ] and [–] for re generati ve braking.
Warranty T roubleshooting and Maintenance 6–16 W arranty W arranty T erms The warranty period under normal inst allation and handling conditions shall be two (2) years from the da te of manuf acture (“DA TE” on product nameplate), or one (1) year from the date of installation, whichev er occurs first.
Glossar y and Bib liograph y In This Appendix.... p age — Glossary ...................... .................... ................ 2 — Bibliography ..
Glossary Appendix A A–2 Glossary Ambient T emperatur e The air temperature in the cham ber containing a po wered electronic unit. A unit’ s heat sinks rely on a lo wer ambient temperature in order to dissipate heat aw ay from sensiti ve electronics.
L200 2 Inverter Appendix A A–3 DC Braking The in verter DC braking feature stops the A C commutation to the motor , and sends a DC current through the motor windings in order to stop the motor . Also called “DC injection braking, ” it has li ttle ef fect at high speed, and is used as the motor is nearing a stop.
Glossary Appendix A A–4 Fr ee-run Stop A method of stopping a motor , caused when the in verter simply turns OFF its motor output connections. This may allo w the motor and load to coast to a stop, or a mechanical brake may intervene and shorten the deceleration time.
L200 2 Inverter Appendix A A–5 Jogging Operation Usu ally done manually , a jog command from an operator’ s panel requests the motor/dri ve system to run indef initely in a particular direction, until the machine operator ends the jog operation.
Glossary Appendix A A–6 Pr ocess V ariable A physical property of a process that is of interest beca use it affects the quality of the primary task acc omplished by the process. For an industrial ov en, temperature is the process variable. See also PID Loop and Err or .
L200 2 Inverter Appendix A A–7 Setpoint (SP) The setpoint is the desired v alue of a pr ocess v a riable of interest. See also Pr ocess V ariable (PV) and PID Loop . Single-phase power An A C power source consisting of Hot and Neutral wires. An Earth Ground connection usually accompanies them.
Bibliography Appendix A A–8 T or que The rotational force e xerted by a mo tor sh aft. The units of measure- ment consist of the distance (r adius from shaft center axis) and force (weight) applied at that di stance. Units are usually gi ven as pound-feet, ounce-inches, or Ne wton-meters.
ModBus Netw ork Comm unications In This Appendix.... p age — Introduction ................. .................... ................ 2 — Connecting the Inverter to ModBus ................. 3 — Network Protocol Reference ........................... 6 — ModBus Data Listing .
Introduction Appendix B B–2 Intr oduction L200 2 Series in verters ha ve b uilt-in RS- 485 serial communications, featuring the ModBus R TU protocol. The inv erters can conne ct directly to existing factory netw orks or work with ne w networked applications, without any e xtra interface equipment.
L200 2 Inverter Appendix B B–3 Connecting the In ver ter to ModBus Follo w the steps in this section to connect the inv erter to the ModBus network. 1. Open Serial P ort Cov er - The in verter keypad has a hinged dust co ver protecting the serial port connector .
Connecting the Inverter to ModBus Appendix B B–4 4. T erminate Network Wiring - The RS-485 wiring must b e terminated at each physical end to suppress electrical reflections and help decrease transmission errors. The L200 2 communications port does not include a termination resistor .
L200 2 Inverter Appendix B B–5 6. In verter Parameter Setup - The in verter has se veral settings related to ModBus communications. The table belo w lists them together . The Requir ed column indicates which parameters must be set properly to allo w communications.
Network Protoc ol Reference Appendix B B–6 Netw ork Pr otocol Reference T ransmission procedure The transmission between the external cont rol equipment and the in verter tak es the procedure belo w.
L200 2 Inverter Appendix B B–7 Data: • A function command is set here. • The data format used in the L200 2 series is corresponding to the Modb us data format belo w . Function code: Specify a function you want to make the in vert er ex ecute. Function codes av ailable to the L200 2 series are listed belo w .
Network Protoc ol Reference Appendix B B–8 Message Configuration: Response T ransmission time requir ed: • A time period between reception of a query from the master and transmission of a response from the in verter is the sum of the silent interv al (3.
L200 2 Inverter Appendix B B–9 No response occurs: In the cases belo w , the in verter ignores a query and returns no response. • When recei ving a broadcasting query • When detecting a transmis.
Network Protoc ol Reference Appendix B B–10 Explanation of function codes Read Coil Status [01h]: This function reads the status (ON/OFF) of selected coils. An example follows belo w . • Read intelligent input terminals [1] to [5] of an in verter ha ving a slav e address “8.
L200 2 Inverter Appendix B B–11 • When a read coil is outside the defi ned coils, the final coil data to be transmitted contains “0“as the status of the coil outside the range. • When the Read Coil Status command cannot be e xecu ted normally , see the exception response.
Network Protoc ol Reference Appendix B B–12 The data set in the response is as follo ws: When the Read Coil Status command cannot be ex ecuted normally , refer to the exception response. Write in Coil [05h]: This function writes data in a single coil.
L200 2 Inverter Appendix B B–13 When writing in a selected coil fails, see the e xception response. Write in Holding Register [06h]: This function writes data in a specif ied holding register . An example follo ws: • Write “50Hz” as the f irst Multi-speed 0 (A020) in an in verter ha ving slave address “5.
Network Protoc ol Reference Appendix B B–14 Loopback T est [08h]: This function checks a master-sla ve tran smission using any test data. An e xample follows: • Send test data to an in verter ha ving slav e address “1” and receiving the test data from the in verter (as a loopback test).
L200 2 Inverter Appendix B B–15 Write in Coils [0Fh]: This function writes data in consecuti ve coils. An e xample follo ws: • Change the state of intelligent input terminal [1] to [5] of an in verter ha ving a slav e address “5. ” • This e xample assumes the intelligent input te rminals ha ve terminal states listed belo w .
Network Protoc ol Reference Appendix B B–16 Writing in Holding Registers [10h]: This function writes data in consecuti v e holding re gisters. An example follo ws: • Write “3000 seconds” as the fi rst acceleration time 1 (F002) in an in verter ha ving a slav e address “1.
L200 2 Inverter Appendix B B–17 Exception Response: When sending a query (excluding a broadcasting qu ery) to an in verter , the master always requests a response from the in verter . Usually , the in verter returns a response according to the query .
Network Protoc ol Reference Appendix B B–18 Store New Register Data (ENTER command) After being written in a selected holding re gister by the Write in Holding Register command (06h) or in selected holding re gisters by the Write in Holding Registers command (10h), ne w data is temporary and still outside the storage element of the in verter .
L200 2 Inverter Appendix B B–19 ModBus Data Listing ModBus Coil List The follow ing tables list the primary coils fo r the in verter interface to the network. The table legend is gi ven belo w . • Coil Number - The network r e gister address of fset for the coil, in hex and decimal.
ModBus Data Listing Appendix B B–20 Note 1: ON usually when either the control circ uit terminal board or a coil is ON. Among intelligent input terminals, the c ontrol circuit terminal board is a high- priority terminal.
L200 2 Inverter Appendix B B–21 ModBus Holding Registers The follo wing tables list the holding registers for the in verter interface to the network.
ModBus Data Listing Appendix B B–22 — Process V a riable (PV) R W PID loop PV value from the network (set A076=02 to enable this setting), range is 0.0 to 100.0% 0005h 00005 0 to 1000 0.1% D001 Output frequency monitor R Real-time display of output frequency to motor , from 0.
L200 2 Inverter Appendix B B–23 Note 1: Assume that the in verter current rating is 1000 (for D002). The follo wing table lists holding re gist ers for the “D” Group Monitor Functions. D080 T rip counter R Number of trip ev ents, range is 0 to 65535 0011h 00024 0 to 65535 1 trip eve n t List of Holding Registers Func.
ModBus Data Listing Appendix B B–24 D083 T rip monitor 3 R T rip monitor 1: factor code 0026h 00272 — R Frequency 0028h 00273 0.1 Hz R Current 002Ah 00274 0.1 % R V oltage 002Bh 00275 0.1 V R Run time (high) 002Ch 00276 1. h R Run time (lo w) 002Dh 00277 R ON time (high) 002Eh 00278 1.
L200 2 Inverter Appendix B B–25 The table below lists the holding re gisters for the “F” Group Main Prof ile Parameters. Note 1: When the v alue is 10000 (100.0 seconds), a value in the second decimal place is ignored. Holding Registers, “F” Group Main Pr of ile Parameters Func.
ModBus Data Listing Appendix B B–26 The follo wing table lists the holding re gist ers for the “ A” Group Standard Functions. Holding Registers f or “A” Group Standard Functions Func. Code Name R/W Description Network Data Register Range Res.
L200 2 Inverter Appendix B B–27 A014 O–L input acti ve range end voltage R/W The ending point (offset) for the acti ve analog input range, range is 0. to 100. 1024h 04132 0 to 100 1 % A015 O–L input start frequency enable R/W T wo options; select codes: 00 .
ModBus Data Listing Appendix B B–28 A039 Jog stop mode R/W Define ho w end of jog stops the motor; three options: 00 ... Free-run stop 01 ... Controlled deceleration 02 ... DC braking to stop 1049h 04169 0, 1, 2 — A041 T orque boost select R/W T wo options: 00 .
L200 2 Inverter Appendix B B–29 A056 DC braking / edge or le vel detection for [DB] input R/W T wo options; select codes: 00 ... Edge detection 01 ... Le vel detection 1056h 04182 0, 1 — A061 Frequency upper limit setting R/W Sets a limit on output frequency less than the maximum frequency (A004).
ModBus Data Listing Appendix B B–30 A076 PV source setting R/W Selects source of Process V ariable (PV), option codes: 00 ... [OI] terminal (current in) 01 ... [O] terminal (v oltage in) 02 ... Network 03 ... Calculate function output 106Dh 04205 0, 1, 2, 3 — A077 Rev erse PID action R/W T wo option codes: 00 .
L200 2 Inverter Appendix B B–31 A093 (high) Deceleration (2) time setting R/W Duration of 2nd segment of deceleration, range is: 0.01 to 3000 sec. 1076h 04214 1 to 300000 *1 0.1 sec A093 (low) R/W 1 077h 04215 A293 (high) Deceleration (2) time setting, (2nd motor) R/W Duration of 2nd segment of deceleration, range is: 0.
ModBus Data Listing Appendix B B–32 A103 [OI]–[L] input activ e range start current R/W The starting point for the current input range. Range is 0. to 100.% 1083h 04227 0 to 100 1 % A104 [OI]–[L] input activ e range end current R/W The ending point for the current input range.
L200 2 Inverter Appendix B B–33 Note 1: When the v alue is 10000 (100.0 seconds), a value in the second decimal place is ignored (for A092/A292 and A093/A293). A152 Pot. input activ e range end frequency R/W The output frequency corre- sponding to the potentiometer range ending point, range is 0.
ModBus Data Listing Appendix B B–34 The follo wing table lists the holding re gist ers for the “B” Group Fine T uning Functions. “B” Group Fine T uning Functions Func. Code Name R/W Description Network Data Register Range Res. hex dec. B001 Selection of auto matic restart mode R/W Sele ct in verter restart method, four option codes: 00 .
L200 2 Inverter Appendix B B–35 B021 Overload restriction operation mode R/W Select the operating mod e during ov erload conditions, three options, option codes: 00.
ModBus Data Listing Appendix B B–36 B083 Carrier frequency setting R/W Sets the PWM carrier (inter- nal switching frequency), range is 2.0 to 14.0 kHz 10D2h 04306 20 to 140 0.1 Hz B084 Initialization mode (parameters or trip history) R/W Select the type of initializa- tion to occur , two option codes: 00 .
L200 2 Inverter Appendix B B–37 B089 Monitor display select for networked in verter R/W Selects the parameter displayed on the keypad display when the in verter is network ed, 7 options: 01... Output frequency monitor 02... Output current monitor 03.
ModBus Data Listing Appendix B B–38 Note 1: Assume that the in verter current rating is 10000 (for B013/B213). B151 Quick-start enable R/W Enables in verter output for constant ON operation to speed up response, two option codes: 00 ... Disable 01 .
L200 2 Inverter Appendix B B–39 The follo wing table lists the holding regi sters for the “C” Group Intelligent Input Functions. I “C” Group Intelligent T erminal Functions Func. Code Name R/W Description Network Data Register Range Res. hex dec.
ModBus Data Listing Appendix B B–40 C041 Overload lev e l setting R/W Sets the ov erload signal le vel between 0% and 200% (from 0 to two times the rated current of the in verter) 1124h 0438 8 0 to 20000 0.
L200 2 Inverter Appendix B B–41 C081 O input span calibration R/W Scale factor between the external frequenc y command on terminals L – O (voltage input) and the frequency output, range is 0.
ModBus Data Listing Appendix B B–42 Note 1: Assume that the in verter current rating is 10000 (for C041). C143 Logic function select R/W Applies a logic function to calculate [LOG] output state, three options: 00 ... [LOG] = A AND B 01 ... [LOG] = A OR B 02 .
L200 2 Inverter Appendix B B–43 The follo wing table lists the holding regi sters for the “H” Group Motor Constants. “H” Group Motor Constants Func. Code Name R/W Description Network Data Register Range Res. hex dec. H003 Motor cap acity R/W Thirteen selections: 0 .
.
Drive P arameter Settings T ab les In This Appendix.... p age — Introduction ................. .................... ................ 2 — Parameter Settings for Keyp ad Entry .
Introduction Appendix C C–2 Intr oduction This appendix lists the user-programmable parameters for the L200 2 s er i es i n ver t er s an d the default v alues for European and U.S. product types. The right-most column of the tables is blank, so you can record v alues you have changed from the default.
L200 2 Inverter Appendix C C–3 Standar d Functions “A” Gr oup Parameters Default Setting User Setting Func. Code Name -FE(F) (EU) -FU (USA) A001 Frequency source setting 01 00 A201 Frequency source setting, 2nd motor 01 00 A002 Run command source setting 01 02 A202 Run command source setting, 2nd motor 01 02 A003 Base frequenc y setting 50.
Parameter Settings for Keypad Entry Appendix C C–4 A028 Multi-speed 8 setting 0.0 0.0 A029 Multi-speed 9 setting 0.0 0.0 A030 Multi-speed 10 setting 0.0 0.0 A031 Multi-speed 11 setting 0.0 0.0 A032 Multi-speed 12 setting 0.0 0.0 A033 Multi-speed 13 setting 0.
L200 2 Inverter Appendix C C–5 A062 Frequency lo wer limit setting 0.0 0.0 A262 Frequency lo wer limit setting, 2nd motor 0.0 0.0 A063, A065, A067 Jump (center) frequency setting 0.0 0.0 A064, A066, A068 Jump (hysteresis) frequency width setting 0.5 0.
Parameter Settings for Keypad Entry Appendix C C–6 A296 Dec1 to Dec2 frequenc y transi- tion point, 2nd motor 0.0 0.0 A097 Acceleration curve selection 00 00 A098 Deceleration curve selection 00 00 A101 [OI]–[L] input acti ve range start frequency 0.
L200 2 Inverter Appendix C C–7 Fine T uning Functions “B” Group P arameters Default Setting User Setting Func. Code Name -FE(F) (EU) -FU (USA) B001 Selection of automatic restart mode 00 00 B002 Allowable under -voltage po wer failure time 1.0 1.
Parameter Settings for Keypad Entry Appendix C C–8 B228 Overload restriction source selection, 2nd motor 00 00 B031 Software lock mode selection 01 0 1 B080 [AM] analog signal gain 100. 100. B082 Start frequency adjustment 0.5 0.5 B083 Carrier frequency setting 5.
L200 2 Inverter Appendix C C–9 Intelligent T erminal Functions “C” Group P arameters Default Setting User Setting Func. Code Name -FE(F) (EU) -FU (USA) C001 T erminal [1] function 00 00 C201 T e.
Parameter Settings for Keypad Entry Appendix C C–10 C044 PID deviation le vel setting 3.0 3.0 C052 PID FBV function high limit 100.0 100.0 C053 PID FBV function low limit 0.
L200 2 Inverter Appendix C C–11 Motor Constants Functions “H” Group P arameters Default Setting User Setting Func. Code Name -FE(F) (EU) -FU (USA) H003 Motor capacity Specified by the in verter .
Parameter Settings for Keypad Entry Appendix C C–12 Expansion Car d Functions “P” Group P a rameters Default Setting User Setting Func. Code Name -FE(F) (EU) -FU (USA) P044 Network comm watchdog timer 1.
CE–EMC Installation Guidelines In This Appendix.... p age — CE–EMC Installation Guidelines ..................... 2 — Hitachi EMC Recommendations .
CE–EMC Installation Guidelines Appendix D D–2 CE–EMC Installation Guidelines Y ou are required to satisfy the EMC directive (89/336/EEC) when using an L200 2 in verter in an EU country . T o satisfy the EMC directive an d to comply with standard, follow the guidelines in this section.
L200 2 Inverter Appendix D D–3 4. T ake measures to minimize interference that is frequently coupled in through installa- tion cables. • Separate interfering cables with 0.25m minimum from cables susceptible to inter- ference. A partic ularly critical point is laying para llel cables over longer distances.
CE–EMC Installation Guidelines Appendix D D–4 Some L200 2 in verters designed for use in Europe (–xxxLFEF/xxxHFEF models) ha ve built-in line f ilters.
L200 2 Inverter Appendix D D–5 L1 L2 L3 PE L200 2 in ver ter with book-type filter M 3~.
Hitachi EMC Recommendations Appendix D D–6 Hitachi EMC Recommendations W ARNING: This equipment should be installed, adjusted, and serviced by qualified personal familiar with construction and ope ration of the equipment and the hazards in volv ed. Failure to observ e this precaution could result in bodily injury .
Inde x A A Group functions 3–10 AC reactors 5–3 Acceleration 1–22 , 3–9 characteristic curves 3–28 second function 3–26 two-stage 4–18 Access levels 3–5 , 3–39 , 4–22 Accessories 5.
Index –2 Choke 2–7 , 5–4 , A–2 Chopper frequency 3–41 Circuit breaker sizes xiv , 2–17 Clearance for ventilation 2–10 Coasting 3–42 Connectors logic terminals 2–4 removal 2–4 seria.
L200 2 Inverter Index –3 G Glossary of terms A–2 H H Group parameters 3–63 Harmonics A–4 History of trip events 3–7 Horsepower A–4 I IGBT 1–18 , A–4 test method 6–15 Index of termina.
Index –4 N Nameplate 1–4 Navigational map 2–26 , 3–4 trip events 6–7 NEC A–5 NEMA definition A–5 rated installation 1–3 Network communications 1–23 , B–2 detection signal 4–49 , .
L200 2 Inverter Index –5 R Ratings label 1–4 Reactance A–6 Read/write copy unit 1–3 Ready input 4–34 Rectifier A–6 Reduced torque 3–18 Regenerative braking A–6 Regulation A–6 Regulat.
Index –6 T Tachometer A–7 Technical support xviii Term definitions A–2 Terminal/program source configuration 2–5 , 2–27 , 3–11 Terminals arrangement 2–19 listing 4–7 torque specs xiii .
Een belangrijk punt na aankoop van elk apparaat Hitachi L2002 (of zelfs voordat je het koopt) is om de handleiding te lezen. Dit moeten wij doen vanwege een paar simpele redenen:
Als u nog geen Hitachi L2002 heb gekocht dan nu is een goed moment om kennis te maken met de basisgegevens van het product. Eerst kijk dan naar de eerste pagina\'s van de handleiding, die je hierboven vindt. Je moet daar de belangrijkste technische gegevens Hitachi L2002 vinden. Op dit manier kan je controleren of het apparaat aan jouw behoeften voldoet. Op de volgende pagina's van de handleiding Hitachi L2002 leer je over alle kenmerken van het product en krijg je informatie over de werking. De informatie die je over Hitachi L2002 krijgt, zal je zeker helpen om een besluit over de aankoop te nemen.
In een situatie waarin je al een beziter van Hitachi L2002 bent, maar toch heb je de instructies niet gelezen, moet je het doen voor de hierboven beschreven redenen. Je zult dan weten of je goed de alle beschikbare functies heb gebruikt, en of je fouten heb gemaakt die het leven van de Hitachi L2002 kunnen verkorten.
Maar de belangrijkste taak van de handleiding is om de gebruiker bij het oplossen van problemen te helpen met Hitachi L2002 . Bijna altijd, zal je daar het vinden Troubleshooting met de meest voorkomende storingen en defecten #MANUAl# samen met de instructies over hun opplosinge. Zelfs als je zelf niet kan om het probleem op te lossen, zal de instructie je de weg wijzen naar verdere andere procedure, bijv. door contact met de klantenservice of het dichtstbijzijnde servicecentrum.