Hit achi Universal S t orage Plat form VM Installation Planning Guide F AS T F IN D L IN K S Document Organization Product Version Getting Help Contents MK-97RD6679-00.
Copyright © 2007 Hitachi Data Systems Corporation, ALL RIGHTS RESERVED Notice: No part of th is publicat ion may be reproduced or transmitted in any form or by any means, electronic or mechanical, in.
Contents iii Hitachi Un iversal Stor age Platfo rm VM Insta llation Plann ing Guide Contents Preface ................................................................................................... v Safety and Environmental Notices ...............
Power Specification s and Requirements ............................................................ 2-13 Power Specifications and Power Supplies ................................................... 2-13 Breaker Configurations ..........................
Preface v Hitachi Un iversal Stor age Platfo rm VM Insta llation Plann ing Guide Preface This document provides installation and configuration planning info rmation for the Hitachi Universal Storage Platfo rm VM (USP VM) storage system.
Safety and Environmental Notices Federal Communications Commission (FCC) Statement This equipment has been tested and found t o comply with the limits for a Class A digital device, pursuant to part 15 of the FCC Rules.
Product Version This document revision applies to Universal Storage Platform VM microcode 60-02-0 x and higher. Document Revision Level Revision Date Description MK-97RD6679-00 November 2007 Initial releas e, supersedes and replaces MK-97RD6079 Changes in this Revision • Added information on the 750-GB hard disk drive ( Table 2-2 , Table 2-8 ).
Document Conventions The term “Universal Storage Platform VM” refers to all models of the Universal Storage Platform VM storage system, unless otherwise noted. This document uses the following icon s to draw attention to information: Icon Meaning Description Note Calls attention to important and/or addi tional infor mat ion.
Getting Help If you need to call the Hitachi Data Systems Support Center, make sure to provide as much information about the problem as possible, including: • The circumstances surrounding the error or failure. • The exact content of any error message(s) displayed on the host system(s).
x Preface Hitachi Un iversal Stor age Platfo rm VM Insta llation Plann ing Guide.
1 Planning for Installation 1-1 Hitachi Un iversal Stor age Platfo rm VM Insta llation Plann ing Guide Planning for Installation This chapter describes the requirements and procedures for planning to install the Universal Storage Platform VM.
Responsibilities The responsibilities for installation planning are shared by the customer and the Hitachi Data Systems account team. The required installation planning tasks must be scheduled and completed to ensure successful and efficient installation of the Universal Storage Platform VM.
Installation Planning Tasks The customer is responsible for performing the following tasks, with assistance as needed from the Hitachi Data Systems account team, to prepare for installation of the Universal Storage Platform VM storage system: 1.
Installation Planning Checklist Complete the checklist below (online or hardcopy) to verify that all installation requirements for the Universal Stor age Platform VM ha ve been met. Successful completion of this checklist ( Yes is checked for all entries) will ensure smooth and efficient installation of the Universal Storage Platform VM.
Installati on Planning Checkl ist Yes No Safety Is the data center eq uipp ed to protect equipmen t from fire? Is the data center free of haz ards (e.g ., cables that ob st ruct access)? Delivery Is the receiving area adequate for equipment delivery and unloading? (overall heigh t: 84 in, 2.
1-6 Planning for Installation Hitachi Un iversal Stor age Platfo rm VM Insta llation Plann ing Guide.
2 Insta llation Req uirements 2-1 Hitachi Un iversal Stor age Platfo rm VM Insta llation Plann ing Guide Installation Requirements This chapter provides the installation requirements for the Univers al Storage Platform VM storage system.
Safety Requirements The safety requirements for Universal Storage Platform VM installation are: • Safety regulations: The data ce nter must comply with all applicable safety regulations, standards, and requirements. • Fire protection: The data center must have an operatio nal fire protection system.
Delivery Requirements The customer site must accommodate the delivery and movement of the equipment to the installation location in the data center. The delivery requirements for Universal St orage Pl.
Storage Requirements If the delivered equipment needs to be stored after delivery and prior to installation, the storage location must meet the environmental requirements for the Universal Storage Platform VM (see Table 2-1 ).
Facilities Requirements The customer site must meet the following facilities requirements: • General: The data center must be fully operational ( e.g., power, air conditioning, cabling, fire protection system). • Floor: The data center must have a tiled raised floor.
Physical Specifications and Requirements Figure 2-1 shows a physical overview of the Universal Storage Platform VM. The physical specifications and requirements for the USP VM incl ude: • Dimensions.
Dimensions and Weight Figure 2-2 shows the dimensions of t he single-rack configuration. Figure 2-3 shows the dimensions of the twin-rack configuration. Table 2-2 lists the dimension and weight specifications for the Universal Storage Platform VM components.
FRONT VI E W TOP V I EW 2001 mm 601 mm 601 mm 1046 mm TBD Figure 2-3 Physical Dimensions: Twin-Rack Config ura tion 2-8 Inst allation Req uirements Hitachi Un iversal Stor age Platfo rm VM Insta llati.
Table 2-2 Component Specifications: Weight and Di mension Dimension (mm) Model Number Weight (kg) Width Depth Height DKC615I-5 70 445 800 438 DKC-F615I-B2 80.5 445 647 522 DKC-F615I-SBX 13 445 800 84 DKC-F615I-LGAB 11 — — — DKC-F615I-PLUC 2.0 — — — DKC-F615I-PHUC 4.
Service Clearance, Floor Cu tout, and Floor Load Rating This section specifies the service clearance requirements (a + b) for the Universal Storage Platform VM storage system, based on the floor load rating and the clearance (c), and the required floor cutouts for cabling.
(Uni t : m m ) Floor cutout ar ea for cables Caste r Screw jack Serv ice clearance G Grid pa nel (over 450 mm x 450 mm) 601 Front G DKC615 a *1 B *1 195 65 125 65 835 63 90 74 61.
(U nit: m m) 1220 G DKC615 a *1 b 195 125 65 835 655 63 90 61.5 74 457 482 585 Floor cut out area for cables Cas t e r Scr e w j ac k Servi ce c lea ran ce G Grid panel (over 450mm x 450mm) *1 215 150 195 215 G 482 585 DKC615 457 74 61.
Power Specifications and Requirements This section describes the power specifications and requirements for the Universal Storage Platform VM storage system: • Power Specifications and Power Supplies.
Prim ary R ack PDU PDU DKU PS Power Cable (AC Input 1) Power Cable (AC Input 2) DKC PS1 1 PS12 PS21 PS22 CL1 CL2 PS31 PS30 × 15 DKU-R0 PS21 PS20 × 15 PS1 1 PS10 × 15 PS01 PS00 × 15 PS31 PS30 × 15.
Breaker Configurations For both racks, AC power is supplied to each power distribution uni t (PDU) from the breaker. Figure 2-7 and Figure 2-8 show the breaker configurations for the primary and secondary racks, respectively.
Power Connectio n The AC power input for the Universal Storage Platform VM has a duplex PDU structure. This duplex structure enables the entire rack to remain powered on in the event that power is removed from one of the two power distribution panels (PDPs).
DKU-R2 DKU-R3 DKC DKU-R1 DKU-R0 AC Input Line Branch Distribution Box To U P S For the AC input power , connect one of the duplexes PDUs t o the UPS and the other one to the PDP .
Input Voltage and Input Frequency Table 2-6 lists the input voltage and input frequency requirements for the Universal Storage Platform VM. Table 2-6 Input Voltage and Input Freque ncy Requirements Fr.
Environmental Specifications and Requirements The environmental specifications and requirements for the Universal Storage Platform VM include: • Temperature, Humidity, and Altitude • Heat Output, .
Heat Output, Power Consumption, and Air Flow Table 2-8 lists the power consumption and heat output specifications and the air flow requirements for the Universal Storage Platform VM. These data generally apply to both 60-Hz and 50- Hz storage systems.
Loudness The acoustic emission values [loudness in dB(A)] for the Universal Storage Platform VM storage system are: Front/rear = 65 dB(A) Both sides = 65 dB(A) Vibration and Shock Table 2-9 lists the vibration and shock tolerance data for the U niversal Storage Platform VM.
Operational Requirements The operational requirements for the Universal Storage Platform VM include: • LAN connection (or RJ-11 analog phone line) for Hi-Track ® The Hi-Track maintenance support to.
A Units and Unit Conversions A-1 Hitachi Un iversal Stor age Platfo rm VM Insta llation Plann ing Guide Units and Unit Conversions Table A-1 provides conversions for metric and standard (U.S.) units of measure associated with the Hitachi Universal Storage Platform VM storage system.
A-2 Units and Unit Conversions Hitachi Un iversal Stor age Platfo rm VM Insta llation Plann ing Guide.
Acronyms and Abbreviations Acronyms-1 Hitachi Un iversal Stor age Platfo rm VM Insta llation Plann ing Guide Acronyms and Abbreviations A ampere ASTM American Society for Testing and Materials BED bac.
Acronyms-2 Acronyms and Abbreviations Hitachi Un iversal Stor age Platfo rm VM Insta llation Plann ing Guide LW long wavelen gth m meter mA milliampere max.
Hitachi Un iversal Stor age Platfo rm VM Insta llation Plann ing Guide.
Hitachi Data Systems Corporate Headquarters 750 Central Expressway Santa Clara, California 95050- 2627 U.S.A. Phone: 1 408 970 1000 www.hds.com info@hds.co m Asia Pacific and Americas 750 Central Expressway Santa Clara, California 95050- 2627 U.S.A. Phone: 1 408 970 1000 info@hds.
Een belangrijk punt na aankoop van elk apparaat Hitachi MK-97RD6679-00 (of zelfs voordat je het koopt) is om de handleiding te lezen. Dit moeten wij doen vanwege een paar simpele redenen:
Als u nog geen Hitachi MK-97RD6679-00 heb gekocht dan nu is een goed moment om kennis te maken met de basisgegevens van het product. Eerst kijk dan naar de eerste pagina\'s van de handleiding, die je hierboven vindt. Je moet daar de belangrijkste technische gegevens Hitachi MK-97RD6679-00 vinden. Op dit manier kan je controleren of het apparaat aan jouw behoeften voldoet. Op de volgende pagina's van de handleiding Hitachi MK-97RD6679-00 leer je over alle kenmerken van het product en krijg je informatie over de werking. De informatie die je over Hitachi MK-97RD6679-00 krijgt, zal je zeker helpen om een besluit over de aankoop te nemen.
In een situatie waarin je al een beziter van Hitachi MK-97RD6679-00 bent, maar toch heb je de instructies niet gelezen, moet je het doen voor de hierboven beschreven redenen. Je zult dan weten of je goed de alle beschikbare functies heb gebruikt, en of je fouten heb gemaakt die het leven van de Hitachi MK-97RD6679-00 kunnen verkorten.
Maar de belangrijkste taak van de handleiding is om de gebruiker bij het oplossen van problemen te helpen met Hitachi MK-97RD6679-00 . Bijna altijd, zal je daar het vinden Troubleshooting met de meest voorkomende storingen en defecten #MANUAl# samen met de instructies over hun opplosinge. Zelfs als je zelf niet kan om het probleem op te lossen, zal de instructie je de weg wijzen naar verdere andere procedure, bijv. door contact met de klantenservice of het dichtstbijzijnde servicecentrum.