Gebruiksaanwijzing /service van het product SJ100 van de fabrikant Hitachi
Ga naar pagina of 214
HIT A CHI SJ100 Series In ver ter Instruction Man ual • Single-phase Input 200V Class • Three-phase Input 200V Class • Three-phase Input 400V Class After r eading this manual, keep it handy f or futur e r eference. Hitachi Industrial Equipment Systems Co.
SJ100 Inverter i Saf ety Messa ges For the best results with the SJ100 Series in v erter , carefully read this manual and all of the warning labels attached to the in v erter before installing and operating it, and follo w the instructions exactly . K eep th is manual handy for quick reference.
ii General Precautions - Read These Fir st! W ARNING: This equipment should be installed, adjusted, and serviced by qualified electrical maintenance personnel familiar w ith the construction and operation of the equipment and the hazards in volv ed. Failure to observe this precaution could result in bodily injury .
SJ100 Inverter iii W ARNING: Rotating shafts and above -ground electr ical potentials can be hazardous. Therefore, it is strongly recommended that all electrical work conform to the National Electrical Codes and local regulations. Inst allation , alignment and maintenance should be performed only by qualified p ersonnel.
iv Inde x to W arnings and Cautions in This Manual Installation - Cautions fo r Mounting Pr ocedures Wiring - W arnings for Electrical Practices and Wire Specifications CA UTION: The in verter is shipped w ith a plastic cover o ver the top v ent grill.
SJ100 Inverter v Wiring - Cautions f or Electrical Practices W ARNING: “Suitable for use on a circui t capable of deli vering not more than 5,000 rms symmetrical amperes, 480 V maximum. ” For models with suf fix H. .... 2–13 HIGH V OL T A GE: Be sure to ground the unit.
vi P owerup T est Caution Messages CA UTION: Remarks for using ground fault interrupter break ers in the main po wer supply: Adjustable freque nc y in verters with CE-f ilters (RFI- filter) and shielded (screened) motor cables ha ve a higher leakage current to ward Earth GND.
SJ100 Inverter vii W arnings for Configuring Drive P arameters Cautions f or Configuring Drive P arameters W arnings for Operations and Monitoring W ARNING: When parameter B_12, lev e l of electronic .
viii Cautions f or Operations and Monitoring W ARNING: Be sure not to touch the insi de of the energized in verter or to put any conducti ve object into it.
SJ100 Inverter ix W arnings and Cautions for T r oubleshooting and Maintenance General W arnings and Cautions W ARNING: Nev er modify the unit. Otherwise, there is a danger of electric shock and/ or injury .
x CA UTION: Do not stop operation by switching OFF electromagnetic contactors on the primary or secondary sides of the in verter . When there has been a sudden po wer failure while an operation instru ction is acti ve, then the unit may restart operation automatical ly after the power failure has end ed.
SJ100 Inverter xi CA UTION: SUPPRESSION FOR NOISE INTERFERENCE FR OM INVER TER The in verter uses many semiconductor switc hing elements such as transistors and IGBTs. Thus, a radio recei ver or measuring instrument located near the in verter is susceptible to noi se interference.
xii CA UTION: When the EEPR OM error E08 occurs, be sure to conf irm the setting v alues again. CA UTION: When using normally closed acti ve state settings (C_11 to C_16) for e xter- nally commanded F.
SJ100 Inverter xiii T erminal Tightening T or que and Wire Size The wire size range and tightening torque fo r f ield wiring terminals are presented in the table below . Wire Connectors W ARNING: Field wiring connections must be made by a UL Listed and CSA Certified ring lug terminal connector sized for the wire gauge being used.
xiv Cir cuit Breaker and Fuse Sizes The in verter’ s connections to input power mu st include UL Listed in verse time circuit breakers with 600V rating, or UL Listed fuses as sho wn in the table below .
xv SJ100 Inverter Safety Messages Hazardous High Voltage i General Precautions - Read These Fi rst! ii Index to Warnings and Cautions in This Manual iv General Warnings and Cautions ix UL ® Cautions,.
xvi Chapter 4: Operations and Monitoring Introduction 4–2 Connecting to PLCs and Other Devices 4–4 Example Wiring Diagram 4–5 Using Intelligent Input Terminals 4–8 Using Intelligent Output Ter.
SJ100 Inverter xvii Revisions Revision History T able No. Revision Comments Date of Issue Operation Manual No. Initial release of manual NB585X April 1999 NB585X 1 Re vision A Added 7.
xviii Contact Inf ormation NO TE: T o receive technical support for the Hita chi in verter you purchased, contact the Hitachi in verter deal er from whom you purchased the unit, or the sales of f ice or factory contact listed abov e. Please be prepared to provide the follo wing in verter nameplate information: 1.
Getting Star ted In This Chapter ... p age — Introduction ................. .................... ................ 2 — SJ100 Inverter S pecifications ................ .......... 5 — Introduction to V ariable-Frequency Drives .... 18 — Frequently Asked Questions .
Introduction Getting Star ted 1–2 Intr oduction Main Features Congratulations on your purchase of an SJ100 Series Hitachi in verter! This in verter dri ve features state-of-the-art circuitry and components to provide high performance. The housing footprint is exceptionally small, gi ven the size of the corresponding motor .
SJ100 Inverter Getting Star ted 1–3 A full line of accessories from Hitachi is av ailabl e to complete your motor application. These include: • Digital remote operator ke ypad • Braking resistor.
Introduction Getting Star ted 1–4 In ver ter Specifications Label The Hitachi SJ100 in verters hav e product labels located on the right side of the housing, as pictured belo w . Be sure to verify that the specifications on the labels match your power source, motor , and application safety requirements.
SJ100 Inverter Getting Star ted 1–5 SJ100 In ver ter Specifications Model-specific tables f or 200V and 400V class in ver ters The follo wing tables are specif ic to SJ100 in verters for the 200V and 400V class model groups. Note that “ General Specif ications ” on page 1–9 apply to both voltage class groups.
SJ100 Inverter Specificatio ns Getting Star ted 1–6 Footnotes for the preceding table and the tables that follo w: Note 1: The protection method conforms to JEM 1030.
SJ100 Inverter Getting Star ted 1–7 SJ100 In verter Specif ications, continued... Item 200V Class Specif ications, continued SJ100 in verters, 200V models CE version 015NFE 022NFE — — — UL version 015NFU 022NFU 037LFU 055LFU 075LFU Applicable motor size *2 kW 1.
SJ100 Inverter Specificatio ns Getting Star ted 1–8 Item 400V Class Specif ications SJ100 in verters, 400V models CE version 004HFE 007HFE 015HFE 022HFE UL version 004HFU 007HFU 015HFU 022HFU Applicable motor size *2 kW 0.4 0.75 1.5 2.2 HP 1/2 1 2 3 Rated capacity (460V) kV A 1.
SJ100 Inverter Getting Star ted 1–9 General Specifications The follo wing table applies to all SJ100 in verters. Item 400V Class Specif ications, continued SJ100 in verters, 400V models CE version 030HFE 040HFE 055HFE 075HFE UL version — 040HFU 055HFU 075HFU Applicable motor size *2 kW 3.
SJ100 Inverter Specificatio ns Getting Star ted 1–10 Input signal Freq. setting Operator panel Up and Down k eys / V alue setting s Potentiometer Analog setting External signal *8 0 to 10 VDC (input.
SJ100 Inverter Getting Star ted 1–11 Signal Ratings Detailed ratings are in “ Specifications of Control and Logic Connections ” on page 4–6 . Signal / Contact Ratings Built-in power for inputs.
SJ100 Inverter Specificatio ns Getting Star ted 1–12 Derating Curves The maximum av ailable in verter current output is limited by the carrier frequency and ambient temperature. The carrier frequency is the in verter’ s internal power switching frequency , settable from 0.
SJ100 Inverter Getting Star ted 1–13 Derating curves, continued... SJ100–007NFE/NFU 0 . 5 2468 1 0 1 2 1 4 1 6 70% 80% 90% 100% 95% 85% 75% % of rated output current Carrier frequency kHz SJ100–0015NFE /NFU 0 . 5 2468 1 0 1 2 1 4 1 6 70% 80% 90% 100% 95% 85% 75% % of rated output current Carrier frequency kHz SJ100–022NFE/NFU 0 .
SJ100 Inverter Specificatio ns Getting Star ted 1–14 Derating curves, continued... SJ100–037LF/LFU 0 . 5 2468 1 0 1 2 1 4 1 6 40% 60% 80% 100% 90% 70% 50% % of rated output current Carrier frequency kHz SJ100–055LFU 0 . 5 2468 1 0 1 2 1 4 1 6 70% 80% 90% 100% 95% 85% 75% % of rated output current Carrier frequency kHz SJ100–075LFU 0 .
SJ100 Inverter Getting Star ted 1–15 Derating curves, continued... SJ100–004HFE/HFU 0 . 5 2468 1 0 1 2 1 4 1 6 40% 60% 80% 100% 90% 70% 50% % of rated output current Carrier frequency kHz SJ100–007HFE/HFU 0 . 5 2468 1 0 1 2 1 4 1 6 40% 60% 80% 100% 90% 70% 50% % of rated output current Carrier frequency kHz SJ100–015HFE/HFU 0 .
SJ100 Inverter Specificatio ns Getting Star ted 1–16 Derating curves, continued... SJ100–022HFE/HFU 0 . 5 2468 1 0 1 2 1 4 1 6 40% 60% 80% 100% 90% 70% 50% % of rated output current Carrier frequency kHz SJ100–040HFE/HFU 0 .
SJ100 Inverter Getting Star ted 1–17 Derating curves, continued... SJ100–075HFE/HFU 0 . 5 2468 1 0 1 2 1 4 1 6 70% 80% 90% 100% 95% 85% 75% % of rated output current Carrier frequency kHz.
Introduction to Varia ble-Frequency Drives Getting Star ted 1–18 Intr oduction to V ariable-Frequency Drives The Purpose of Motor Speed Contr ol for Industry Hitachi in verters provide speed control fo r 3-phase A C induction motors. Y ou connect A C power to the in verter , and connect the in verter to the motor .
SJ100 Inverter Getting Star ted 1–19 T orque and Constant V olts/Her tz Operation In the past, A C variab le speed dri ves used an open loop (scalar) technique to control speed. The constant-volts-per -hertz operation maintains a constant ra tio between the applied voltage and the applied frequenc y .
Introduction to Varia ble-Frequency Drives Getting Star ted 1–20 In ver ter Output to the Motor The A C motor must be connected only to the in verter’ s output terminals. The output terminals are uniquely labeled (to dif ferentiate them from the input terminals) with the designations U/T1, V/T2, and W/T3.
SJ100 Inverter Getting Star ted 1–21 Intelligent Functions and P arameters Much of this manual is de voted to describ ing how to use in ve rter functions and how to conf ig- ure in verter parameters. The in verter is micro- processor- controlled, and has many indepen dent functions.
Introduction to Varia ble-Frequency Drives Getting Star ted 1–22 V elocity Pr ofiles The SJ100 in verter is capable of sophisticated speed control. A graphi cal representation of that capability will help you understand and conf igure the associated parameters.
SJ100 Inverter Getting Star ted 1–23 Frequentl y Asked Questions Q. What is the main advantage in using an in verter to dri ve a motor , c ompared to alternativ e solutions? A. An in verter can vary the motor speed wi th very little loss of eff iciency , unlike mechanical or hydraulic speed control solutions.
Frequently Asked Qu estions Getting Star ted 1–24 Q. Why does the manual or other document ation use termin ology such as “200V class” instead of naming the actual v oltage, such as “230 V A C?” A. A specific in verter model is set at the factory to work across a v oltage range particular to the destination country fo r that model.
SJ100 Inverter Getting Star ted 1–25 Q. Ho w will I kno w if my application will require resistiv e braking? A. For ne w applications, it may be dif f icult to tell before you actually test a motor/driv e solution.
In ver ter Mounting and Installation In This Chapter .... p age — Orientation to Inverter Features ...................... 2 — Basic System Description .................. ............. 5 — S tep-by-S tep Basic Installation .......................
Orientation to I nverter Features In v er ter Mounting and Installation 2–2 Orientation to In ver ter Features Unpack ing and Inspection Please take a fe w moments to unpack your new SJ100 in verter and perform these steps: 1. Look for any damage that may ha ve occurred during shipping.
SJ100 Inverter In v er ter Mounting and Installation 2–3 2. Second-le vel access - Locate the lift tab at the right lower corner of the front panel near the safety warning messa ge. Lift the corner to swi ng the half-door around to the left. This exposes fou r more control buttons and some connectors.
Orientation to I nverter Features In v er ter Mounting and Installation 2–4 3. Third-level access - First, ensure no po wer source of any kind is connected to the in verter . If power has been connected, wait fi ve minutes after po werdown and v erify the Power LED is OFF to proceed.
SJ100 Inverter In v er ter Mounting and Installation 2–5 Basic System Description A motor control system will obviously include a motor and in verter , as well as a breaker or fuses for safety . If you are connecting a motor to the in verter on a test bench just to get started, that’ s all you may need for now .
Step-by-St ep Ba sic Installation In v er ter Mounting and Installation 2–6 W ARNING: In the cases below in volving a gene ral-purpose in verter , a large peak current can flo w on the power supply side , sometimes destro ying the con verter module: 1.
SJ100 Inverter In v er ter Mounting and Installation 2–7 Choosing a Mounting Location Step 1: Study the follo wing caution messages associated with mounting the in verter . This is the time when mistakes are most likely to occur that will result in expensi ve re work, equipment damage, or personal injury .
Step-by-St ep Ba sic Installation In v er ter Mounting and Installation 2–8 Ensure Adequate V e ntilation Step 2: T o summarize the caution messages—you wi ll need to find a solid, non-flamma- ble, vertical surface that is in a relati vely clean and dry en vironment.
SJ100 Inverter In v er ter Mounting and Installation 2–9 3. When installing the in verter in an encl osure, maintain the clearance around the in verter and verify that its ambient temperature is within specif ication when the enclosure door is closed.
Step-by-St ep Ba sic Installation In v er ter Mounting and Installation 2–10 Dimensional drawings, continued... FAN MODEL External Dimensions SJ 100 -004HFE -004HFU -007NFE -007NFU 98(3.86) 118(4.65) 5(0.20) 130(5.12) 5(0.20) Air Air 98(3.86) 118(4.
SJ100 Inverter In v er ter Mounting and Installation 2–11 Dimensional drawings, continued ... FAN SJ100 -015NFE -015NFU SJ100 -022NFE -022NFU -030HFE -037LFU -040HFE -040HFU 140(5.51) 168(6.61) 180(7.08) 128(5.04) 5(0.20) 5(0.20) 7(0.28) Ground Terminal 164(6.
Step-by-St ep Ba sic Installation In v er ter Mounting and Installation 2–12 Dimensional drawings, continued... NO TE: Model SJ100-075LFU has (2) fans. All other models in this housing ha ve (1) fan. 182 (7.17) 160 (6.30) 236 (9.29) 170 (6.69) Air Air 257 (10.
SJ100 Inverter In v er ter Mounting and Installation 2–13 Prepare for Wiring Step 5: It is ve ry important to perform the wi ring steps carefully and correctly . Before proceeding, please study the caution and warning messages belo w . W ARNING: “Use 60/75°C Cu wire only” or equiv alent.
Step-by-St ep Ba sic Installation In v er ter Mounting and Installation 2–14 Determining Wire and Fuse Sizes The maximum motor currents in your applic ation determines the recommend ed wire size.
SJ100 Inverter In v er ter Mounting and Installation 2–15 T erminal Dimensions and T or que Specs The terminal scre w dimensions for all SJ100 in verters are listed in table below . This information is useful in sizing spade lug or ring lug connectors for wire terminations.
Step-by-St ep Ba sic Installation In v er ter Mounting and Installation 2–16 Please use the terminal arrangement be lo w corresponding to your in verter model. NO TE: An in verter po wered by a portable po we r generator may recei ve a disto rted power w a veform, o verheating the generator .
SJ100 Inverter In v er ter Mounting and Installation 2–17 CA UTION: Be sure not to connect an A C po wer supply to the output terminals. Other- wise, there is the possibility of damage to th e in verter and the danger of injury and/or fir e .
Step-by-St ep Ba sic Installation In v er ter Mounting and Installation 2–18 Wire the In ver ter Output to Motor Step 7: The process of motor selection is beyond the scop e of this manual. Ho we ver , it must be an A C induction motor with three phases.
SJ100 Inverter In v er ter Mounting and Installation 2–19 Uncover the In ver ter V ents Step 8: After mounting and wiring the in verter , remov e any cov e rs from the in verter housing. This includes material ov er the side ventilation ports. Remov e the square cov er panel at the top of the housing.
Powerup Test In v er ter Mounting and Installation 2–20 Pre-test and Operational Precautions The follow ing instructions apply to the powerup test, or to an y time the inv erter is powered and operating. Please study the follo wing instructions and messages before proceeding with the po werup test.
SJ100 Inverter In v er ter Mounting and Installation 2–21 Using the Fr ont P anel Ke ypad Fr ont P anel Introduction Please take a moment to familiarize yourself with the keypad layout sho wn in the figure belo w . These are the visible controls and i ndicators when the front panel door is closed.
Using the Front Panel Keypad In v er ter Mounting and Installation 2–22 • Parameter Display - A 4-digit, 7-se gment display for parameters and function codes. • Display Units, Hertz/Amperes - One of these LEDs will be ON to indicate the units associated with the paramete r display .
SJ100 Inverter In v er ter Mounting and Installation 2–23 Ke ypad Navigational Map The SJ100 Series in verter dri ves hav e ma ny programmable functi ons and parameters. Chapter 3 will cov er these in detail, but you need to access just a few items to perform the po werup test.
Using the Front Panel Keypad In v er ter Mounting and Installation 2–24 Selecting Functions and Editing P arameters In order to run the motor for the po werup test, this section will show ho w to: .
SJ100 Inverter In v er ter Mounting and Installation 2–25 Select the Potentiometer f or Speed Command - The motor speed may be controlled from the follo wing sources: • Potentiometer on front pane.
Using the Front Panel Keypad In v er ter Mounting and Installation 2–26 Conf igure the In vert er f or the Number of Motor P oles - The number of magnetic poles of a motor is determined by the moto r’ s internal winding arrangement. The specifi- cations label on the motor usually indicate s its number of poles.
SJ100 Inverter In v er ter Mounting and Installation 2–27 Monitoring P arameters with the Displa y After using the ke ypad for parameter editing, it’ s a good idea to switch the in verter from Program Mode to Monitor Mode and close the panel door (puts the ke ys for parameter editing out of sight).
Using the Front Panel Keypad In v er ter Mounting and Installation 2–28 P owerup T est Obser vations and Summary Step 10: Reading this section will help you make some useful observ ations when f irst running the motor .
Configuring Drive P arameter s In This Chapter .... p age — Choosing a Programming Device ................... 2 — Using Keypad Devices .................... ................ 3 — “D” Group: Monitoring Functions ..................... 6 — “F” Group: Main Profile Parameters .
Choosing a Programmin g Device Configuring Drive P arameters 3–2 Choosing a Pr ogramming Device Intr oduction Hitachi v ariable frequenc y dri ves (in verte rs) use the latest electronics technology for getting the right A C wav eform to the motor at the right time.
SJ100 Inverter Configuring Drive P arameters 3–3 Using K e ypad De vices In ver ter Front P anel Ke ypad The SJ100 Series in verter fr ont ke ypad contains all the elements for both monitoring and programming parameters. The ke ypad layout is pictured belo w .
Using Keypad Devices Configuring Drive P arameters 3–4 Ke ypad Navigational Map Y ou can use the inv erter’ s front panel keypad to na vigate to any parameter or fun ction. The diagram below sho ws the basic navigational map to access these items.
SJ100 Inverter Configuring Drive P arameters 3–5 Operational Modes The R UN and PGM LEDs tell just part of the story; Run Mode and Program Modes are independent modes, not opposite modes. In the state diagram to the right, Run alternates with Stop, and Program Mode alternates with Monitor Mode.
“D” Group: Monitoring Fun ctions Configuring Drive P arameters 3–6 “D” Gr oup: Monitoring Functions P arameter Monitoring Functions Y ou can access important system paramete r values with the “D” Group monitoring functions, whether the in verter is in R un Mode or Stop Mode.
SJ100 Inverter Configuring Drive P arameters 3–7 T rip Event and Histor y Monitoring The trip e vent and history monitoring featur e lets you cycle through related information using the ke ypad. See “ Monitoring T rip Events, History , & Conditions ” on page 6–5 for more details.
“F” Group: Main Profile Parameters Configuring Drive P arameters 3–8 “F” Gr oup: Main Profile P arameters The basic frequency (speed) pro file is defined by parameters contained in the “F” Group as sho wn to the right.
SJ100 Inverter Configuring Drive P arameters 3–9 “A” Gr oup: Standard Functions Basic P arameter Settings These settings af fect the most fundamental be ha vior of the in verter—the outputs to the motor . The frequency of the in verter’ s A C output determines the motor speed.
“A” Group: Standard Function s Configuring Drive P arameters 3–10 Analog Input Settings The in verter has the capability to accept an external analog input that can command the output frequency to the motor . V oltage i nput (0 –10V) and current input (4–20mA) are av ailable on separate terminal s ([O] and [OI], respecti vely).
SJ100 Inverter Configuring Drive P arameters 3–11 Multi-speed and Jog Frequency Setting The SJ100 in verter has the capability to store and output up to 16 preset frequencies to the motor (A_20 to A_35). As in traditional motion terminology , we call this multi-speed pr ofile capability .
“A” Group: Standard Function s Configuring Drive P arameters 3–12 “A” Function Run Mode Edit Defaults Func. Code Name / SR W Display Description –FE (CE) –FU (UL) –FR (Jpn) Units A_20 .
SJ100 Inverter Configuring Drive P arameters 3–13 T orque Contr ol Algorithms The in verter generates the motor output according to the V/f algorithm or the sensor- less vector control algorithm. P arameter A_44 selects the in verter algorithm for gener- ating the frequency output, as sho wn in the diagram to the right (A244 for 2nd motor).
“A” Group: Standard Function s Configuring Drive P arameters 3–14 parameters A_42 and A_43. The manual boost is calculated as an addition to the standard straight V/f line (constant torque curv e). NO TE: Manual torque boost is not operational when sensorless vector control is in use.
SJ100 Inverter Configuring Drive P arameters 3–15 The follo wing table sho w s the methods of torque control selection. “A” Function Run Mode Edit Defaults Func. Code Name / SR W Display Description –FE (CE) –FU (UL) –FR (Jpn) Units A_41 T orque boost method selection T wo options: 00.
“A” Group: Standard Function s Configuring Drive P arameters 3–16 DC Braking Settings The DC braking feature can provide additional stopping torque when compared to a normal deceleration to a stop. DC braking is particularly useful at lo w speeds when normal decelera- tion torque is minimal.
SJ100 Inverter Configuring Drive P arameters 3–17 Frequency-related Functions Frequency Limits – Upper and lo wer limits can be imposed on the inv erter output frequency . These limits will appl y regardless of the sou rce of the speed refer- ence.
“A” Group: Standard Function s Configuring Drive P arameters 3–18 Jump Fr equencies – Some motors or machines exhi bit resonances at particular speed(s), which can be destructi ve for prolo nged running at those speeds. The in verter has up to three jump fr equencies as sho wn in the graph.
SJ100 Inverter Configuring Drive P arameters 3–19 PID Contr ol When enabled, the built- in PID loop calculates an ideal in verter output v alue to cause a loop feedback process v a riable (PV) to mov e closer in v a lue to the setpoint (SP). The current frequency command serv es as the SP .
“A” Group: Standard Function s Configuring Drive P arameters 3–20 A utomatic V oltage Regulation (A VR) Function The automatic v oltage regulation (A VR) featur e keeps the in verter output w aveform at a relati vely constant amplitude during po wer input fluctuations.
SJ100 Inverter Configuring Drive P arameters 3–21 Second Acceleration and Deceleration Functions The SJ100 in verter features two-stage accele ration and deceleration ramps.
“A” Group: Standard Function s Configuring Drive P arameters 3–22 NO TE: F or A_95 and A_96 (and for 2nd motor settings), if you set a very rapid Acc1 or Dec1 time (less than 1.0 second), the in verter ma y not be able to change rates to Acc2 or Dec2 before reaching the ta rget fr equenc y .
SJ100 Inverter Configuring Drive P arameters 3–23 Accel/Decel Standard acceleration and deceleration is linear . The in verter CPU can also calculate an S-curve acceleration or deceleration curve as sho wn. This profile is useful for fa voring the load characteristics in particu- lar applications.
“B” Group: Fine Tuning Fun ctions Configuring Drive P arameters 3–24 “B” Gr oup: Fine T uning Functions The “B” Group of functions and parameters adju st some of the more subtle b ut useful aspects of motor control and system conf iguration.
SJ100 Inverter Configuring Drive P arameters 3–25 Electr onic Thermal Overload Alarm Setting The thermal ov erload detection protects the in verter and motor from ov erheating due to an excessi ve load. It uses a current/in verse time curve to determine the trip point.
“B” Group: Fine Tuning Fun ctions Configuring Drive P arameters 3–26 W ARNING: When parameter B_12, level of electroni c thermal setting, is set to de vice FLA rating (Full Load Ampere nameplate rating), the device pro vides solid state motor ov erload protection at 115% of de vice FL A or equi v alent.
SJ100 Inverter Configuring Drive P arameters 3–27 Overload Restriction If the in verter’ s output current e xceeds a preset current le vel you specify during acceleration or constant speed, the ov e rload restriction feature automatically reduces the output frequenc y to restrict the ov erload.
“B” Group: Fine Tuning Fun ctions Configuring Drive P arameters 3–28 Software Loc k Mode The software lock function keeps personnel fr om accidentally cha nging parameters in the in verter memory . Use B_31 to select from various protection le vels.
SJ100 Inverter Configuring Drive P arameters 3–29 NO TE: T o disable parameter editing when using B_31 lock mo des 00 and 01, assign the [SFT] function to one of the intelligent input terminals. See “ Software Lock ” on page 4–19 . “B” Function Run Mode Edit Defaults Func.
“B” Group: Fine Tuning Fun ctions Configuring Drive P arameters 3–30 Miscellaneous Settings The miscellaneous settings include scaling factors, initialization modes, and others. this section cov e rs some of the most importa nt setting s you may need to conf igure.
SJ100 Inverter Configuring Drive P arameters 3–31 “B” Function Run Mode Edit Defaults Func. Code Name / SR W Display Description –FE (CE) –FU (UL) –FR (Jpn) Units B_81 [FM] terminal analog.
“B” Group: Fine Tuning Fun ctions Configuring Drive P arameters 3–32 B_91/B_88: Stop Mode / Restart Mode Conf iguration – Y ou can configure ho w the in verter performs a standard stop (each time Run FWD and REV signals turn OFF).
SJ100 Inverter Configuring Drive P arameters 3–33 B_90: Dynamic braking usage ratio – This parameter limits th e amount of time the in verter can use the dynamic braking accessory de vice without entering the T rip Mode. Please refer to “ Dynamic Braking ” on page 5–5 for more information on dynamic braking accessories.
“C” Group: Intelligent Terminal Functions Configuring Drive P arameters 3–34 “C” Gr oup: Intellig ent T erminal Functions The six input terminals [ 1] , [ 2] , [ 3] , [ 4] , [ 5] , and [ 6] can be configured for an y of 19 dif ferent functions.
SJ100 Inverter Configuring Drive P arameters 3–35 The input logic con vention is programmable for each of the six inputs. Most inputs default to normally open (acti ve high), b ut you ca n select normally closed (acti ve lo w) in order to in vert the sense of the logic.
“C” Group: Intelligent Terminal Functions Configuring Drive P arameters 3–36 Input Function Summary T able – This table show s all nineteen intelligent input functions at a glance.
SJ100 Inverter Configuring Drive P arameters 3–37 Note 1: When using the Multi-speed Select settings CF1 to CF4, do not display parameter F_01 or change the v alue of F _01 while the in verter is in Run Mode (motor running). If it is necessary to check the v alue of F_01 during Run Mode, please monitor D_01 instead of F_01.
“C” Group: Intelligent Terminal Functions Configuring Drive P arameters 3–38 Output T erminal Configuration The in verter provides conf iguration for logi c (discrete) and analog outputs, shown in the table belo w . The output logic con vention is programmabl e for terminals [11], [12], and the alarm relay terminals.
SJ100 Inverter Configuring Drive P arameters 3–39 Output Function Summary T able – This table sho ws all six functions for the logical outputs (terminals [11], [12]) at a glance.
“C” Group: Intelligent Terminal Functions Configuring Drive P arameters 3–40 Analog Function Summary T able – This table shows all three functions for the analog output [FM] (frequency meter) terminal.
SJ100 Inverter Configuring Drive P arameters 3–41 Output Function Adjustment P arameters The follow ing parameters work in conjunction with the intelligent output function, when configured. The o verload le vel parameter (C_41) sets the motor current le vel at which the o verload signal [OD] turns ON.
“C” Group: Intelligent Terminal Functions Configuring Drive P arameters 3–42 NO TE: Settings C_81 and C_82 are fact ory-calibrated for each in verter . Do not change these settings unless absolutely necessary . Note that if you restore factory def a ults for all parameters, these settings will not change.
SJ100 Inverter Configuring Drive P arameters 3–43 “H” Gr oup: Motor Constants Functions Intr oduction The “H” Group parameters configure the in verter for the motor characteristics. You must manually set H_03 and H_04 values to match the motor.
“H” Group: Motor Co nstants Functions Configuring Drive P arameters 3–44 H204 Motor poles setting, 2n d motor Four selections: 2 / 4 / 6 / 8 ✘ 4 4 4 poles 2AUXP 4p H_05 Motor speed constant Mo.
SJ100 Inverter Configuring Drive P arameters 3–45 H_24 Motor Constant J Ratio (unit-less), range is 1.0 to 1000 ✘ Factory set according to in verter model — AUX J 0020.0 H224 Motor constant J, 2nd motor Ratio (unit-less), range is 1.0 to 1000 ✘ Factory set according to in verter model — 2AUXJ 0020.
Operations and Monitoring In This Chapter .... p age — Introduction ................. .................... ................ 2 — Connecting to PLCs and Other Devices ......... 4 — Using Intelligent Input T erminals ..................... 8 — Using Intelligent Output T erminals .
Introduction Operations and Monitoring 4–2 Intr oduction The pre vious material in Chapter 3 ga ve a reference listing of all the programmable functions of the in verter . W e suggest that you first scan through the listing of in ve rter functions to gain a general familiarity .
SJ100 Inverter Operations and Monitoring 4–3 W arning Messages for Operating Pr ocedures Before continuing, please read the follo wing W arning messages. W ARNING: Be sure to turn ON the input po wer supply only after closing the front case. While the in verter is energized, be sure not to open the front case.
Connecting to PLCs and Other Devices Operations and Monitoring 4–4 Connecting to PLCs and Other De vices Hitachi in verters (dri ves) are useful in many types of applications . During installation, the in verter ke ypad (or other programming de vice) will facilitate the initial configura- tion.
SJ100 Inverter Operations and Monitoring 4–5 Example Wiring Diagram The schematic diagram below pro vides a gene ral example of logic connector wirin g, in addition to basic po wer and motor wiring co ve red in Chapter 2.
Example Wiring Di agram Operations and Monitoring 4–6 Specifications of Contr ol and Logic Connections The control logic connectors are located just behind the front panel half-door . The relay contacts are accessible behind the main door . Connector labeling is shown belo w .
SJ100 Inverter Operations and Monitoring 4–7 T erminal Listing Use the follo wing tables to locate pages for intelligent input and output material in this chapter .
Using Intelligent Input Terminals Operations and Monitoring 4–8 Using Intelligent Input T erminals T erminals [1], [2], [3], [4], [5], and [6 ] are identical, programmable inputs for general use. The input circuits can use the in verter’ s internal (isolated) +24V f ield supply (P24) to po wer the inputs.
SJ100 Inverter Operations and Monitoring 4–9 Forwar d Run/Stop and Re verse Run/Stop Commands: When you input the Run command via the terminal [FW], the in verter ex ecutes the Forw ard Run command (high) or Stop command (lo w).
Using Intelligent Input Terminals Operations and Monitoring 4–10 Multi-Speed Select The in verter can store up to 16 dif ferent target frequencies (speeds) that the motor output uses for steady-state run condition.
SJ100 Inverter Operations and Monitoring 4–11 While using the multi-speed capability, you ca n monitor the current frequency with monitor function D_01 during each se gment of a multi-speed operation.
Using Intelligent Input Terminals Operations and Monitoring 4–12 Jogging Command The Jog input [JG] is used to command the motor to rotate slowly in small i ncrements for manual operation. The speed is limited to 10 Hz. The frequency for the jogging opera- tion is set by parameter A_38.
SJ100 Inverter Operations and Monitoring 4–13 External Signal f or DC Braking When the terminal [DB] is turned ON, the DC braking feature is enabled. Set the follow- ing parameters when the external DC braking terminal [DB] is to be used: • A_53 – DC braking delay time setting.
Using Intelligent Input Terminals Operations and Monitoring 4–14 Set Second Motor If you assign the [SET] function to an intel ligent input terminal, you can select between two sets of motor parameters. The second pa rameters store an alternate set of motor characteristics.
SJ100 Inverter Operations and Monitoring 4–15 T wo-stage Acceleration and Deceleration When terminal [2CH] is turned ON, the in verter changes the rate of acceleration and deceleration from the initial settings (F_02 and F_03) to use the second set of accelera- tion/deceleration v alues.
Using Intelligent Input Terminals Operations and Monitoring 4–16 Free-run Stop When the terminal [FRS] is turned ON, the in verter stops the output and the motor enters the free-run state (coasting). If terminal [F RS] is turned OFF , the output resumes sending power to the motor if the Run command is still acti ve.
SJ100 Inverter Operations and Monitoring 4–17 External T rip When the terminal [EXT] is turned ON, the in verter enters the trip state, indicates error code E12, and stops the output. This is a gene ral purpose interrupt type feature, and the meaning of the error depends on what you c onnect to the [EXT] terminal.
Using Intelligent Input Terminals Operations and Monitoring 4–18 Unattended Start Protection If the Run command is already set when power is turned ON, the in verter starts running immediately after po werup.
SJ100 Inverter Operations and Monitoring 4–19 Software Loc k When the terminal [SFT] is turned ON, the data of all the parameters and functions (except the output frequenc y , depending on the setting of B_31) is locked (prohibited from editing). When the data is locked, the ke ypad ke ys cannot edit in verter parameters.
Using Intelligent Input Terminals Operations and Monitoring 4–20 Analog Input Current/V oltage Select The [AT] terminal selects whether the inverter uses the voltage [O] o r current [OI] input terminals for external frequency control.
SJ100 Inverter Operations and Monitoring 4–21 Reset In ver ter The [RS] terminal causes the inverter to execute the reset operation. If the inverter is in Trip Mode, the reset cancels the Trip state. When the signal [RS] is turned ON and OFF, the inverter executes the reset operation.
Using Intelligent Input Terminals Operations and Monitoring 4–22 Thermistor Thermal Pr otection Motors that are equipped with a thermisto r can be protected from o verheating. Input terminal [5] has the unique ability to sense a thermistor resistance.
SJ100 Inverter Operations and Monitoring 4–23 Remote Contr ol Up and Down Functions The [UP] [D WN] terminal functions can adju st the output frequenc y for remote control while the motor is running. The acceleration ti me and deceleration time of this function is same as normal operation A CC1 and DE C1 (2A CC1,2DEC1).
Using Intelligent Output Terminals Operations and Monitoring 4–24 Using Intelligent Output T erminals The intelligent output terminals are programmable in a similar way to the intelligent input terminals. The in verter has se veral output functions that you can assign individu- ally to three physical logic outputs.
SJ100 Inverter Operations and Monitoring 4–25 Run Signal When the [R UN] signal is selected as an intelligent output terminal, the in verter outputs a signal on that terminal when it is in Run Mode. The output logic is acti ve low , and is the open collector type (switch to ground).
Using Intelligent Output Terminals Operations and Monitoring 4–26 Frequency Arriv al Signals The F requ ency Arrival group of outputs help coordinate external systems with the current velocity prof ile of the in verter . As the name implies, output [F A1] turns ON when the output fr equency arrives at the standard set frequency (parameter F_01 ).
SJ100 Inverter Operations and Monitoring 4–27 Frequency arri val output [F A1] uses the standard output frequency (parameter F_01) as the threshold for switching. In the figure to the right, Frequenc y Arriv al [F A1] turns ON when the outpu t frequency gets within 0.
Using Intelligent Output Terminals Operations and Monitoring 4–28 Overload Adv ance Notice Signal When the output current e xceeds a preset value, the [OL] terminal signal turns ON. The parameter C_41 sets the ov erload threshold. The ov e rload detection circuit operates during po wered motor opera- tion and during regenerati ve braking.
SJ100 Inverter Operations and Monitoring 4–29 Output Deviation f or PID Control The PID loop error is defined as the magnitude (absolute v alue) of the dif fer- ence between the Set point (target v alue) and the Process V a riable (actual v alue). When the error magnitude exceeds the preset v alue for C_44, the [OD] terminal signal turns ON.
Using Intelligent Output Terminals Operations and Monitoring 4–30 Alarm Signal The in verter alarm signal is acti ve when a f a ult has occurred and it is in the T rip Mode (refer to the diagram at right). When the fault is cleared the alarm signal becomes ina cti ve.
SJ100 Inverter Operations and Monitoring 4–31 The alarm output terminals are connected as sho wn below (left) by defa ult. The contact logic can be in verted as sho wn (belo w ri ght) by using the parameter setting C_33. The relay contacts normally open (N.
Analog Input Oper ation Operations and Monitoring 4–32 Analog Input Operation The SJ100 in verters provide for analog input to command the in verter frequency output va lue. The analog input terminal group includes the [L], [OI], [O], and [H] terminals on the control connector , which provide for V oltage [O] or Current [OI] input.
SJ100 Inverter Operations and Monitoring 4–33 Analog and Digital Monitor Output In the system design for in verter applications it is useful to monitor the in verter operation from a remote location. In some cases, this requires only a panel-mounted analog meter (moving-coil type).
Analog and Digita l Monitor Output Operations and Monitoring 4–34 TIP: When using the analog meter for monitoring, adjust the meter so it has a zero reading when the [FM] output is zero. Then use scale factor B_81 to adjust the [FM] output so the maximum frequency in the in ve rter corresponds to a full-scale reading on the meter .
SJ100 Inverter Operations and Monitoring 4–35 A uto-tuning f or Sensorless V e ctor Contr ol The SJ100 in verter has a b uilt-in auto-tuning algorithm.
Auto-tuning for Sen sorless Vector Con trol Operations and Monitoring 4–36 NO TE: During step 11, the motor will make a slight humming sound during the A C and DC excitation (A and B) steps of the auto-tuning process. Th is sound is normal. NO TE: When the SL V control method is selected with A_44, set the carrier frequency to 2.
SJ100 Inverter Operations and Monitoring 4–37 If the in verter dri ves a motor/load with a small inertia, the motor may e xhibit “hunting” during running. If this occurs, ta ke the follo wing correctiv e steps: 1. Adjust the stabilization constant H_06/H206.
Auto-tuning for Sen sorless Vector Con trol Operations and Monitoring 4–38 Note 6: Do not interrupt the auto-tuning proce dure by remov ing power or by using the Stop command, unless it is an emer gency .
SJ100 Inverter Operations and Monitoring 4–39 PID Loop Operation In standard operation, the in verter uses a reference source sele cted by parameter A_01 for the output frequency , which may be a fix ed value (F_01), a v ariable set by the front panel potentiometer , or value from an analog i nput (v oltage or current).
Configuring the Inver ter for Multiple Motors Operations and Monitoring 4–40 Configuring the In ver ter f or Multiple Motors Simultaneous Connections For some app lications, you may need to connect two or more motors (wired in parallel) to a single in verter’ s output.
SJ100 Inverter Operations and Monitoring 4–41 Having tw o motor profiles lets you store two “per sonalities” for motors in one in verter’ s memory . The in verter allo ws the final selec tion between the two motor ty pes to be made in the f ield through the use of an intelligent input terminal function [SET].
In ver ter System Accessories In This Chapter .... p age — Introduction ................. .................... ................ 2 — Component Descriptions .................... ............. 3 — Dynamic Braking ...................................
Introduction Motor Control Accessories 5–2 Intr oduction A motor control system will obviously include a motor and in verter , as well as fuses for safety . If you are connecting a motor to the in verter on a test bench just to get started, that’ s all you may need for no w .
SJ100 Inverter Motor Control Accessories 5–3 Component Descriptions A C Reactors, Input Side This is useful in suppressing harmonics i nduced on the po wer supply lines, or when the main po wer voltage imbalance exceed s 3% (and po wer source capacity is more than 500 kV A), or to smooth out line fluctuations.
Component D escriptions Motor Control Accessories 5–4 Zer o-phase Reactor (RF Noise Filter) The zero-phase reactor helps reduce radiated noise from the in verter wiring. It can be used on the input or output side of the in verter . The example zero-phase reactor sho wn to the right comes with a mounting bracket.
SJ100 Inverter Motor Control Accessories 5–5 Dynamic Braking Intr oduction The purpose of dynamic braking is to improv e the ability of the in verter to stop (decelerate) the motor and load.
Dynamic Braking Motor Control Accessories 5–6 Dynamic Braking Usage Ratio The in verter controls braking via a duty cycle method (percent of the time braking is ON versus total time). Parameter B_90 sets the dynamic braking usage ratio. In the graph to the right, the example sho ws three uses of dynamic braking in a 100-second period.
SJ100 Inverter Motor Control Accessories 5–7 SJ100 Dynamic Braking Selection T ables The SJ100 series in verter models hav e inte rnal braking units. Additional stopping torque is a vailable by adding extern al resistors. The required braking torq ue depends on your particular application.
Dynamic Braking Motor Control Accessories 5–8 Selecting Braking Resistors f or Internal Braking Units Y ou can add one or more resi stors to your in verter conf i guration to increase braking torque performance. The tables belo w lists th e resistor types for in verter models with internal braking units.
SJ100 Inverter Motor Control Accessories 5–9 The table below lists 400V -class in verter models with built-in braking units. Depending on the desired braking torque or on the in verter model, the resistor selection sp ecifies multiple resistors in a parallel or series combination.
Dynamic Braking Motor Control Accessories 5–10 Use one BRD–E2 braking unit for the braki ng torque listed in th e follo wing table. Note the column meanings in the tables: • Column “ A ” = A verage braking torque from 60 Hz to 3 Hz. • Column “B” = A verage braking torque from 120 Hz to 3 Hz.
SJ100 Inverter Motor Control Accessories 5–11 400V Class In verters – The follo wing tables specify the braking options for 400V class SJ100 in verters and the braking torque for each option. Y ou can c onnect a single braking unit to the in verter , or two braking units for additional braking torque.
T r oub leshooting and Maintenance In This Chapter .... p age — T roubleshooting .......................... ..................... 2 — Monitoring T rip Events , History , & Conditions . 5 — Restoring Factory Default Settings .................
Troubleshooting T roub leshooting and Maintenance 6–2 T r oubleshooting Safety Messages Please read the followin g safety messages before troubleshooting or performing mainte- nance on the in verter and motor system.
SJ100 Inverter T roub leshooting and Maintenance 6–3 T roub leshooting Tips The table below lists typical symptoms and the corresponding solution(s). Symptom/condition Probable Cause Solution The motor will not run. The in verter outputs [U], [V], [W] are not supplying voltage.
Troubleshooting T roub leshooting and Maintenance 6–4 The motor speed will not reach the target frequenc y (desired speed). • If using the analog input, is the current or voltage at [O] or [OI]? • Check the wiring. • Check the potentiometer or signal generating de vice.
SJ100 Inverter T roub leshooting and Maintenance 6–5 Monitoring T rip Events, History , & Conditions Fa ult Detection and Clearing The microprocessor in the in verter detects a v ariety of fault conditions and captures the e vent, record- ing it in a history table.
Monitoring Trip Events , History, & C onditions T roub leshooting and Maintenance 6–6 NO TE: If an EEPR OM error (E08) occurs, be sure to conf irm the parameter data v a lues are still correct. If the po wer is turned OFF while the [RS] (Reset) intelligent input terminal is ON, an EEPR OM error will occur when po wer is restored.
SJ100 Inverter T roub leshooting and Maintenance 6–7 T rip Histor y and In ver ter Status W e recommend that you first f ind the cause of the fault before clearing it. When a fault occurs, the in verter stores important performa nce data at the moment of the fault.
Restoring Factory Default Settings T roub leshooting and Maintenance 6–8 Restoring F actor y Default Settings Y ou can restore all inv erter parameters to th e original factory (default) settings for the intended country of use. After initializing the in verter , use the po werup test in Chapter 2 to get the motor running again.
SJ100 Inverter T roub leshooting and Maintenance 6–9 Maintenance and Inspection Monthly and Y early Inspection Char t Note 1: The life of a capacitor is affected by the ambient te mperature. See “ Ca pacitor Life Curve ” on p age 6–11 . Note 2: The in verter must be cleaned periodica lly .
Maintenan ce and Inspecti on T roub leshooting and Maintenance 6–10 Megger T est The me gger is a piece of test equipment that us es a high v oltage to determine if an insulation degradation has occurred. F or in vert ers, it is important that the po wer termi- nals be isolated from the Earth GND terminal via the proper amount of insulation.
SJ100 Inverter T roub leshooting and Maintenance 6–11 Spare par ts W e recommend that you stock spare parts to reduce do wn time, including these parts: Capacitor Life Curve The DC b us inside the in verter uses a large capacitor as sho wn in the diagram below .
Maintenan ce and Inspecti on T roub leshooting and Maintenance 6–12 General In ver ter Electrical Measurements The follow ing table specifies ho w t o measur e ke y system electrical parameters. The diagrams on the ne xt page sho w in verter-mot or systems and the location of measurement points for these parameters.
SJ100 Inverter T roub leshooting and Maintenance 6–13 The figu res belo w show measurement locations for v oltage, c urrent, and po wer measure- ments listed in the table on the pre vious page. The v oltage to be measured is the funda- mental wa ve ef fecti ve v oltage.
Maintenan ce and Inspecti on T roub leshooting and Maintenance 6–14 In ver ter Output V oltage Measurement T echniques T aking voltage measurements around dri ves equipment requires the right equipment and a safe approach. Y ou are working with high voltages and high-frequenc y switching wa veforms that are not pure sinusoids.
SJ100 Inverter T roub leshooting and Maintenance 6–15 IGBT T est Method The follo wing procedure will check the in verter transistors (IGBTs) and diodes: 1. Disconnect input po wer to terminals [R, S, and T] and motor terminals [U, V , and W]. 2. Disconnect any wires from terminals [+ ] and [RB] for re generati ve brakin g.
Warranty T roub leshooting and Maintenance 6–16 W arranty W arranty T erms The warranty period under normal inst allation and handling conditions shall be two (2) years from the da te of manuf acture (“DA TE” on product nameplate), or one (1) year from the date of installation, whichev er occurs first.
Glossar y and Bib liograph y In This Appendix.... p age — Glossary ...................... .................... ................ 2 — Bibliography ..
Glossary Appendix A A–2 Glossary Ambient T emperatur e The air temperature in the cham ber containing a po wered electronic unit. A unit’ s heat sinks rely on a lo wer ambient temperature in order to dissipate heat aw ay from sensiti ve electronics.
SJ100 Inverter Appendix A A–3 DC Braking The in verter DC braking feature stops the A C commutation to the motor , and sends a DC current through the motor windings in order to stop the motor . Also called “DC injection braking, ” it has li ttle ef fect at high speed, and is used as the motor is nearing a stop.
Glossary Appendix A A–4 Fr equency Setting While frequenc y has a broad meani ng in electronics, it typically refers to moto r speed for variable-frequency driv es (in verters). This is because the output frequency of the in verter is v ariable, and is proportional to the attained motor speed.
SJ100 Inverter Appendix A A–5 Jump Fr equency A jump frequency is a point on the in verter output frequency range that you want the in verter to skip around. This feature may be used to av oid a resonant frequency , and you can program up to three jump frequencies in the in verter .
Glossary Appendix A A–6 PWM Pulse-width modulation: A type of A C adjustable frequency dri ve that accomplishes frequenc y and voltage control at the output section (in verter) of the dri ve.
SJ100 Inverter Appendix A A–7 Single-phase power An A C power source consisting of Hot and Neutral wires. An Earth Ground connection usually accompanies them. In theory , the voltage potential on Neutral stays at or near Earth Ground, while Hot v aries sinusoidally abov e and below Neutral.
Bibliography Appendix A A–8 T or que The rotational force e xerted by a mo tor sh aft. The units of measure- ment consist of the distance (r adius from shaft center axis) and force (weight) applied at that di stance. Units are usually gi ven as pound-feet, ounce-inches, or Ne wton-meters.
Drive P arameter Settings T ab les In This Appendix.... p age — Introduction ................. .................... ................ 2 — Parameter Settings for Keyp ad Entry .
Introduction Appendix B B–2 Intr oduction This appendix lists the user-programmable parameters for the SJ100 series in verters and the default v alues for European and U.S. product types. The right-most column of the tables is blank, so you can record v alues you have changed from the default.
SJ100 Inverter Appendix B B–3 Standar d Functions “A” Gr oup Parameters Default Setting User Setting Func. Code Name -FE (Europe) -FU (USA) –FR (Japan) A_01 Frequency source setting 01 01 00 A_02 Run command source setting 01 01 02 A_03 Base frequenc y setting 50.
Parameter Settings for Keypad Entry Appendix B B–4 A_32 Multi-speed 12 setting 0 0 0 A_33 Multi-speed 13 setting 0 0 0 A_34 Multi-speed 14 setting 0 0 0 A_35 Multi-speed 15 setting 0 0 0 A_38 Jog frequency setting 1.
SJ100 Inverter Appendix B B–5 A_72 PID proportional gain 1.0 1.0 1.0 A_73 PID integral time constant 1.0 1.0 1.0 A_74 PID deri vati ve gain 0.0 0.0 0.0 A_75 PV scale con version 1.00 1.00 1.00 A_76 PV source setting 00 00 00 A_81 A VR function select 02 00 02 A_82 A VR voltage select 230/400 230/460 200/400 A_92 Acceleration (2) time setting 15.
Parameter Settings for Keypad Entry Appendix B B–6 Fine T uning Functions “B” Gr oup Parameters Default Setting User Setting Func. Code Name -FE (Europe) -FU (USA) –FR (Japan) B_01 Selection of automatic restart mode 00 00 00 B_02 Allowable under -voltage po wer failure time 1.
SJ100 Inverter Appendix B B–7 B_89 Data select for digital op. OPE-J 01 01 01 B_90 Dynamic braking usage ratio 0.0 0.0 0.0 B_91 Stop mode selection 00 00 00 B_92 Cooling fan control 00 00 00 “B” Group P arameters Default Setting User Setting Func.
Parameter Settings for Keypad Entry Appendix B B–8 Intelligent T erminal Functions “C” Group P arameters Default Setting User Setting Func. Code Name -FE (Europe) -FU (USA) –FR (Japan) C_01 T .
SJ100 Inverter Appendix B B–9 Motor Constants Functions C_91 Debug mode enable 00 00 00 Do not edit C_92 Core monitor address 0000 0000 0000 Do not edit C_93 Core monitor date — — — Do not edi.
Parameter Settings for Keypad Entry Appendix B B–10 H_22 Motor constant L Factory set Factory set Factory set H222 Motor constant L, 2nd motor F actory set Factory set Factory set H_23 Motor constan.
CE–EMC Installation Guidelines In This Appendix.... p age — CE–EMC Installation Guidelines ..................... 2 — Hitachi EMC Recommendations .
CE–EMC Installation Guidelines Appendix C C–2 CE–EMC Installation Guidelines Y ou are required to satisfy the EMC dire ctiv e (89/336/EEC) when using an SJ100 in verter in an EU country . T o satisfy the EMC directive an d to comply with standard, follow the guidelines in this section.
SJ100 Inverter Appendix C C–3 4. T ake measures to minimize interference that is frequently coupled in through installa- tion cables. • Separate interfering cables with 0.25m minimum from cables susceptible to inter- ference. A particularly critical point is laying parallel cables ov er longer distances.
CE–EMC Installation Guidelines Appendix C C–4 L1 L2 L3 PE M 3~ SJ100 in ver ter with footprint-type filter.
SJ100 Inverter Appendix C C–5 L1 L2 L3 PE SJ100 in ver ter with book-type filter M 3~.
Hitachi EMC Recommendations Appendix C C–6 Hitachi EMC Recommendations W ARNING: This equipment should be installed, adjusted, and serviced by qualified personal familiar with construction and ope ration of the equipment and the hazards in volv ed. Failure to observ e this precaution could result in bodily injury .
Inde x A A Group functions 3–9 AC reactors 5–3 Acceleration 1–22 , 3–8 characteristic curves 3–23 second function 3–21 two-stage 4–15 Access levels 3–5 , 3–28 , 4–19 Access to term.
Index –2 D D Group parameters 3–6 DC braking 3–16 , 4–12 , 4–13 , A–3 DC link choke 5–4 Deadband A–3 Deceleration 1–22 , 3–8 , 4–12 characteristic curves 3–23 second function 3.
SJ100 Inverter Index –3 I IGBT 1–18 , A–4 test method 6–15 Index of terminal functions 4–7 Inertia A–4 Initialization 6–8 Initialization codes 3–30 Input circuits 4–8 Input terminals.
Index –4 O Open-collector outputs 4–24 , A–5 Operational modes 3–5 Operator interfaces 1–3 Optional components 2–5 Options 1–2 Output adjustment parameters 3–41 Output circuits 4–24 .
SJ100 Inverter Index –5 Specifica tions derating curves 1–12 general 1–9 inverter 1–5 label 1–4 , 2–3 logic signals 4–6 Speed control 1–18 , 1–22 , 4–10 Speed pot 2–25 Squirrel c.
Een belangrijk punt na aankoop van elk apparaat Hitachi SJ100 (of zelfs voordat je het koopt) is om de handleiding te lezen. Dit moeten wij doen vanwege een paar simpele redenen:
Als u nog geen Hitachi SJ100 heb gekocht dan nu is een goed moment om kennis te maken met de basisgegevens van het product. Eerst kijk dan naar de eerste pagina\'s van de handleiding, die je hierboven vindt. Je moet daar de belangrijkste technische gegevens Hitachi SJ100 vinden. Op dit manier kan je controleren of het apparaat aan jouw behoeften voldoet. Op de volgende pagina's van de handleiding Hitachi SJ100 leer je over alle kenmerken van het product en krijg je informatie over de werking. De informatie die je over Hitachi SJ100 krijgt, zal je zeker helpen om een besluit over de aankoop te nemen.
In een situatie waarin je al een beziter van Hitachi SJ100 bent, maar toch heb je de instructies niet gelezen, moet je het doen voor de hierboven beschreven redenen. Je zult dan weten of je goed de alle beschikbare functies heb gebruikt, en of je fouten heb gemaakt die het leven van de Hitachi SJ100 kunnen verkorten.
Maar de belangrijkste taak van de handleiding is om de gebruiker bij het oplossen van problemen te helpen met Hitachi SJ100 . Bijna altijd, zal je daar het vinden Troubleshooting met de meest voorkomende storingen en defecten #MANUAl# samen met de instructies over hun opplosinge. Zelfs als je zelf niet kan om het probleem op te lossen, zal de instructie je de weg wijzen naar verdere andere procedure, bijv. door contact met de klantenservice of het dichtstbijzijnde servicecentrum.