1 Caution: Be sur e to r ead the SJ200 2 In verter Manual and follow its Cautions and W arnings for the initial product installation. This Quick Refer ence Guide is intended for refer ence use by experienced users in servic ing existing installations.
2 T erminal Tightening T orque and Wire Size The wire size range and tightening torq ue for field wiring terminals are presented i n the tables below . 200V Models Motor output In verter Model Wire S ize (A WG) T orque kW HP ft-lbs (N-m) 0.2 1/4 –002NFE(F)2/NFU2 16 0.
3 Wire Connec tors Wa r n i n g : Field wirin g connections must be made by a UL Listed and CSA Certified ring lug terminal connector sized for the wir e gauge being used. The connector must be fixed using the crimping tool specified by the con- nector manufactur er .
4 Motor Overload Protection Hitachi SJ200 2 inv erters provide solid state motor overload protection, which depends on the proper sett ing of the following para meters: • B012 “electronic ov erloa.
5 P o wer Circuit T erminals RB In verter models SJ200 –002NFE(F)2/NFU2 to –005NFE(F)2/ NFU2 Jum per RB +1 + – U/T1 V/T2 W/T3 Chassis Ground In verter models SJ200 –007NFE(F)2 to –022NFE(F)2.
6 Contr ol Cir cuit T erminals Te r m i n a l Name Description Ratings and Notes PCS +24V for logic inputs 24VDC supply , 30 mA max. (Notes: Do not use for netw ork power Do not short to terminal L) 1, 2, 3, 4, 5, 6 Intelligent (program- mable) discrete logic inputs 27VDC max.
7 11, 12 Discrete logic outp uts 5 0 mA max. ON current, 27 VDC max. OFF voltage CM2 GND for logic outputs 100 mA max for sum of terminals 11 and 12 currents AM Analog v oltage output 0 to 10VDC, 1 mA max., 50% duty cycle L (bottom row) GND for analog signals Sum of OI, O, H, and AM currents (return) OI Analog input, current 4 to 19.
8 Basic Wiring Dia gram The following wiring diag ram show s the power and motor connections for basic operation. The op tional signal input wiring supports e xternal Fwd and Rev Run command, an d a speed potentiome ter .
9 In verter Ke ypad Operation • Run/Stop LED – ON when the inv erter output is ON and the motor is de veloping torque , and OFF when the in verter ou tput is OFF (Stop Mode). • Program/Monitor LED – ON when the inv erter is ready for parame- ter editing (Program Mode).
10 • Para meter Disp lay – A 4-digit, 7-segment display for parameter s and function codes. • Display Units: Hertz/Amperes – One of these LEDs will be O N to indicate the units associated with the parameter display . • Po wer LED – ON when the power input to the inv erter is ON.
11 Ke ypad Na vigation Map H007 H003 1 2 C1 4 9 C 001 1 2 b 15 1 b 001 1 2 A1 5 5 A001 1 2 1 2 1 2 1 2 H- - - 1 2 C- - - 1 2 b --- 1 2 A- - - F0 0 4 F0 0 1 1 2 d 083 d 001 1 2 0.
12 P o werup T est The Powerup T est procedure uses mi nimal parameter settings to run the motor . The procedur e describes two alternati ve methods for command ing the in verter: via the in verter ke ypad , or via the logic terminals . • Check power input and m otor output wiring (see page 8 diagram) .
13 Error Codes The SJ200 2 series in v erters will trip on over-current, ov er-v oltage, and under-v oltage to protect the in v erter . The motor output turns OFF , allow- ing the motor to free-run to a stop. Pr ess the Stop/Reset key to reset the in verter and clear the error .
14 Erro r T rip Conditions Use function code D081 to access the er ror trip conditions for the current error as shown in the table below . Use the Up and Do wn arrow ke ys to scroll through the trip c ondition parameters. E35 Thermistor • Thermistor input, [THM] and [L], is over the temp.
15 Restoring Factory Default Settings Note: After initializing the inverter , use the P owerup T est on page 12 to get the motor running aga in. Action Displ ay Function/Par ameter Press , or as needed. b --- “B” Group selected Press . b 001 First “B” Group parameter Press/hold until.
16 Pa ra m e t er T a bl e s “D” Gr oup: Monitorin g Functions Func. Code Name / Description Units D001 Output frequenc y monitor Hz D002 Output current monitor A D003 Rotation direction monitor .
17 T rip Histor y and In verter Status Func. Code Name / Description Units D080 T rip Counter Hz D081 T rip monitor 1 (most recent trip n) — D082 Trip monitor 2 (trip n-1) — D083 Trip monitor 3 (trip n-2) — E0 7 60 . 0 1 2 4.0 39 8 . 0 1 2 1 2 d 083 1 2 0.
18 Parameter tables for user-settable functions follo w these conv entions: • Some parameters have 2nd motor e qui valents, indicated by the x2xx parameter codes in the left-most column. • Some parameters specify an op tion code. Where appli cable, the options codes will be in a bulleted list in the Name/Description column.
19 A003/ A203 Base frequency setting 50.0 / 60.0 A004/ A204 Maximum frequency setting 50.0 / 60.0 A005 [A T] sele ction • 00 Select between [O] and [OI] at [A T] • 01 [O]+[OI] ([A T] input is ignored) • 02 Select between [O] and keypad pot • 03 Select between [OI] and keypad pot 00 A011 Pot.
20 A045/ A245 V/f gain setting 100. A046/ A246 Automatic tor que boost voltage gain 100 A047/ A247 Automatic torque boost slip gain 100 A051 DC braking enabl e • 00 Disable • 01 Enable 00 A052 DC braking frequency setting 0.5 A053 DC braking wait time 0.
21 A081 A VR function sel ect • 00 A VR enab led • 01 A VR di sabled • 02 A VR enab led except during decel 00 A082 A VR voltage select 230 / 230 400 / 460 A092/ A292 Acceleration (2) time setting 15.0 A093/ A293 Deceleration (2) time setting 15.
22 “B” Gr oup: Fine-tuni ng Functions A146 ADD direction select • 00 Plus (adds A145 value to output frequency) • 01 M inus (subtracts A145 v alue from output frequency) 00 A151 Pot. input act i ve range start frequency 0.0 A152 Pot. input act i ve range end frequency 0.
23 B021/ B221 Overload restri ction operation mode •0 0 D i s a b l e d • 01 Enabled for accel and const ant speed • 02 Enabled for constant speed onl y 01 B022/ B222 Overload re striction se tting Rated current x 1.5 B023/ B223 Deceleration rate at overload restriction 1.
24 “C” Gr oup: Intelligent T erminal Function s B095 Dynamic braking control • 00 Disable • 01 Enable during R UN only • 02 Enable always 00 B096 Dynamic braking activ ation level 360 / 720 .
25 C011 T erminal [1] acti ve state • 00 Normally open [NO] •0 1 N o r m a l l y closed [NC] 00 C012 T erminal [2] acti ve st ate 00 C013 T erminal [3] acti ve st ate 00 C014 T erminal [4] acti ve.
26 C076 Communication error select • 00 T rip (error code E60) • 01 Decelerate to stop and trip (error code E60) • 02 Disable • 03 Free run stop (coasting) • 04 Decelerate to a stop 02 C077 Communication error time-out 0.00 C078 Communication wait time 0.
27 “H” Gr oup: Motor Constants Functi ons “P” Grou p: Expansion Card Fu nctions Note: The “P” Gr oup par ameters do not appea r in the parameter list show n on the ke ypad displa y unless the e xpansion car d is installed on the in verter .
28 Intelligent Input T erminal Listing Symbol Code Input T erminal Name FW 00 Forward Run/Stop R V 01 Rev erse Run/Stop CF1 02 Multi-sp eed select, Bit 0 (LSB) CF2 03 Multi-sp eed select, Bit 1 CF3 04.
29 Intelligent Output T erminal Listing Analog Input Configuration The following table sho ws the parameter settings and [A T] state required to select various analog input so urces. Symbol Code Input T erminal N ame R UN 00 Run si gnal F A1 01 Freq. arri val type 1 – constant speed F A2 0 2 Freq.
30 Analog Output Function Listi ng The following table sho ws the functio ns available for assignment to the analog output terminal via term inal [AM], option set by C028: Option Code Function Name Description Corresponding Signal Range 00 Analog freq.
31 NO TES:.
32 NO TES:.
Een belangrijk punt na aankoop van elk apparaat Hitachi SJ2002 (of zelfs voordat je het koopt) is om de handleiding te lezen. Dit moeten wij doen vanwege een paar simpele redenen:
Als u nog geen Hitachi SJ2002 heb gekocht dan nu is een goed moment om kennis te maken met de basisgegevens van het product. Eerst kijk dan naar de eerste pagina\'s van de handleiding, die je hierboven vindt. Je moet daar de belangrijkste technische gegevens Hitachi SJ2002 vinden. Op dit manier kan je controleren of het apparaat aan jouw behoeften voldoet. Op de volgende pagina's van de handleiding Hitachi SJ2002 leer je over alle kenmerken van het product en krijg je informatie over de werking. De informatie die je over Hitachi SJ2002 krijgt, zal je zeker helpen om een besluit over de aankoop te nemen.
In een situatie waarin je al een beziter van Hitachi SJ2002 bent, maar toch heb je de instructies niet gelezen, moet je het doen voor de hierboven beschreven redenen. Je zult dan weten of je goed de alle beschikbare functies heb gebruikt, en of je fouten heb gemaakt die het leven van de Hitachi SJ2002 kunnen verkorten.
Maar de belangrijkste taak van de handleiding is om de gebruiker bij het oplossen van problemen te helpen met Hitachi SJ2002 . Bijna altijd, zal je daar het vinden Troubleshooting met de meest voorkomende storingen en defecten #MANUAl# samen met de instructies over hun opplosinge. Zelfs als je zelf niet kan om het probleem op te lossen, zal de instructie je de weg wijzen naar verdere andere procedure, bijv. door contact met de klantenservice of het dichtstbijzijnde servicecentrum.