USER GUIDE 62-2030-01 Str yker V A V User Guide CONTENTS 1. ABOUT STR YKER V A V ............. .............. .............. ...... 2 1.1 Ov e rview .............. ........... .............. .............. ...... 2 1.2 Features a vailable in the Stryker V A V Configur ation T ool .
STR YKER V A V USER GUIDE 62-2030—0 1 2 1. ABOUT STRYKER V A V 1.1 Overview The Honeywell Stryker V A V de vices are con f ig urab le Lon controllers that can be used to control V A V Zone ter minal box es. These controllers also provide 2 freely configurab le PID loops to make use of an y free pins in the controller .
STRYKER V A V USER GUIDE 3 62-2030—01 1.4 Icons av ailable in the St ryker V A V Configuration T ool T able 2. A vailable Icons. Tip • Numeric values are stored in the application in a defined unit. When these values are loaded in the configuration wizard they ma y be display ed in a different unit.
STR YKER V A V USER GUIDE 62-2030—0 1 4 2. CONFIGURATION 2.1 Adding a de vice Use this page to add an Str yker V A V device to the LON network. Y ou can add a device either in the online mode or the offline mode. T o a dd an Stryker V A V device: 2.
STRYKER V A V USER GUIDE 5 62-2030—01 RELATED T OPICS “1. About Stryker V A V” on page 2 3. CONFIGURING THE OUTPUTS Use this page to conf igure the outputs of the Str yker V A V de vice as we ll as the paramet ers used to control the outputs. To configure outputs : Flow T ype Displays the control flo w algor ithm used by the controller .
STR YKER V A V USER GUIDE 62-2030—0 1 6 3.1 Fields T able 4. Output Fields. Name Definition Output Displa ys the list of Output s th at can be controlled such as: Damper motor , Reheat, P eripheral heat, F an and Wall module occupancy status LED . Output Assignment Displa ys the mode of output assi gnment f or all output types.
STRYKER V A V USER GUIDE 7 62-2030—01 RELATED T OPICS “1. About Stryker V A V” on page 2 “2. Configuration” on page 4 Output Parameters Damper Motor, Reheat, P er ipheral Heat, F an, F reeAn.
STR YKER V A V USER GUIDE 62-2030—0 1 8 4. CONFIGURING THE INPUTS Use this page to configure the inputs used b y the Str yker V A V de vice . This page is also used to configure the optional 10-point custom sensor cur v es. To set inputs: 4.1 Fields Step Action 1 From the left pane of the V A V Configuration Wizard , select Inputs .
STRYKER V A V USER GUIDE 9 62-2030—01 Tip When you upload the input and output values of the configured custom sensors, y o u will not obtain the exact values which y ou configured earlier . There will be slight loss in precision alwa ys. Related Topics “1.
STR YKER V A V USER GUIDE 62-2030—0 1 10 5. CONFIGURING THE SCHEDULE Use this page to configure the schedule e vents and holidays to be used b y the Str yker V A V device . Y ou can also configure occupancy ov err ide related parameters in this page.
STRYKER V A V USER GUIDE 11 62-2030—01 6. CONFIGURING THE T EMPERATURE SETPOINTS Use this page to configure the temperature setpoints used b y the Str yker V A V device and other parameters that a ff ect temperature control. T o configur e temperature setpoints: 6.
STR YKER V A V USER GUIDE 62-2030—0 1 12 RELATED T OPICS “1. About Stryker V A V” on page 2 “2. Conf iguration” on page 4 Setpoint Ramp V alues f or cooling and heati ng setpoint ramp rates. The setpoint Ramp value r anges between 0- 36 Deg F/Hour.
STRYKER V A V USER GUIDE 13 62-2030—01 7. CONFIGURING THE FLOW SETPOINTS Use this page to conf igure flow setpoints for an Stryker V A V device and other parameters that affect flow/damper control. 7.1Pr ocedure To set flow setpoints: 7.2 Fields NO TE: Flow setpoints are enabled only if Pressure T ype is selected as Pressure Independent.
STR YKER V A V USER GUIDE 62-2030—0 1 14 RELATED T OPICS “1. About Stryker V A V” on page 2 “2. Conf iguration” on page 4 K factor This is the V A V Bo x K-factor used to calculate the flow value. IMPORT ANT NO TES: 1. The K factor must be configured before star ting the airflo w balancing procedure.
STRYKER V A V USER GUIDE 15 62-2030—01 8. CONFIGURING THE CONTR OL P ARAMETER S Use this page to set control parameters for an Stry ker V A V device that are used to control the damper .
STR YKER V A V USER GUIDE 62-2030—0 1 16 RELATED T OPICS “1. About Stryker V A V” on page 2 “4. Configuring the In puts” on page 8 9. CONFIGURING THE PID Use this page to conf igure the PID parameters for both the heating and cooling loops in a Str yker V A V de vice.
STRYKER V A V USER GUIDE 17 62-2030—01 RELATED T OPICS “1. About Stryker V A V” on page 2 “2. Configuration” on page 4 10. CONFIGURING THE ACCESSORY LOOPS Use this page to configure accessory loops for Stryker V A V device on the LON netw ork.
STR YKER V A V USER GUIDE 62-2030—0 1 18 Setpoint Configure the setpoints to be used b y the loop in different occupancy modes. Conf igure the minimum and maximum reset values to be used and the corresponding reset sensor values .
STRYKER V A V USER GUIDE 19 62-2030—01 Related T opics “1. About Stryker V A V” on page 2 “2. Configuration” on page 4 “3. Conf iguri ng the Outputs” on page 5 “4. Configuring the Inputs” on page 8 “6. Configuring the T emperatur e Setpoints” on page 11 “8.
STR YKER V A V USER GUIDE 62-2030—0 1 20 12.1 Fields There are fiv e ca tegories of alar ms: Sensor Errors : These errors are generated for all the sensors that are connected to the onboard UI pins in the controll er . All such sensors are monitored by the controller for out-of- range/inv alid values.
STRYKER V A V USER GUIDE 21 62-2030—01 Sylkbus Alarm : The Sylkb us communication alar m occurs when the communication link between the Sylk sensor and the controller is lost or when th e Sylk sensor is configured with the wrong address.
STR YKER V A V USER GUIDE 62-2030—0 1 22 14. FLO W BALANCING The flow balancing view is used to balance a con troller that is programmed with a standard V A V application. Based on the version of the V A V applicatio n a nd its features , the f ollowing operations can be performed on the view .
STRYKER V A V USER GUIDE 23 62-2030—01 T wo point calibration Y ou can star t either maximum or minimum balancing in any order . The tool does not enforce an y rules on the order of balancing. Maximum calibration T o star t maximum calibration: Click Start Maximum Balancing.
STR YKER V A V USER GUIDE 62-2030—0 1 24 15.1 Fields NO TE: Note : Only configurable parameter s are dis- play ed in the Mo nitoring screen. NO TE: Note: For the Monitor Sensor inpu t the value w ill be displa yed as reported from the co ntro ller even if the value li es outsid e the range of the sensor type that is configured.
STRYKER V A V USER GUIDE 25 62-2030—01 16. SENSOR CALIBRATION Use this page for sensor calibration in an Stryker V A V device on the LON network. Using Sensor Calibration feature, y ou can correct the input values to the controller. This action can be performed with the device in onl ine mode.
STR YKER V A V USER GUIDE 62-2030—0 1 26 17. SETTING TIME Use this page to set time f or an Stry ke r V A V device on the LON network. This action can be performe d with the de vi ce in online mode. The controller must be in a commissioned state. Using Se t Time feature , you can specify time or use the computer's time in the controller .
STRYKER V A V USER GUIDE 27 62-2030—01.
STR YKER V A V USER GUIDE Automation and Co ntrol Solutions Honeywell Internationa l Inc. 1985 Douglas Drive North Golden Valley, MN 55422 customer.honeywell.
Een belangrijk punt na aankoop van elk apparaat Honeywell 62-2030-01 (of zelfs voordat je het koopt) is om de handleiding te lezen. Dit moeten wij doen vanwege een paar simpele redenen:
Als u nog geen Honeywell 62-2030-01 heb gekocht dan nu is een goed moment om kennis te maken met de basisgegevens van het product. Eerst kijk dan naar de eerste pagina\'s van de handleiding, die je hierboven vindt. Je moet daar de belangrijkste technische gegevens Honeywell 62-2030-01 vinden. Op dit manier kan je controleren of het apparaat aan jouw behoeften voldoet. Op de volgende pagina's van de handleiding Honeywell 62-2030-01 leer je over alle kenmerken van het product en krijg je informatie over de werking. De informatie die je over Honeywell 62-2030-01 krijgt, zal je zeker helpen om een besluit over de aankoop te nemen.
In een situatie waarin je al een beziter van Honeywell 62-2030-01 bent, maar toch heb je de instructies niet gelezen, moet je het doen voor de hierboven beschreven redenen. Je zult dan weten of je goed de alle beschikbare functies heb gebruikt, en of je fouten heb gemaakt die het leven van de Honeywell 62-2030-01 kunnen verkorten.
Maar de belangrijkste taak van de handleiding is om de gebruiker bij het oplossen van problemen te helpen met Honeywell 62-2030-01 . Bijna altijd, zal je daar het vinden Troubleshooting met de meest voorkomende storingen en defecten #MANUAl# samen met de instructies over hun opplosinge. Zelfs als je zelf niet kan om het probleem op te lossen, zal de instructie je de weg wijzen naar verdere andere procedure, bijv. door contact met de klantenservice of het dichtstbijzijnde servicecentrum.