HA40 4-Channel Contr oller T echnical Man ual ALARM 1 ALARM 2 ALARM 3 COMMON LEVEL ALARMS KEYP AD CAL IN PROGRESS FA UL T ALARM Magnetic Keypad (Key pa d buttons behind door) HA40 Display & Alarm Controller ST AT US LED's Quad Channel Edit Alarm Reset Next 219995 Classified to CS A C22.
HA40 4-Channel Contr oller Re vision 1 (07/08) HA40 T echnical Manual i Safety W arning Read and understand contents of this manual prior to operation.
HA40 4-Channel Contr oller Re vision 1 (08/08) HA40 T echnical Manual ii T ab le of Contents Safety ���������������������������������.
HA40 4-Channel Contr oller Re vision 1 (08/08) HA40 T echnical Manual iii 2 Operation 2 Operation ����������������������������������.
HA40 4-Channel Contr oller Re vision 1 (08/08) HA40 T echnical Manual iv 3 Motherboard Interface PCB 3 Motherboard Interface PCB �����������������������.
HA40 4-Channel Contr oller Re vision 1 (08/08) HA40 T echnical Manual 1-1 1 General Description.
HA40 4-Channel Contr oller Re vision 1 (08/08) HA40 T echnical Manual 1-2 1 General Description The Honeyw ell Analytics HA40 Quad Channel Controller is designed to display , and control alar m e vent switching f or f our inputs. Inputs are typically v oltage or 4-20mA current from transmitters , monitors or other analog output devices .
HA40 4-Channel Contr oller Re vision 1 (08/08) HA40 T echnical Manual 1-3 1�1 Data Displa y Screens The HA40 Controller offers three modes f or displa ying monitored data, shown in Figure 1-4.
HA40 4-Channel Contr oller Re vision 1 (08/08) HA40 T echnical Manual 1-4 The basic HA40 consumes only 1.5 watts of 10-30 VDC from the integral po wer supply . Optional f eatures, and e xternal de vices such as remote transmitters , increase pow er consumption as descr ibed belo w: Discrete Rela y PCB option; add 1.
HA40 4-Channel Contr oller Re vision 1 (08/08) HA40 T echnical Manual 1-5 1�3�6 Housings / Installation Categories *NEMA 4X wall mount. DIV 2 Groups A,B,C ,D; Categor y II and • po llu tio n d egre e 3 ; NE MA 4X ; IP 66* NEM A 7 wal l m oun t for DI V 1 & 2 Groups B,C ,D; includes • o-r ing in door to satisfy NEMA 4 rating.
HA40 4-Channel Contr oller Re vision 1 (07/08) HA40 T echnical Manual 2-1 2 Operation.
HA40 4-Channel Contr oller Re vision 1 (07/08) HA40 T echnical Manual 2-2 2 Operation The HA 40’ s graph ic L CD dis plays m oni tore d d ata. Th e 5- butto n ke ypad and the displa y ser v e as the system’ s operator interf ace.
HA40 4-Channel Contr oller Re vision 1 (07/08) HA40 T echnical Manual 2-3 2�2 Changing Menu V ariables Using the Ke ypad Upon entering a menu, a pointer controlled by the Up/down arrows ke ys points to the selected variable . Some are simple YES/NO or ON/ OFF entries toggl ed by pressin g the Edit ke y .
HA40 4-Channel Contr oller Re vision 1 (07/08) HA40 T echnical Manual 2-4 2�2�3 F ault / Alarm 1 / Alarm 2 / Alarm 3 Set-Up Menus Alarm 1 , 2 and 3 ha ve identical menus . The only diff erence between each is that A1 front panel LED indicators are yellow while A2 and A3 are red.
HA40 4-Channel Contr oller Re vision 1 (07/08) HA40 T echnical Manual 2-5 Name / Eunits ASCII Data Fields The rst two items in this menu are for entering the 10 character channel Name and engineering unit ASCII elds. Name should describe the channel’ s data in user ter minology such as tag # or other description.
HA40 4-Channel Contr oller Re vision 1 (07/08) HA40 T echnical Manual 2-6 2�2�5 Cal Setup Menu The CAL SETUP f eature suppor ts pushbutton calibration of zero and span v alues.
HA40 4-Channel Contr oller Re vision 1 (07/08) HA40 T echnical Manual 2-7 Unity Gain may be used at anytime to cancel incorrect calibrations and star t again.
HA40 4-Channel Contr oller Re vision 1 (07/08) HA40 T echnical Manual 2-8 Over Ride • menu allo ws entering one of the 16 different alar ms that will tr ip this rela y regardless of the V otes entr ies. There are f our alarms per channel and f our channels and any one of these alar ms may be used as the Over Ride.
HA40 4-Channel Contr oller Re vision 1 (07/08) HA40 T echnical Manual 2-9 2�3�4 Analog Setup Menu The system ANALOG SETUP menu allows setting the 12-bit A/D (analog to digital) counts and the 10-bit D/A (digital to analog) counts f or each of the fo ur channe ls.
HA40 4-Channel Contr oller Re vision 1 (07/08) HA40 T echnical Manual 2-10 The Rela y 2 ACK menu item deter mines if standard rela y 2 may be ackno wledged by an Alar m Reset. ON causes an Alar m Reset to silence the hor n e v en though an alar m condition remains activ e.
HA40 4-Channel Contr oller Re vision 1 (07/08) HA40 T echnical Manual 2-11.
HA40 4-Channel Contr oller Re vision 1 (08/08) HA40 T echnical Manual 3-1 3 Motherboar d Interface PCB.
HA40 4-Channel Contr oller Re vision 1 (08/08) HA40 T echnical Manual 3-2 3 Motherboar d Interface PCB (P/N 10-0215) The HA40 Motherboard sho wn in Figure 3.
HA40 4-Channel Contr oller Re vision 1 (08/08) HA40 T echnical Manual 3-3 U2 J1 S1 TP 1 S2 PS 1 U3 CR 5 2- AMP FU SE (5 x 2 0 mm ) U5 K2 K1 P3 J2 3 B T 2 B T 1 B T P1 P2 D2 D1 N/ C N/ O C RE LAY 1 N/ .
HA40 4-Channel Contr oller Re vision 1 (08/08) HA40 T echnical Manual 3-4 3�1�2 Optional Analog Input PCB (P/N 10-0221) T ransmitter input PCB option # 10-0298, shown in Figure 3-3, is av ailab le f or interf acing the HA40 to eld transmitters with 4-20mA or v oltage outputs (0-2 VDC max).
HA40 4-Channel Contr oller Re vision 1 (08/08) HA40 T echnical Manual 3-5 K1, K2, K3, K4, K5 & K6 are programmable , as described in section 2.3.1 Figure 3-5. Optional Discr ete Relay PCB’ s (P/N 10-0222) 3�1�4 Optional 4-20mA Analog Output Board (P/N 10-0308) An optional 4-20mA analog output board, shown in Figure 3-6, ma y be added.
HA40 4-Channel Contr oller Re vision 1 (08/08) HA40 T echnical Manual 3-6 3�2 MODBUS RS-232 / RS-485 Interface Option (P/N 10-0253) The 10-0253 Modbus option PCB add both RS-232 and RS-485 Modbus RTU slav e por ts. Figure 3-7 shows this optional PCB, which mounts to connectors on the upper right cor ner of the HA40 motherboard.
HA40 4-Channel Contr oller Re vision 1 (08/08) HA40 T echnical Manual 3-7 Standard Rela y 1 12017 2 NA Standard Rela y 2 12018 2 NA Optional Rela y 1 12019 2 NA Optional Rela y 2 12020 2 NA Optional R.
HA40 4-Channel Contr oller Re vision 1 (08/08) HA40 T echnical Manual 3-8 CHAN1 F A UL T CHAN1 ALARM1 CHAN1 ALARM2 CHAN1 ALARM3 CHAN2 F A UL T CHAN2 ALARM1 CHAN2 ALARM2 CHAN2 ALARM3 CHAN3 F A UL T CHA.
HA40 4-Channel Contr oller Re vision 1 (08/08) HA40 T echnical Manual 3-9 Chan 1 Alar m 2 Divisor 41008 3 NA Chan 1 Alar m 3 Real 41009 3 NA Chan 1 Alar m 3 Divisor 41010 3 NA Chan 2 Zero Real 41011 3.
HA40 4-Channel Contr oller Re vision 1 (06/08) HA40 T echnical Manual 4-1 4 Enc losures.
HA40 4-Channel Contr oller Re vision 1 (06/08) HA40 T echnical Manual 4-2 4 Enc losures 4�1 HA40N4 NEMA 4X W all Mount Enc losure The HA40-01 wall mount NEMA 4X enclosure is shown in Figure 4-1. Non-metallic enclosures are not grounded b y metal conduit.
HA40 4-Channel Contr oller Re vision (08/08) HA40 T echnical Manual 5-1 5 P ar ts List.
HA40 4-Channel Contr oller Re vision 1 (08/08) HA40 T echnical Manual 5-2 5 P arts List Base Units HA40N4 HA40 4 Channel in NEMA 4X Enclosure incl Magnetic K eypad f or nonintr usiv e control, 4-20mA .
HA40 4-Channel Contr oller Re vision (07/08) HA40 T echnical Manual 6-1 6 Specifications.
HA40 4-Channel Contr oller Re vision 1 (07/08) HA40 T echnical Manual 6-2 5 Specifications Input power: 100-240 V AC , 50/60 Hz 24 VDC DC output power: 15 watts (internal supply) 50 watts (optional e.
HA40 4-Channel Contr oller Re vision 1 (07/08) HA40 T echnical Manual 7-1 7 W arranty.
HA40 4-Channel Contr oller Re vision 1 (07/08) HA40 T echnical Manual 7-2 Honeywell Anal ytics W arranty Statement Al l prod uct s are desi gne d and man uf actu red to the la tes t inte rnati ona lly recognized standards by Honeywell Analytics under a Quality Management System that is cer tied to ISO 9001.
1998M0742 Rev 1 August 2008 © 2007 Honeywell Analytics Find out more www .honeywellanalytics.com Customer business center Americas Honeyw ell Analytics 404 Barcla y Boulev ard Lincolnshire, IL 60069 T el: +1 847 955 8200 T oll free: +1 800 538 0363 F ax: +1 847 955 8208 detectgas@honeyw ell.
Een belangrijk punt na aankoop van elk apparaat Honeywell HA40 (of zelfs voordat je het koopt) is om de handleiding te lezen. Dit moeten wij doen vanwege een paar simpele redenen:
Als u nog geen Honeywell HA40 heb gekocht dan nu is een goed moment om kennis te maken met de basisgegevens van het product. Eerst kijk dan naar de eerste pagina\'s van de handleiding, die je hierboven vindt. Je moet daar de belangrijkste technische gegevens Honeywell HA40 vinden. Op dit manier kan je controleren of het apparaat aan jouw behoeften voldoet. Op de volgende pagina's van de handleiding Honeywell HA40 leer je over alle kenmerken van het product en krijg je informatie over de werking. De informatie die je over Honeywell HA40 krijgt, zal je zeker helpen om een besluit over de aankoop te nemen.
In een situatie waarin je al een beziter van Honeywell HA40 bent, maar toch heb je de instructies niet gelezen, moet je het doen voor de hierboven beschreven redenen. Je zult dan weten of je goed de alle beschikbare functies heb gebruikt, en of je fouten heb gemaakt die het leven van de Honeywell HA40 kunnen verkorten.
Maar de belangrijkste taak van de handleiding is om de gebruiker bij het oplossen van problemen te helpen met Honeywell HA40 . Bijna altijd, zal je daar het vinden Troubleshooting met de meest voorkomende storingen en defecten #MANUAl# samen met de instructies over hun opplosinge. Zelfs als je zelf niet kan om het probleem op te lossen, zal de instructie je de weg wijzen naar verdere andere procedure, bijv. door contact met de klantenservice of het dichtstbijzijnde servicecentrum.