PRODUCT D A T A Copyright © 1996 Honeywell Inc. • All Rights Reserved X-XX UL 60-2337-3 R4140G Flame Safeguard Programming Controls APPLICA TION The R4140G Flame Safeguard Programmers provide flame.
R4140G FLAME SAFEGU ARD PROGRAMMING CONTROLS 60-2337 — 3 2 ORDERING INFORMA TION When purchasing replacement and modernization products from your TRADELINE ® wholesaler or distributor , refer to the TRADELINE ® Catalog or price sheets for complete ordering number or specify order number .
R4140G FLAME SAFEGU ARD PROGRAMMING CONTROLS 60-2337 — 3 3 NOTE: Allowable inrush can be up to ten times the pilot duty rating. EXAMPLE: Pilot duty rating = 50 V A. At 120V , running current is: 50 120 = 0.42A . Maximum allowable inrush is ten times 0.
R4140G FLAME SAFEGU ARD PROGRAMMING CONTROLS 60-2337 — 3 4 Fig. 1. Mounting dimensions of the Q520A wiring subbase in in. (mm). 13/64 (5) DIAMETER (4) (FOR MOUNTING ON 4 X 4 [102 X 102] JUNCTION BOX.
R4140G FLAME SAFEGU ARD PROGRAMMING CONTROLS 60-2337 — 3 5 Accessories: W136A T est Meter (includes 1 17053 Meter Connector Plug); has SPL position with damping for testing self- checking flame detection systems. 1 17053 Meter Connector Plug (for older W136A models).
R4140G FLAME SAFEGU ARD PROGRAMMING CONTROLS 60-2337 — 3 6 OPERA TION Models with Preignition Interlocks Fig. 3 shows all contacts in the standby position (zero seconds). The opening and closing times are shown adjacent Fig. 3. Simplified schematic dia gram of R4140G1015 Programmer .
R4140G FLAME SAFEGU ARD PROGRAMMING CONTROLS 60-2337 — 3 7 Fig. 4. Timer sequence for R4140G1015 Programmer . Step-By-Step Operation (R4140G1015) Start And Prepurge 0 seconds — On a call for heat, the burner controller contacts close.
R4140G FLAME SAFEGU ARD PROGRAMMING CONTROLS 60-2337 — 3 8 Ignition T rials 60 seconds — M4A closes; power is applied to terminals 5 and 6, energizing the ignition transformer and pilot valve (or main fuel valve(s) on terminal 7 if using direct spark ignition).
R4140G FLAME SAFEGU ARD PROGRAMMING CONTROLS 60-2337 — 3 9 Fig. 5. Simplified schematic dia gram of R4140G1106 Programmer . 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 B R W B R W 14 12 11 10 9 L1 (HOT) L2 1 2 120V , 60 HZ POWER SUPPL Y UNDERLINED O OR C DENOTES SNAP A CTION OF CONT ACT .
R4140G FLAME SAFEGU ARD PROGRAMMING CONTROLS 60-2337 — 3 10 Fig. 6. Timer sequence for R4140G1106 Programmer . Step-By-Step Operation (R4140G1106) Start and Prepurge 0 seconds — On a call for heat, the burner controller contacts close.
R4140G FLAME SAFEGU ARD PROGRAMMING CONTROLS 60-2337 — 3 11 Ignition T rials 60 seconds — M4A closes; power is applied to terminals 5 and 6, energizing the ignition transformer and pilot valve (or main fuel valve(s) on terminal 7 If using direct spark ignition).
R4140G FLAME SAFEGU ARD PROGRAMMING CONTROLS 60-2337 — 3 12 Fig. 7. Simplified schematic dia gram of R4140G1049 Programmer . 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 B R W B R W 14 12 11 10 9 L1 (HOT) L2 1 2 120V , 60 HZ POWER SUPPL Y UNDERLINED O OR C DENOTES SNAP A CTION OF CONT ACT .
R4140G FLAME SAFEGU ARD PROGRAMMING CONTROLS 60-2337 — 3 13 Fig. 8. Timer sequence for R4140G1049 Programmer . M10055 TIMER SECONDS TIMER DIAL TIMER MOTOR BURNER MOTOR (BLOWER) INTERRUPTED PILOT/IGN.
R4140G FLAME SAFEGU ARD PROGRAMMING CONTROLS 60-2337 — 3 14 Ignition T rials 60 seconds — M4A closes; power is applied to terminals 18, 5, and 6, energizing the ignition transformer and pilot valve (or main fuel valve(s) on terminal 7 if using direct spark ignition).
R4140G FLAME SAFEGU ARD PROGRAMMING CONTROLS 60-2337 — 3 15 Fig. 9. Simplified schematic dia gram of the R4140G1056 and R4140G1064 Programmer s. 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 B R W B R W 14 12 11 10 9 L1 (HOT) L2 1 2 120V , 60 HZ POWER SUPPL Y UNDERLINED O OR C DENOTES SNAP A CTION OF CONT ACT .
R4140G FLAME SAFEGU ARD PROGRAMMING CONTROLS 60-2337 — 3 16 Fig. 10. Timer sequence for R4140G1056 and R4140G1064 Programmer s. M10056 TIMER SECONDS TIMER DIAL TIMER MOTOR BURNER MOTOR (BLOWER) INTE.
R4140G FLAME SAFEGU ARD PROGRAMMING CONTROLS 60-2337 — 3 17 Ignition T rials 60 seconds — M4A closes; power is applied to terminals 18, 5, and 6, energizing the ignition transformer and pilot valve (or first stage fuel valve when using direct spark ignition).
R4140G FLAME SAFEGU ARD PROGRAMMING CONTROLS 60-2337 — 3 18 Fig. 11. Simplified schematic dia gram of R4140G1171, R4140G122 and R4140G1114 Programmer s. 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 B R W B R W 14 12 11 10 9 L1 (HOT) L2 1 2 120V , 60 HZ POWER SUPPL Y UNDERLINED O OR C DENOTES SNAP A CTION OF CONT ACT .
R4140G FLAME SAFEGU ARD PROGRAMMING CONTROLS 60-2337 — 3 19 Fig. 12. Timer sequence for R4140G1171, R4140G1122 and R4140G1114 Programmer s. M10057 1 2 3 4 5 6 TERMINAL NUMBERS (CIRCLED). SLOPE DEPENDS ON MOTOR TIMING. TIMER STOPS AT 60 SECONDS UNTIL LOW FIRE PROVING SWITCH CLOSES.
R4140G FLAME SAFEGU ARD PROGRAMMING CONTROLS 60-2337 — 3 20 Ignition T rials 70 seconds — M4A closes; power is applied to terminals 18, 5 and 6, energizing the ignition transformer and pilot valve (and terminal 7, main oil valve solenoid, if using direct spark ignition of oil).
R4140G FLAME SAFEGU ARD PROGRAMMING CONTROLS 60-2337 — 3 21 Fig. 13. Simplified schematic dia gram of R4140G1148 Programmer . 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 B R W B R W 14 12 11 10 9 L1 (HOT) L2 1 2 120V , 60 HZ POWER SUPPL Y UNDERLINED O OR C DENOTES SNAP A CTION OF CONT ACT .
R4140G FLAME SAFEGU ARD PROGRAMMING CONTROLS 60-2337 — 3 22 Fig. 14. Timer sequence for R4140G1148 Programmer . Step-By-Step Operation (R4140G1148) Start and Prepurge 0 seconds — On a call for heat, the burner controller contacts close.
R4140G FLAME SAFEGU ARD PROGRAMMING CONTROLS 60-2337 — 3 23 Ignition T rials 60 seconds — M4A closes; power is applied to terminals 18, 5 and 6, energizing the ignition transformer and pilot valve (or main fuel valve(s) on terminal 7 if using direct spark ignition).
R4140G FLAME SAFEGU ARD PROGRAMMING CONTROLS 60-2337 — 3 24 Fig. 15. Sample bloc k diagram of field wiring f or R4140G1007, R4140G1015 and R4140G1106 Programmer s.
R4140G FLAME SAFEGU ARD PROGRAMMING CONTROLS 60-2337 — 3 25 Fig. 16. Sample bloc k diagram of field wiring f or R4140G1049, R4140G1056, R4140G1064, R4140G1114, R4140G1122, R4140G1148 and R4140G1171 Programmer s.
R4140G FLAME SAFEGU ARD PROGRAMMING CONTROLS 60-2337 — 3 26 Optional Hookups f or T wo-Sta ge Switching or Intermittent Pilot/Ignition (Nonmodulating Oil Burners) If modulation of the firing rate is.
R4140G FLAME SAFEGU ARD PROGRAMMING CONTROLS 60-2337 — 3 27 M10061 TIMER SECONDS INTERRUPTED PILOT/IGNITION OR 1ST STAGE OIL VALVE 20 SECOND INTERRUPTED PILOT/IGNITION MAIN FUEL VALVE OR 2ND STAGE OIL VALVE 0 10 20 30 40 50 60 70 80 90 100 110 120 3 1 1 2 3 2 12 5 6 TERMINAL NUMBERS (CIRCLED).
R4140G FLAME SAFEGU ARD PROGRAMMING CONTROLS 60-2337 — 3 28 Honeywell Europe S.A. 3 Avenue du Bourget B-1140 Brussels Belgium Honeywell Asia Pacific Inc.
Een belangrijk punt na aankoop van elk apparaat Honeywell R4140G (of zelfs voordat je het koopt) is om de handleiding te lezen. Dit moeten wij doen vanwege een paar simpele redenen:
Als u nog geen Honeywell R4140G heb gekocht dan nu is een goed moment om kennis te maken met de basisgegevens van het product. Eerst kijk dan naar de eerste pagina\'s van de handleiding, die je hierboven vindt. Je moet daar de belangrijkste technische gegevens Honeywell R4140G vinden. Op dit manier kan je controleren of het apparaat aan jouw behoeften voldoet. Op de volgende pagina's van de handleiding Honeywell R4140G leer je over alle kenmerken van het product en krijg je informatie over de werking. De informatie die je over Honeywell R4140G krijgt, zal je zeker helpen om een besluit over de aankoop te nemen.
In een situatie waarin je al een beziter van Honeywell R4140G bent, maar toch heb je de instructies niet gelezen, moet je het doen voor de hierboven beschreven redenen. Je zult dan weten of je goed de alle beschikbare functies heb gebruikt, en of je fouten heb gemaakt die het leven van de Honeywell R4140G kunnen verkorten.
Maar de belangrijkste taak van de handleiding is om de gebruiker bij het oplossen van problemen te helpen met Honeywell R4140G . Bijna altijd, zal je daar het vinden Troubleshooting met de meest voorkomende storingen en defecten #MANUAl# samen met de instructies over hun opplosinge. Zelfs als je zelf niet kan om het probleem op te lossen, zal de instructie je de weg wijzen naar verdere andere procedure, bijv. door contact met de klantenservice of het dichtstbijzijnde servicecentrum.