INST ALLA TION INSTRUCTIONS 62-0311—1 3 TB6575/TB8575 Digital F an Coil Thermostats PRODUCT DESCRIPTION The TB6575 and TB8575 are a fa mily of Digi tal F an Co il therm ostats for residential and comm ercial applications such as hotels, condomin iums, school classrooms, etc.
TB6575/TB8575 DIGITAL F AN COIL THERMOSTATS 62-0311—13 2 SPECIFICATIONS Supply V olta ges: TB6575A10 16 and TB65 75B1000: • 120 V ac ±10 % at 50/60Hz • 240 V ac -15% to +10% at 50 /60Hz TB6575C.
TB6575/TB8575 DIGITAL F AN COIL THER MOSTATS 3 62-0311—13 T able 2. Ap plication s and Features Fig. 1. Dime nsions in in ches (mm). INSTALLATION When Installing this Pr oduct… 1. Read these inst ructions ca refully . Failure to follo w them could da mage the pro duct or caus e a hazard- ous condition.
TB6575/TB8575 DIGITAL F AN COIL THERMOSTATS 62-0311—13 4 adaptor plate (50033847 -001) can be used wit h a 4 x 4 in . or a vert ical junction box for which mounting screws are supplied (see F ig. 3 on pa ge 5). 1. Prepare th e supply wires : a. Mounting on a 4 x 4 in.
TB6575/TB8575 DIGITAL F AN COIL THER MOSTATS 5 62-0311—13 Fig. 3. Mount ing sub-base and thermostat using the adap tor plate (50 033847-001) . T e rminal Wiring T able 3 provides the ter minal wir ing for each model an d application.
TB6575/TB8575 DIGITAL F AN COIL THERMOSTATS 62-0311—13 6 T erminal Identifier LW / Y n / a i Gl Gm Gh N Rs a Sc b SB c Ps d Fly lead wire color Black Orange Red Blue Brown White None e 2 pipes; Heat.
TB6575/TB8575 DIGITAL F AN COIL THER MOSTATS 7 62-0311—13 Accessory Wiring Remote Pipe Sensor Wiring The remote pipe sensor is us ed for 2 pipes auto a nd 2 pipes heat and cool with auxi liar y heat change ov er . The pipe sensor will sense the temperatur e in the pipes to tell the ther mostat when the system is set for Heat or Cool.
TB6575/TB8575 DIGITAL F AN COIL THERMOSTATS 62-0311—13 8 Thermostat Wiring Diagrams The figures in this section illust rate typical wiring for : • TB6575A1016,TB65 75B1000 and TB6575C1016 fan coil ther mostats, which are 120/24 0/277 V ac p owered.
TB6575/TB8575 DIGITAL F AN COIL THER MOSTATS 9 62-0311—13 . Fig. 13. Wirin g diagram wh en missi ng a wire for electromechanical r etrofit (120/240/ 277 V ac shown). 24 V ac Wiring Diagrams (TB8575) For the TB8575A1016 model, a 24 V ac C lass 2 NEMA rated transformer must be used.
TB6575/TB8575 DIGITAL F AN COIL THERMOSTATS 62-0311—13 10 Fig. 19. T wo pipes (Heat or Cool) wi th A uxiliary Heat and Manual Ch angeover wir ing diagram (24 V a c shown ). . Fig. 20. Wirin g diagram wh en missi ng a wire for electr omechani cal retr ofit (24 V ac shown).
TB6575/TB8575 DIGITAL F AN COIL THER MOSTATS 11 62-0311—13 Fig. 23. LCD displ ay sho wing default screen. Po w e r - u p At power-up, the thermostat’s LCD shows all display segments fo r two seco nds, en ters a sel f-test mo de f or a fe w seconds, and then d isplays the current room temperature (d efault screen), as shown in F ig.
TB6575/TB8575 DIGITAL F AN COIL THERMOSTATS 62-0311—13 12 2 System T ype 0 Heat only 1 Cool only 2 T wo pipes: Heat or Cool; Manual Changeover 3 T wo pipes: Heat or Coo l; Seasona l Changeo ver (req.
TB6575/TB8575 DIGITAL F AN COIL THER MOSTATS 13 62-0311—13 10 Control Meth od for 4-Pipe A uto Changeover 1 Singl e Setpoi nt (Defaul t) Uses switching diff erential to change b etween heating and c.
TB6575/TB8575 DIGITAL F AN COIL THERMOSTATS 62-0311—13 14 Installer T est (IT) Mode T o enter Installer T est Mode: • Press and hold both the Up arrow button and th e Down Ar ro w butt on for th ree (3) second s. This disp la ys all segm ents of th e LCD scre en on the LCD .
TB6575/TB8575 DIGITAL F AN COIL THER MOSTATS 15 62-0311—13 3. After the desire d value displays , press the Syst em button to store your value selection and dis play the next IT code. NO TE: Ex iting Insta ller T est Mode is the same as the method for en tering t est mode , Fig.
TB6575/TB8575 DIGITAL F AN COIL THERMOSTATS 62-0311—13 16 Fig. 26. Auto Chang eover with Heat/Coo l Setpoints deadband illu stration. For 4 pipe applications with Auto Changeover and a single setpoint, when Economy Setback is enabled, the setpoint will rev er t to a dual he at/cool setpoint approach.
TB6575/TB8575 DIGITAL F AN COIL THER MOSTATS 17 62-0311—13 T able 7. Log ic for 2 Pipes with Auxiliar y Heat If pipe temperatu re is between the two threshold values after the 5 m inute purge occur s, the therm ostat will activ ate a second 5 min ute purge to doub le check the wate r temper ature.
TB6575/TB8575 DIGITAL F AN COIL THERMOSTATS 62-0311—13 18 T ROUBLESHOOTING T able 8 provides troubleshooting in formation. T able 8. T roubl eshooting. Symptom P ossible Cause Action Display does not come on. Thermostat is not being pow ered. For TB6575A/B/C, check f o r 120/240 /277 V ac b etween L and N.
TB6575/TB8575 DIGITAL F AN COIL THER MOSTATS 19 62-0311—13 Cooling does no t turn on (Cool On is so lid in the display). Cooling equipm ent failure. For TB6575A/ B/C: 1. Check f or 120/240/2 77 V ac at t he equipment be tween power and common , (terminals L an d N).
TB6575/TB8575 DIGITAL F AN COIL THERMOSTATS Automation and Control Solutions Honeywell Intern ational Inc. 1985 Douglas Drive North Golden Valley, MN 55422 customer.hone ywell.com ® U.S . Registered T rademark © 2013 Honey well International In c. 62-0311—13 KK Re v .
Een belangrijk punt na aankoop van elk apparaat Honeywell TB8575 (of zelfs voordat je het koopt) is om de handleiding te lezen. Dit moeten wij doen vanwege een paar simpele redenen:
Als u nog geen Honeywell TB8575 heb gekocht dan nu is een goed moment om kennis te maken met de basisgegevens van het product. Eerst kijk dan naar de eerste pagina\'s van de handleiding, die je hierboven vindt. Je moet daar de belangrijkste technische gegevens Honeywell TB8575 vinden. Op dit manier kan je controleren of het apparaat aan jouw behoeften voldoet. Op de volgende pagina's van de handleiding Honeywell TB8575 leer je over alle kenmerken van het product en krijg je informatie over de werking. De informatie die je over Honeywell TB8575 krijgt, zal je zeker helpen om een besluit over de aankoop te nemen.
In een situatie waarin je al een beziter van Honeywell TB8575 bent, maar toch heb je de instructies niet gelezen, moet je het doen voor de hierboven beschreven redenen. Je zult dan weten of je goed de alle beschikbare functies heb gebruikt, en of je fouten heb gemaakt die het leven van de Honeywell TB8575 kunnen verkorten.
Maar de belangrijkste taak van de handleiding is om de gebruiker bij het oplossen van problemen te helpen met Honeywell TB8575 . Bijna altijd, zal je daar het vinden Troubleshooting met de meest voorkomende storingen en defecten #MANUAl# samen met de instructies over hun opplosinge. Zelfs als je zelf niet kan om het probleem op te lossen, zal de instructie je de weg wijzen naar verdere andere procedure, bijv. door contact met de klantenservice of het dichtstbijzijnde servicecentrum.