506 01 5001 00 May 2007 INST ALLA TION INSTRUCTIONS 3-phase R-22 Split System Heat Pump Product Family: N2H3, H2H3 These instructions must be read and understood completely before attempting installation.
INST ALLA TION INSTRUCTIONS 3-phase R-22 Split System Heat Pump 2 506 01 5001 00 INSPECT NEW UNIT After uncrating unit, inspect thoroughly for hidden damage. If damage is found, notify the transportation company immediately and file a concealed damage claim.
INST ALLA TION INSTRUCTIONS 3-phase R-22 Split System Heat Pump 506 01 5001 00 3 Figure 1 Clearances (various examples) W all 6” 24” Service W all W all W all 6” 6” Post W all W all 18” 18.
INST ALLA TION INSTRUCTIONS 3-phase R-22 Split System Heat Pump 4 506 01 5001 00 UNIT SUPPORT NOTE: Unit must be level | 2 degrees ( a inch rise or fall per foot of run) or compressor may not function properly . A. GROUND LEVEL INST ALLA TION The unit must be level and supported above grade by beams, platform, or a pad.
INST ALLA TION INSTRUCTIONS 3-phase R-22 Split System Heat Pump 506 01 5001 00 5 ! CAUTION PRODUCT DAMAGE HAZARD Failure to follow this caution may result in product damage. Indoor coil and outdoor unit must be listed as a certified combination (match) in the ARI Unitary Directory of Certified Products.
INST ALLA TION INSTRUCTIONS 3-phase R-22 Split System Heat Pump 6 506 01 5001 00 C. ROUTING AND SUSPENDING REFRIGERANT LINES Run refrigerant lines as straight and direct as possible, avoiding unnecessary bends and turns. Always insulate the entire suction line.
INST ALLA TION INSTRUCTIONS 3-phase R-22 Split System Heat Pump 506 01 5001 00 7 Figure 7 Liquid Line Filter-Drier Installed at Indoor Coil 38-1 1-84 Filter-Drier F . SERVICE V AL VES Service valves are closed and plugged from the factory . Outdoor units are shipped with a refrigerant charge sealed i n the unit.
INST ALLA TION INSTRUCTIONS 3-phase R-22 Split System Heat Pump 8 506 01 5001 00 H. EV ACUA TING LINE SET AND INDOOR COIL The unit is shipped with a factory refrigerant charge. The liquid line and suction line service valves have been closed after final testing at the factory .
INST ALLA TION INSTRUCTIONS 3-phase R-22 Split System Heat Pump 506 01 5001 00 9 NOTE: These are not back-seating valves. It is not necessary to force the stem tightly against the rolled lip. The service valve cap is a primary seal for the valve and must be properly tightened to prevent leaks.
INST ALLA TION INSTRUCTIONS 3-phase R-22 Split System Heat Pump 10 506 01 5001 00 Thermostat Wiring Connections Route thermostat wiring through rubber grommet in bottom of Control Box. Low voltage lead wires are provided in the control box for connection to thermostat wires (use wire nuts).
INST ALLA TION INSTRUCTIONS 3-phase R-22 Split System Heat Pump 506 01 5001 00 11 DEFROST SYSTEM A. DEFROST THERMOST A T The defrost thermostat is factory installed on a short tube stub extending from the coil end plate. Refer to Figure 14 and confirm that the thermostat is securely fastened in place on the tube stub.
INST ALLA TION INSTRUCTIONS 3-phase R-22 Split System Heat Pump 12 506 01 5001 00 ST ART-UP PROCEDURE 1. Set indoor thermostat selector switch to OFF . 2. T urn ON all electrical disconnect devices. 3. I f unit has a crankcase heater , energize the heater and wait 24 hours before proceeding.
INST ALLA TION INSTRUCTIONS 3-phase R-22 Split System Heat Pump 506 01 5001 00 13 Figure 16 R-22 Required Liquid Line T emperature ( ° F) - Cooling Mode Measured Liquid Pressure (psig) Rating Plate (.
INST ALLA TION INSTRUCTIONS 3-phase R-22 Split System Heat Pump 14 506 01 5001 00 TROUBLESHOOTING Some models are factory equipped with the Comfort Alert t Diagnostics device in the control box (refer to Figure 17). Comfort Alert provides around-the-clock monitoring for common electrical problems, compressor defects, and broad system faults.
INST ALLA TION INSTRUCTIONS 3-phase R-22 Split System Heat Pump 506 01 5001 00 15 Figure 18 Comfort Alert t Diagnostics (some models) Status LED Status LED Description Status LED T roubleshooting Info.
INST ALLA TION INSTRUCTIONS 3-phase R-22 Split System Heat Pump 16 506 01 5001 00 Figure 19 Comfort Alert t Diagnostics (some models) Miswired Module Indication T roubleshooting Information Green LED is not on, module does not power up Determine if both R and C module terminals are connected.
Een belangrijk punt na aankoop van elk apparaat HP H2H3 (of zelfs voordat je het koopt) is om de handleiding te lezen. Dit moeten wij doen vanwege een paar simpele redenen:
Als u nog geen HP H2H3 heb gekocht dan nu is een goed moment om kennis te maken met de basisgegevens van het product. Eerst kijk dan naar de eerste pagina\'s van de handleiding, die je hierboven vindt. Je moet daar de belangrijkste technische gegevens HP H2H3 vinden. Op dit manier kan je controleren of het apparaat aan jouw behoeften voldoet. Op de volgende pagina's van de handleiding HP H2H3 leer je over alle kenmerken van het product en krijg je informatie over de werking. De informatie die je over HP H2H3 krijgt, zal je zeker helpen om een besluit over de aankoop te nemen.
In een situatie waarin je al een beziter van HP H2H3 bent, maar toch heb je de instructies niet gelezen, moet je het doen voor de hierboven beschreven redenen. Je zult dan weten of je goed de alle beschikbare functies heb gebruikt, en of je fouten heb gemaakt die het leven van de HP H2H3 kunnen verkorten.
Maar de belangrijkste taak van de handleiding is om de gebruiker bij het oplossen van problemen te helpen met HP H2H3 . Bijna altijd, zal je daar het vinden Troubleshooting met de meest voorkomende storingen en defecten #MANUAl# samen met de instructies over hun opplosinge. Zelfs als je zelf niet kan om het probleem op te lossen, zal de instructie je de weg wijzen naar verdere andere procedure, bijv. door contact met de klantenservice of het dichtstbijzijnde servicecentrum.