Gebruiksaanwijzing /service van het product 7800 Series van de fabrikant 2nd Ave.
Ga naar pagina of 20
® U.S. Registered Trademark Copyright © 1998 Honeywell Inc. • All Rights Reserved CHECKOUT AND TEST 65-0229-1 7800 SERIES Relay Modules This publication provides gener al checkout and troub leshooting procedures for the 7800 SERIES Rela y Modules.
2 7800 SERIES RELA Y MODULES 65-0229—1 T able 1. Chec kout Steps and Applicable 7800 Series Systems. Checkout Step Piloted Systems DSI Systems Infrared Flame Detectors Flame Rod Systems Ultraviolet .
7800 SERIES RELA Y MODULES 3 65-0229—1 b . On the subbase, jumper L1 to the ignition ter minal; ref er to the appropriate wir ing diagr am to deter mine the proper terminal. Disconnect the leadwire to the pilot valv e if it is connected to the same ter minal.
4 7800 SERIES RELA Y MODULES 65-0229—1 12. W ait about three minutes. Close the master s witch, open the manual fuel shutoff v alve(s), and tr y to light off the burner again. The first attempt may be required to purge the lines and bring sufficient fuel to the burner .
7800 SERIES RELA Y MODULES 5 65-0229—1 12. Close the master switch to recycle the b ur ner and stop the sequence in the PILOT period b y using the Run/ T est Switch. 13. Increase the pilot flame size by increasing its fuel flo w until a smooth main flame is accomplished.
6 7800 SERIES RELA Y MODULES 65-0229—1 IGNITION SP ARK RESPONSE TEST (ALL UL TRA VIOLET DETECT ORS) T est to mak e cer tain that the ignition spar k is not actuating the FLAME LED: 1. Close the pilot and main burner manual fuel shut-off valv e(s). 2.
7800 SERIES RELA Y MODULES 7 65-0229—1 6. Loss of flame during RUN. a. Open the main fuel manual shutoff valv e(s) and open manual pilot shutoff valv e(s). b . Depress the RESET button. c. Star t the system. Star t-up should be normal and the main b ur ner should light nor mally .
8 7800 SERIES RELA Y MODULES 65-0229—1 Table 2. Keyboard Display Module Sequence and Status Hold Messages. Sequence Status INITIATE mm:ss The Keyboard Display Module (KDM) indicates the burner statu.
7800 SERIES RELA Y MODULES 9 65-0229—1 T able 2. Keyboar d Display Module Sequence and Status Hold Messages (continued). Sequence Status If the relay module is in a PURGE HOLD status, the following .
10 7800 SERIES RELA Y MODULES 65-0229—1 T able 3. Hold and F ault Message Summary . Fault Code System Failure Recommended Troubleshooting Fault 1 *No Purge Card* No card is plugged into the purge card slot. 1 . Make sure the purge card is seated properly.
7800 SERIES RELA Y MODULES 11 65-0229—1 T ab le 3. Hold and F ault Message Summary (continued). (continued) Fault Code System Failure Recommended Troubleshooting Fault 11 *Running ILK On* Running Interlock powered at improper sequence point. 1 . Check wiring to make sure that interlocks are connected properly between terminals 6 and 7.
12 7800 SERIES RELA Y MODULES 65-0229—1 T able 3. Hold and Fault Message Summary (continued). Fault Code System Failure Recommended Troubleshooting Fault 18 *Flame Detected* Flame sensed when shutter is open and no flame is expected during PREPURGE.
7800 SERIES RELA Y MODULES 13 65-0229—1 T ab le 3. Hold and F ault Message Summary (continued). Fault Code System Failure Recommended Troubleshooting Fault 27 *Start Switch On* Start Switch was on during PREPURGE (RM7838A, RM7838B only). 1 . Start Switch held on too long.
14 7800 SERIES RELA Y MODULES 65-0229—1 T able 3. Hold and Fault Message Summary (continued). Fault Code System Failure Recommended Troubleshooting Fault 32 *Airflow Switch* Combustion Airflow Interlock fault. 1 . Check wiring; correct any errors. 2 .
7800 SERIES RELA Y MODULES 15 65-0229—1 T ab le 3. Hold and F ault Message Summary (continued). Fault Code System Failure Recommended Troubleshooting Fault 45 *Low Fire Sw. Off* Low Fire Interlock switch failure to close or stay closed. 1 . Check wiring; correct any errors.
16 7800 SERIES RELA Y MODULES 65-0229—1 T able 3. Hold and Fault Message Summary (continued). Fault Code System Failure Recommended Troubleshooting Fault 51 *Flame Too Strong* Flame signal value is too high to be valid. 1 . Make sure that flame detector and flame amplifier are compatible.
7800 SERIES RELA Y MODULES 17 65-0229—1 T ab le 3. Hold and F ault Message Summary (continued). (continued) Fault Code System Failure Recommended Troubleshooting Fault 68 *Preignition ILK* Preignition Interlock fault. 1 . Check wiring; correct any errors.
18 7800 SERIES RELA Y MODULES 65-0229—1 T able 3. Hold and Fault Message Summary (continued). Fault Code System Failure Recommended Troubleshooting Fault 109 *Call Service* Negative cycle test failed, earth ground absent or line voltage phasing improper.
7800 SERIES RELA Y MODULES 19 65-0229—1.
20 7800 SERIES RELA Y MODULES 65-0229—1 65-0229—1 G.R. Re v . 4-98 Home and Building Control Honeywell Limited-Honeywell Limitée 155 Gordon Baker Road North York, Ontario M2H 3N7 Home and Building Control Honeywell Inc. Honeywell Plaza P.O. Box 524 Minneapolis MN 55408-0524 Printed in U.
Een belangrijk punt na aankoop van elk apparaat 2nd Ave. 7800 Series (of zelfs voordat je het koopt) is om de handleiding te lezen. Dit moeten wij doen vanwege een paar simpele redenen:
Als u nog geen 2nd Ave. 7800 Series heb gekocht dan nu is een goed moment om kennis te maken met de basisgegevens van het product. Eerst kijk dan naar de eerste pagina\'s van de handleiding, die je hierboven vindt. Je moet daar de belangrijkste technische gegevens 2nd Ave. 7800 Series vinden. Op dit manier kan je controleren of het apparaat aan jouw behoeften voldoet. Op de volgende pagina's van de handleiding 2nd Ave. 7800 Series leer je over alle kenmerken van het product en krijg je informatie over de werking. De informatie die je over 2nd Ave. 7800 Series krijgt, zal je zeker helpen om een besluit over de aankoop te nemen.
In een situatie waarin je al een beziter van 2nd Ave. 7800 Series bent, maar toch heb je de instructies niet gelezen, moet je het doen voor de hierboven beschreven redenen. Je zult dan weten of je goed de alle beschikbare functies heb gebruikt, en of je fouten heb gemaakt die het leven van de 2nd Ave. 7800 Series kunnen verkorten.
Maar de belangrijkste taak van de handleiding is om de gebruiker bij het oplossen van problemen te helpen met 2nd Ave. 7800 Series . Bijna altijd, zal je daar het vinden Troubleshooting met de meest voorkomende storingen en defecten #MANUAl# samen met de instructies over hun opplosinge. Zelfs als je zelf niet kan om het probleem op te lossen, zal de instructie je de weg wijzen naar verdere andere procedure, bijv. door contact met de klantenservice of het dichtstbijzijnde servicecentrum.