562156-UIM-A-0610 R-410A OUTDOOR SPLIT -SYSTEM AIR CONDITIONING MODELS: 16 SEER - CZF / AC6B / AL6B SERIES 2 TO 5 T ONS INSTALLATION MANUAL LISTED ISO 9001 Certified Quality Management System T ABLE OF CONTENTS GENERAL . . . . . . . . . . . . . . . . .
562156-UIM-A-0610 2 Johnson Controls Unitary Products INSPECTION As soon as a unit is r eceived, it should be inspected for possible dam- age during transit. If damage is evident, th e extent of the damage should be noted on the carrier ’s delivery receipt.
562156-UIM-A-0610 Johnson Controls Unitary Produ cts 3 GROUND IN ST ALLA TION The unit may be installed at ground level on a solid b ase that will not shift or settle, causing strain on t he refrigerant lines and possible leaks.
562156-UIM-A-0610 4 Johnson Controls Unitary Products The outdoor condensing unit must be connected to the indoor evapora - tor coil using field supplied refrigerant grade copper tubing that is inter- nally clean and dry . Units should be installed only with the tubing sizes for approved system combinations as specified in tabular data sheet.
562156-UIM-A-0610 Johnson Controls Unitary Produ cts 5 2. Remove the cap and Schrader core from both the liquid and vapor service valve service ports at th e outdoor unit. Connect low pressure nitrogen to the liquid line service port. 3. Braze the liquid line to the liquid valve at the outdoor unit.
562156-UIM-A-0610 6 Johnson Controls Unitary Products FIELD CONNECTIONS POWER WIRING 1. Install the proper size weather proof disconnect switch outdoors and within sight of the unit. 2. Remove the screws at the bottom of the corner cover . Slide corner cover down and remove from unit.
562156-UIM-A-0610 Johnson Controls Unitary Produ cts 7 CFM SELECTION BOARD SETTINGS For proper system operation the CFM Selection Board jumpers must be set properly . Refer to the T ech Guide for the recommende d air flow settings for each size condensing unit and matchu p.
562156-UIM-A-0610 8 Johnson Controls Unitary Products For additional connection diagrams for a ll UPG equipment refer to “Low V olt age System Wiring” document available online at www .
562156-UIM-A-0610 Johnson Controls Unitary Produ cts 9 FIGURE 1 1: Thermostat Wiring – Single S tage Air Conditioner (with AC control) – VS Air Handler 09 $9 ,'02'(/ 6 -XPSHU.
562156-UIM-A-0610 10 Johnson Controls Unitary Products FIGURE 12: Thermostat Wiring – Single S tage Air Conditi oner (with AC control) – Modulating F urnace </&/&.
562156-UIM-A-0610 Johnson Controls Unitary Produ cts 11 SECTION VI: SY STEM CHARGE 1. The factory charge in the outdoor unit includes enough charge for the unit, a 15 ft. line set and the smallest rated indoor coil match-up. Some indoor coil matches may r equire additional charge.
562156-UIM-A-0610 12 Johnson Controls Unitary Products 3. If the coil needs to be cleaned , use clean water to wash dust, dir t, and debris from outdoor condensing coil. 4. Refer to the furnace or air handler instructions for filter a nd blower motor maintenance.
562156-UIM-A-0610 Johnson Controls Unitary Produ cts 13 LED DIAGN OSTIC INDICA TORS The control includes two LED’s that display diagnostic information. LED1 is red and LED2 is green. These LED’s are used to display oper- ational mode, fault information.
562156-UIM-A-0610 14 Johnson Controls Unitary Products F AUL T CODE DISPLA Y The control will display any fault cod e that is currently active using the LED’s.
562156-UIM-A-0610 Johnson Controls Unitary Produ cts 15 COOLING OPERA TION First-St age Cooling Operation During first-stage cooling operation, the con trol will receive a thermostat signal at the Y1 terminal. The contr ol will energize the M compressor output terminal.
562156-UIM-A-0610 16 Johnson Controls Unitary Products SECTION IX: WIRING DIAGRAM FIGURE 13: Wiring Diagram (2 - 4 T on).
562156-UIM-A-0610 Johnson Controls Unitary Produ cts 17 FIGURE 14: Wiring Diagram (5 T on).
Subject to change without not ice. Published in U.S.A. 562156-UIM-A-0610 Copyright © 2010 by Johnson Controls, Inc. All rights reserved. Supersedes: Nothing Johnson Contro ls Unitar y Prod uc t s 500.
Een belangrijk punt na aankoop van elk apparaat Johnson Controls AC6B (of zelfs voordat je het koopt) is om de handleiding te lezen. Dit moeten wij doen vanwege een paar simpele redenen:
Als u nog geen Johnson Controls AC6B heb gekocht dan nu is een goed moment om kennis te maken met de basisgegevens van het product. Eerst kijk dan naar de eerste pagina\'s van de handleiding, die je hierboven vindt. Je moet daar de belangrijkste technische gegevens Johnson Controls AC6B vinden. Op dit manier kan je controleren of het apparaat aan jouw behoeften voldoet. Op de volgende pagina's van de handleiding Johnson Controls AC6B leer je over alle kenmerken van het product en krijg je informatie over de werking. De informatie die je over Johnson Controls AC6B krijgt, zal je zeker helpen om een besluit over de aankoop te nemen.
In een situatie waarin je al een beziter van Johnson Controls AC6B bent, maar toch heb je de instructies niet gelezen, moet je het doen voor de hierboven beschreven redenen. Je zult dan weten of je goed de alle beschikbare functies heb gebruikt, en of je fouten heb gemaakt die het leven van de Johnson Controls AC6B kunnen verkorten.
Maar de belangrijkste taak van de handleiding is om de gebruiker bij het oplossen van problemen te helpen met Johnson Controls AC6B . Bijna altijd, zal je daar het vinden Troubleshooting met de meest voorkomende storingen en defecten #MANUAl# samen met de instructies over hun opplosinge. Zelfs als je zelf niet kan om het probleem op te lossen, zal de instructie je de weg wijzen naar verdere andere procedure, bijv. door contact met de klantenservice of het dichtstbijzijnde servicecentrum.