FOR DISTRIBUTION USE ONLY - NOT TO BE USED AT POINT OF RETAIL SALE 279815-PTG-D- 0408 DESCRIPTION These packaged cooling air conditi oners are designed for outdoor installation. Only ut i lity and duct connections are required at the point of installation.
279815-PTG-D-0408 2 Johnson Controls Unitary Products TABLE OF CONTENTS DESCRIPTION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1 STANDARD FEATURES / BENEFITS . . . . . . . . . . . . . . . . . 1 FIELD-INSTALLED ACCESSORIES . .
279815-PTG-D-0408 Johnson Controls Unitary Products 3 DESCRIPTION (CONTINUED) UTILITY CONNECTIONS MADE EASY - Electri c al utility knockouts are provided through the bottom as well as the side of the unit. Utility connections can be made quickly and with a minimum amount of field labor.
279815-PTG-D-0408 4 Johnson Controls Unitary Products operation. Independe nt blade desig n insures p roper control and less than 1% leak rate. Includes hood an d me sh bird screen filter integrated into the ho od, dry bulb senso r and relie f damper.
279815-PTG-D-0408 Johnson Controls Unitary Products 5 SEER = Seasonal Energy Efficiency Ratio - the total coolin g output in BTU's during a normal annual usage period for cooling div ided by the total electric power input in watt-hours dur ing the same period.
279815-PTG-D-0408 6 Johnson Controls Unitary Products T ABLE 3: COOLING CAP ACITIES - 2 TON (ACP024) Air on Evaporator Coil Temperature of Air on Condenser Coil Total Capacity 1 (MBh) Total Input (kW).
279815-PTG-D-0408 Johnson Controls Unitary Products 7 115°F 125°F 600 77 22.9 2.5 11.4 8.7 6.0 - - - 21.2 2.7 11.0 8.2 5.4 - - - 72 20.4 2.4 15.0 12.3 9.6 6.9 - - 18.1 2.6 14.4 11.6 8.8 6.0 - - 67 17.8 2.3 17.0 16.0 13.2 10.5 7.8 - 15.1 2.5 15.0 15.
279815-PTG-D-0408 8 Johnson Controls Unitary Products T ABLE 4: COOLING CAP ACITIES - 2 -1/2 TON (ACP030) Air on Evaporator Coil Temperature of Air on Condenser Coil Total Capacity 1 (MBh) Total Input.
279815-PTG-D-0408 Johnson Controls Unitary Products 9 115°F 125°F 750 77 29.8 2.9 13.7 10. 6 7.4 - - - 28.8 3.1 13.2 10.0 6.7 - - - 72 27.3 2.8 18.3 15. 1 11.9 8.8 - - 25.8 3.0 17.6 14.3 11.1 7.8 - - 67 24.8 2.8 22.9 19.7 16. 5 13.3 10.1 - 22.8 2.9 21.
279815-PTG-D-0408 10 Johnson Controls Unitary Products T ABLE 5: COOLING CAP ACITIES - 3 TON (ACP036) Air on Evaporator Coil Temperature of Air on Condenser Coil Total Capacity 1 (MBh) Total Input (kW.
279815-PTG-D-0408 Johnson Controls Unitary Products 11 115°F 125°F 1000 77 36.0 3.6 17.9 14.4 10. 9 - - - 32.6 3.9 16.6 13.2 9.9 - - - 72 32.6 3.5 23.2 19.7 16. 2 12.8 - - 29.5 3.8 21.7 18.4 15.1 11.7 - - 67 29.3 3.4 28.6 25.1 21. 6 18.1 14.6 - 26.4 3.
279815-PTG-D-0408 12 Johnson Controls Unitary Products T ABLE 6: COOLING CAP ACITIES - 3 -1/2 TON (ACP042) Air on Evaporator Coil Temperature of Air on Condenser Coil Total Capacity 1 (MBh) Total Inpu.
279815-PTG-D-0408 Johnson Controls Unitary Products 13 115°F 125°F 1050 77 42.9 4.6 20.5 16.2 11. 9 - - - 40.5 5.1 19.5 15.1 10.7 - - - 72 39.1 4.5 27.4 23.1 18. 8 14.6 - - 36.5 5.0 26.6 22.2 17.8 13.4 - - 67 35.3 4.5 32.1 30.1 25. 8 21.5 17.2 - 32.
279815-PTG-D-0408 14 Johnson Controls Unitary Products T ABLE 7: COOLING CAP ACITIES - 4 TON (ACP048) Air on Evaporator Coil Temperature of Air on Condenser Coil Total Capacity 1 (MBh) Total Input (kW.
279815-PTG-D-0408 Johnson Controls Unitary Products 15 115°F 125°F 1200 77 47.1 5.0 23.3 19.1 14. 9 - - - 43.8 5.5 21.7 17.7 13.7 - - - 72 42.2 5.0 29.5 25.3 21. 1 16.9 - - 38.8 5.5 27.7 23.7 19.7 15.7 - - 67 37.2 4.9 35.7 31.5 27. 3 23.1 18.9 - 33.
279815-PTG-D-0408 16 Johnson Controls Unitary Products T ABLE 8: COOLING CAP ACITIES - 5 TON (ACP060) Air on Evaporator Coil Temperature of Air on Condenser Coil Total Capacity 1 (MBh) Total Input (kW.
279815-PTG-D-0408 Johnson Controls Unitary Products 17 115°F 125°F 1500 77 60.2 6.2 27.6 22.0 16. 3 - - - 57.5 6.8 26.9 21.2 15.6 - - - 72 54.3 6.2 36.6 31.0 25. 3 19.7 - - 51.1 6.7 35.6 29.9 24.2 18.6 - - 67 48.4 6.1 45.6 39.9 34. 3 28.7 23.0 - 44.
279815-PTG-D-0408 18 Johnson Controls Unitary Products T ABLE 10: ADDITIONAL ST ATIC RESIST ANCE Size (Tons) CFM Wet Indoor Coil Economizer 1 Filter/Frame Kit Electric Heat 024 (2.0) 500 0.01 0.00 0.01 0.02 600 0.01 0.00 0.02 0.03 700 0.01 0.00 0.02 0.
279815-PTG-D-0408 Johnson Controls Unitary Products 19 FIGURE 2 - TYPICAL FI ELD WIRING DIAGRAM REFER TO ELECTRICAL DA T A T ABLES TO SIZE THE DIS - CONNECT SWITCH, WIRING & OVERCURRENT PROTECTION.
279815-PTG-D-0408 20 Johnson Controls Unitary Products T ABLE 1 1: ACP024-060 ELECTRICAL DA T A / ELECTRIC HEA T Size (Tons) Volt Compressors (each) OD Fan Motors (each) Supply Blower Motor Electric Heat Option MCA 1 (Amps) Max Fuse 2 / Breaker 3 Size (Amps) RLA LRA MCC FLA FLA Model kW Stages Amps 024 (2.
279815-PTG-D-0408 Johnson Controls Unitary Products 21 060 (5.0) 208/230-1-60 25.0 150 39 2.3 7.6 None - - - 41.2 50 2NH04501006 7. 5 / 10 2 36.1 / 41. 7 54.6 / 61.6 60 / 70 2NH04501506 11.3 / 15 2 54.2 / 62.5 7 7.2 / 87.6 80 / 90 2NH04502006 15 / 20 2 72.
279815-PTG-D-0408 22 Johnson Controls Unitary Products FIGURE 3 - UNIT DIMENSIONS HIGH VO L TAGE CONN. “ x " DIA. KNOCKOUT 6 DRAIN “ NPTI CONDENS A TE LOW VO L TAGE CONN.
279815-PTG-D-0408 Johnson Controls Unitary Products 23 FIGURE 4 - CENTER OF GRAVITY NOTE: F or units applied with a roof curb, the minimum clearance may be reduced from 1 inch to 1/2 inch between combustible ro of curb material and the supply duct. T ABLE 12: UNIT WEIGHTS Unit Size Sh ipping Weight Operating Weight Corner Weights Economizer (lbs.
279815-PTG-D-0408 24 Johnson Controls Unitary Products TYPICAL APPLICATIONS FIGURE 5 - TYPICAL SLAB ON GROUND INSTALLATION FIGURE 6 - TYPICAL ROOF CURB INSTALLATION TO POWER SUPPL Y SUPPL Y AIR DUCT R.
279815-PTG-D-0408 Johnson Controls Unitary Products 25 FIGURE 7 - ROOF CURB DIMENSIONS (8 ” Roof curb al so available) FIGURE 8 - ROOF CURB APPLICATION FRONT 1 1 WOOD NAILER 4 INSULA TED P ANELS 22 .
279815-PTG-D-0408 26 Johnson Controls Unitary Products FIGURE 9 - T YPICAL WIRING DIAGRAM ( 208/230-1-60 POWER SUPPL Y) ACP MODEL S.
279815-PTG-D-0408 Johnson Controls Unitary Products 27 FIGURE 10 -TYPIC A L WI RI NG DIAGRAM (208/230-3-60 POWER SUPPLY) ACP MODELS.
279815-PTG-D-0408 28 Johnson Controls Unitary Products FIGURE 11 -TYPIC A L WI RI NG DIAGRAM (460-3-60 PO WER SUPPLY) ACP MODELS.
279815-PTG-D-0408 Johnson Controls Unitary Products 29 MECHANICAL SPECIFICATIONS GENERAL DESCRIPTION Units shall be factory-assembl ed, single packaged, Electric Cooling units, designed for outdoor mounted instal lation. ACP units shall have minimum SEER ra tings of 13.
279815-PTG-D-0408 30 Johnson Controls Unitary Products a. Unit shall contain a large, l ow voltage Te rminal Bo ard for easy connection of fi eld low voltage wiring.
279815-PTG-D-0408 Johnson Controls Unitary Products 31.
Subject to change without notice. Print ed in U. S.A. 279815-PTG-D-0408 Copyright © 2008 by Johnson Controls, In c. All righ ts reserved. Supersedes: 279815-PTG-C-1007 Johnson Cont rols Unitary Pr od.
Een belangrijk punt na aankoop van elk apparaat Johnson Controls ACPU024 THRU 060 (of zelfs voordat je het koopt) is om de handleiding te lezen. Dit moeten wij doen vanwege een paar simpele redenen:
Als u nog geen Johnson Controls ACPU024 THRU 060 heb gekocht dan nu is een goed moment om kennis te maken met de basisgegevens van het product. Eerst kijk dan naar de eerste pagina\'s van de handleiding, die je hierboven vindt. Je moet daar de belangrijkste technische gegevens Johnson Controls ACPU024 THRU 060 vinden. Op dit manier kan je controleren of het apparaat aan jouw behoeften voldoet. Op de volgende pagina's van de handleiding Johnson Controls ACPU024 THRU 060 leer je over alle kenmerken van het product en krijg je informatie over de werking. De informatie die je over Johnson Controls ACPU024 THRU 060 krijgt, zal je zeker helpen om een besluit over de aankoop te nemen.
In een situatie waarin je al een beziter van Johnson Controls ACPU024 THRU 060 bent, maar toch heb je de instructies niet gelezen, moet je het doen voor de hierboven beschreven redenen. Je zult dan weten of je goed de alle beschikbare functies heb gebruikt, en of je fouten heb gemaakt die het leven van de Johnson Controls ACPU024 THRU 060 kunnen verkorten.
Maar de belangrijkste taak van de handleiding is om de gebruiker bij het oplossen van problemen te helpen met Johnson Controls ACPU024 THRU 060 . Bijna altijd, zal je daar het vinden Troubleshooting met de meest voorkomende storingen en defecten #MANUAl# samen met de instructies over hun opplosinge. Zelfs als je zelf niet kan om het probleem op te lossen, zal de instructie je de weg wijzen naar verdere andere procedure, bijv. door contact met de klantenservice of het dichtstbijzijnde servicecentrum.