TABULAR DATA SHEET

Outdoor Split System Air Conditioner 2 Thru 5 Tons

MODELS: TCGF24* THRU 60 14.5 SEER – R-410A, 1 PHASE

Physical and Electrical Data

MODEL TCGF24S41S1TCGF30S41S1TCGF36S41S1TCGF42S41S1TCGF48S41S1TCGF60S41S1 Unit Supply Voltage208-230V, 1φ, 60Hz Normal Voltage Range 1187 to 252 Minimum Circuit Ampacity 16.818.419.123.927.935.9 Max. Overcurrent Device Amps 2 253030404560 Min. Overcurrent Device Amps 3 202020253040 Compressor Type ScrollScrollScrollScrollScrollScroll Compressor R Amps Lated Load 12.814.114.117.921.127.5 ocked Rotor 587377112115135 Crankcase Heater NoNoNoNoNoNo Fan Motor Amps Rated Load .8.81.51.51.51.5 Fan Diameter Inches 222222242424 R Fan Motor N Nated HP 1/81/81/41/41/41/4 ominal RPM 10751075850850850850 ominal CFM 275028003200360036003700 F Coil R Face Area Sq. Ft. 13.117.417.420.021.424.0 ows Deep111111 in / Inches 232323232323 Liquid Line Set OD (Field Installed) 3/83/83/83/83/83/8 Vapor Line Set OD (Field Installed) 3/43/43/47/87/81 1/8 Unit Charge (Lbs. - Oz.) 4 3- 23 - 73 - 104 - 44 - 95 - 9 Charge Per Foot, Oz. 0.620.620.620.670.670.75 Operating Weight Lbs. 128130145172180199
1. Rated in accordance with ARI Standard 110, utilization range “A”.
2. Dual element fuses or HACR circuit breaker. Maximum allowable overcurrent protection.
3. Dual element fuses or HACR circuit breaker. Minimum recommended overcurrent protection.
4. The Unit Charge is correct for the outdoor unit, matched indoor coil and 15 feet of refrigerant tubing. For tubing lengths other than 15 feet, add or subtract the amount of refrigerant, using the difference in length multiplied by the per foot value.

All dimensions are in inches. They are subject to change without notice. Certified dimensions will be provided upon request.

Unit ModelDimensions (Inches)Refrigerant Connection Service Valve Size A1BCLiquidVapor 242829293/4” 30362929 36362929 423433.633.67/8” 483633.633.6

A

60 40 33.6 33.6 7/8”2

1. Including Fan Guard.

B

2. Adapter fitting required for 1-1/8” line set.

Johnson Controls Unitary Products 362564-UTD-B-0708

Page 2 of the Johnson Controls TCGF24 user manual — 362564-UTD-B-0708
Pagina 2 · klik om te vergroten
Pagina 2

362564-UTD-B-0708

R-410A SYSTEM CHARGING PROCEDURE

Additional R-410A Charge / Orifice Size for Various Matched Systems Outdoor UnitTCGF24S41S1TCGF30S41S1TCGF36S41S1TCGF42S41S1TCGF48S41S1TCGF60S41S1 Required Orifice or TXV 11TVM9021TVM9031TVM9031TVM9031TVM9051TVM906 Factory Charge, lbs-oz3 - 23 - 73 - 104 - 44 - 95 - 9 Indoor Coil2,3,4Additional Charge, Oz FC/MC/PC24A3X5––––– FC/MC/PC24B3X5––––– FC/MC/PC30A3X122–––– FC/MC/PC30B3X122–––– FC/MC/PC32A3X1610–––– FC/MC/PC35B3X1610–––– FC/MC/PC35C3X1610–––– FC/MC/PC36A3X84–––– FC/MC/PC36B3X848––– FC/MC/PC36C3X841––– FC/MC/PC37A3X241915––– FC/MC/PC43B3X2419155–– FC/MC/PC43C3X2419155–– FC/MC/PC48C3X4032151716– FC/MC/PC48D3X4032271716– FC/MC/PC60D3X–––17160 FC/MC62D3X–––252618 UC24A3X8––––– UC24B3X8––––– UC30A3X84–––– UC30B3X84–––– UC36A3X–––––– UC36B3X–––––– UC36C3X–––––– UC42B3X–––––– UC42C3X–––––– UC48C3X–––––– UC48D3X–––––– UC60C3X––12––– UC60D3X––12––– HC18A3X–––––– HC30A3X10––––– HC36B3X16118––– HC42C3X2519156–– HC60D3X–––000 HD24*3X16––––– HD36*3X18––––– HD48*3X5142362425– HD60*3X––––24– AHP18B3X–––––– AHP24B3X3––––– AHP30B3X16–––– AHP36C3X–1915–––
Johnson Controls TCGF24 — 362564-UTD-B-0708 diagram (page 2)
Afb. 1

2 Johnson Controls Unitary Products

Page 3 of the Johnson Controls TCGF24 user manual — PROCEDURES:
Pagina 3 · klik om te vergroten
Pagina 3

362564-UTD-B-0708

R-410A SYSTEM CHARGING PROCEDURE

Johnson Controls TCGF24 — 362564-UTD-B-0708 diagram (page 3)
Afb. 2
Additional R-410A Charge / Orifice Size for Various Matched Systems (Continued) Outdoor UnitTCGF24S41S1TCGF30S41S1TCGF36S41S1TCGF42S41S1TCGF48S41S1TCGF60S41S1 Required Orifice or TXV 11TVM9021TVM9031TVM9031TVM9031TVM9051TVM906 Factory Charge, lbs-oz3 - 23 - 73 - 104 - 44 - 95 - 9 Indoor Coil2,3,4Additional Charge, Oz AHP42C3X–––––– AHP/SHP60D3X––––1– AV24B3X3––––– AV36C3X251915––– AV/SV48D3X––901– AV/SV60D3X–––010 F4FP024See Caution below0––––– See Caution below F4FP030 See Caution below30–––– F4FP036 See Caution below–85––– F4FP040 See Caution below–128––– F4FP042 See Caution below––80–– F4FP045 See Caution below––92–– F5FP048 See Caution below––201011– F5FP060 See Caution below––201011– F4FV060 See Caution below––9101–

FOOTNOTES:

1. Systems matched with furnace or air handlers not equipped with blower-off delays may require blower Time Delay Kit 2FD06700224. 2. PC coils cannot be used in downflow or horizontal applications. FC coils cannot be used in horizontal applications. 3. A TXV kit must be used with these coils to obtain system performance. Note: If a TXV is factory installed on the coil, it must be replaced with the listed TXV 4. Refer to Technical Guide for actual system performance and matches.

PROCEDURES:

1. Unit factory charge listed on the unit nameplate includes refrigerant for the condenser, the smallest evaporator and 15 feet of inter- connecting line tubing. 2. Verify the TXV or orifice and additional charge required for specific evaporator coil in the system using the above table. 3. Add additional charge for the amount of interconnecting line tubing greater than 15 feet at the rate specified in Physical and Electri- cal Data Table. 4. For TXV match charge weight needs to be weighed in for specififc coil match and lineset length. 5. Permanently mark the unit nameplate with the total system charge. Total System Charge = Base Charge (as shipped) + adder for evaporator + adder for line set.

Johnson Controls TCGF24 — PROCEDURES: diagram (page 3)
Afb. 3

If the F*FP Air Handler used has a with a factory installed R-22 TXV it MUST BE CHANGED OUT to a R-410A TXV or a orifice for proper operation. If the TXV is not changed out system damage will occur.

Johnson Controls Unitary Products 3

Page 4 of the Johnson Controls TCGF24 user manual — Johnson Controls Unitary Products
Pagina 4 · klik om te vergroten
Pagina 4

NOTES

*362564*

Subject to change without notice. Printed in U.S.A. 362564-UTD-B-0708 Copyright © 2008 by Johnson Controls, Inc. All rights reserved. Supersedes: 362564-UTD-A-0608

Johnson Controls Unitary Products

5005 York Drive Norman, OK 73069

Vraag stellen over de Johnson Controls TCGF24

Eigenaren en ons team reageren doorgaans binnen een dag — en uw vraag helpt ook de volgende persoon.

Add your email to get notified when it’s answered — no spam, ever.

0 questions
Nog geen vragen over de Johnson Controls TCGF24

Stel als eerste een vraag — andere eigenaren of ons team geven antwoord.

Origineel document

Johnson Controls TCGF24 handleiding-pdf

4 pagina's·115 KB·Airconditioner·PDF
Klik op een bovenstaande pagina om deze hier te openen
Pagina 1 / …
100%
Pagina's laden…