MGE TM Galaxy TM 5000 20 - 120 kVA Install ation and us er manual.
34001813E N/AE - Page 2 Introduction Thank you for selecting an APC by Schneider Electr ic product t o protect yo ur electrical equipment. The MGE TM Gala xy TM 5000 range has been designed with the ut most care. We recommend that you take the time to read this manual to t ake full advantage of the many features of your UP S .
34001813E N/AE - Page 3 Safety Safet y rules Safet y of pe rsons Product sa fety Special precautions The UPS must be installed in a room wit h restricted acce s s (qualified personnel only, according to s tandard 62040-1-2). A UPS has its own int ernal power source (t he battery).
34001813E N/AE - Page 4 Foreword Pictograms Docu ment D ispla y Danger, these instructions are imperative. Information, advice, help Visual indication Act ion Audio signal LED OFF LED flashing LED ON .
334001813EN/A E - Page 5 Content s 1. Present ation 1.1 MGE TM Galaxy TM 5000 ................. ........... ................. ........... ................. ........... ................. ......... 8 UPS cabinet .............. ............ .............
334001813E N/AE - Page 6 Contents 2.16 Po wer con nections for an externa l battery c abinet ............. ........... ................. ........... ...........38 2.17 A ssembly and con nection of an empty b attery ca binet ................. .........
334001813EN/A E - Page 7 Content s NMC (Network Manag ement Card) option ................... ........... ................. ........... ................. ....... 59 Option al comm unicatio ns card wi th additio nal power re lay ..................... ..
34001813E N/AE - Page 8 1. Presentation 1.1 M GE TM Galaxy TM 5000 UPS cabinet Extern al batt ery cab inet / au xiliary cabin et Dimensions UPS power rating (kVA) Dim ensi ons (H x W x D) 20/30/40/60 .
34001813EN/A E - Page 9 1. Presen tation 1.2 In side the UPS cabine t, acce ss to con necti ons Example o f version wi th built-in batte ry Simplified diagram o f power conn ections (1) Connectors for.
34001813E N/AE - Page 10 1. Presentation Power-conne ction terminal blocks (versi on with buil t-in battery) Power-conne ction termi nal blocks (version w ith external battery) INTN card for aux iliary interconn ections of p arallel UPS unit s 1.
34001813EN/ AE - Page 11 1. Presen tation 1.4 User -machine i nterfac e 1.5 Rel ay communi cation ca rd (30) Graphical display (31) Load protected LED (32) Minor fault LED (33) Major fault LED (34) He.
34001813E N/AE - Page 12 2. Installation 2.1 Lo cat ion 2.2 La yout o f cab inets To ensure correct ventilation, leave nothing on top of the UPS. Leave one meter of free space in front of the UPS for door opening. The cabinet rests on four cylindrical feet, 40 mm in diameter, positioned in the f our corners of the cabinet to spread the weight.
34001813EN/ AE - Page 13 2. Installation 2.3 Re moving the cardboard pr otec ting th e ba tteries In the UP S In the ext ernal b attery cabin et The cardboard protecting the batteries must always be removed once the equipment is installed in it s final location.
34001813E N/AE - Page 14 2. Installation 2.4 Requ ired pr otecti ve devi ces and cable sizes Recommended up stream prot ection Recommended d ownstream protection Eart h-l eakag e c urr ent UPS earth-leakage current is 1 A.
34001813EN/ AE - Page 15 2. Installation Required cable s izes Cable sizes are d etermined for co pper conductors ( for aluminiu m conductors, increase t he size by 30%). S ize calculations also take into account a voltage o f 400 V an d grouping of four cables.
34001813E N/AE - Page 16 2. Installation Required cabl e sizes for p arallel U PS installat ions with an ext ernal bypass Rat ed power of each UPS unit Number of par a l le l UPS unit s Total r ated p.
34001813EN/ AE - Page 17 2. Installation 2.5 2.5 Syst em ea rthin g arran gemen ts This chapter lists the main s ystem earthing arrangeme nts and their wiring requirem ents. For system e arthing arrangements which are not listed in this document, please refer to the “S EA guide” reference 34002636X T.
34001813E N/AE - Page 18 2. Installation TNC upstream, TNS downst ream For separate Normal AC and Bypass AC lines from a single source Instal lation with upst ream IT and dow nstream TNS For separate .
34001813EN/ AE - Page 19 2. Installation Frequency converter (w ithout Bypass AC input) Up stream and do wnstream: T T , TN or IT sys tem with neutral distributed Up stream and do wnstream: Neutral n .
34001813E N/AE - Page 20 2. Installation Parallel configu ration w ithou t externa l byp ass ca binet a nd with separ ate nor mal and Bypa ss AC inputs (maximu m two u nits i n paral lel) The requirements for the different system earthing arrangemen ts (SEA) are similar to those for si ngle UPS configurations.
34001813EN/ AE - Page 21 2. Installation Parallel UPS with ext ernal byp ass cabinet an d separate No rmal and B ypass AC netwo rk inputs (6 UPS in p ara llel for 4 PN ) The requirements for the different system earthing arrangements (SEA) are similar to those for single UPS configu ration s.
34001813E N/AE - Page 22 2. Installation 2.6 Connect ion of power cabl es in a singl e UPS unit Interconnect ing the c abinet earths UPS unit s with com mon normal and By pas s AC input s UPS unit s w.
34001813EN/ AE - Page 23 2. Installation 2.7 Earth-cable connecti on for a single unit in a TNC earthi ng system 1.Connect the powe r network cable PEN to the UPS earthing te rminal 2.Connect the usage c able PEN to the UPS earthing terminal 3.Connect the Q4S (15) neutral term inal to the UPS earth us ing the cable supplied 4.
34001813E N/AE - Page 24 2. Installation 2.8 Co nnect ion of pow er ca bl es for parallel UPS uni ts Equipotential bonding between par allel-connected units Connect the expos ed conductive pa rts (ECP.
34001813EN/ AE - Page 25 2. Installation Redundant par allel configurati on (maximum two UPS units for Pn) This configuration does not have an ext ernal bypass. UPS unit s with c ommon normal and Byp ass AC input s To access the connection terminal blocks, see section 1.
34001813E N/AE - Page 26 2. Installation Frequency c onverter To access the connection terminal blocks, see section 1.2. 1 - The earthing conductors of each UPS must be connected to the UPS earthing plate. 2 - Connect the neutral conductor of the Normal AC source to the neut ral terminal on terminal block (15) of UPS1.
34001813EN/ AE - Page 27 2. Installation UPS unit s with s epa rate normal an d Byp ass AC inpu ts To access the connection terminal blocks, see section 1.2. 1 - The earthing conductors must be connected to the earthing plate of each UPS. 2 - Connect the t hree phases of the Normal AC source t o terminal block (16) in eac h UPS unit.
34001813E N/AE - Page 28 2. Installation 2.9 Co nnectio n of the 15 0 kV A exte rnal bypass cabinet Key A : top view of c abinet B : front view of cabinet C : 317 x 120 mm opening for cable running D .
34001813EN/ AE - Page 29 2. Installation 2.10 Conne ction of the 360 kVA ex ternal by pass cabi net Key AA : section AA of cabinet B : front view of cabinet C : fron t D : connection of Bypass AC sour.
34001813E N/AE - Page 30 2. Installation 2.11 Con necti on o f the 6 00 k VA ext ernal b ypass ca binet Key AA : section AA of cabinet B : front view of cabinet C : front D : connection of Bypass A C .
34001813EN/ AE - Page 31 2. Installation 2.12 Aux iliary in tercon nection s betw een UPS units i n paralle l conf iguratio ns Redundant par allel configurati on (maximum two UPS units ) For security reasons, the connections of the auxiliary interconnections of the parallel UPSs must be carried out whilst all the UPSs are de-energised.
34001813E N/AE - Page 32 2. Installation Parall el configuratio n for increased cap acity (maximum four UPS units) Interconnections with the external bypas s cabinet ◗ Interconnect terminals 1, 3 and 5 on the auxiliary terminal block in the cabinet.
34001813EN/ AE - Page 33 2. Installation Fitt ing t he pr otec tion c ove r for th e au xili ary inte rcon nec tion cabl es The protection cov er supplied with the par allel connected UPS units protects t he us er against direct contact with v oltages other than SELVs an d ensures the auxiliary inte rconnection cables are maintained in position.
34001813E N/AE - Page 34 2. Installation 2.14 Con necti on o f th e relay com municat ions ca rd Isolate and l ock-out all power sources f o r this card before making connections. Never connect SELV (safety extra low voltage) and n on-SELV circuits to the different o utputs of the same card .
34001813EN/ AE - Page 35 2. Installation Characte ristics o f the cont acts on the relay communica tions card . Communica tions ca rd connection example If a SELV (safety extra low voltage) source is .
34001813E N/AE - Page 36 2. Installation 2.15 Ru nning the c ontrol /commun ications cables Single UPS The following assembly r ecommendations m ust be followed to ensur e correct positioning and suppo rt of the various s trands of the control and communication cables on the front face of the UPS.
34001813EN/ AE - Page 37 2. Installation Parallel UPS Parallel-connection cabl es for connection to the external bypass cabinet (not supplied max. 2.5 mm 2 ). The CAN and I exchange cables are supplied. Relay communicat ion card Optional communications c ards Ties General-shutdown cable (not supplied, max.
34001813E N/AE - Page 38 2. Installation 2.16 Pow er co nnectio ns for an ext ernal battery c abinet The earth on an external battery cabinet must be connected to the UPS 2.17 A ssembly and conn ection of an emp ty battery cabi net Mounti ng the ba ttery circ uit brea ker kit Secure: 1 - The base plate (60) supporting the circuit breaker.
34001813EN/ AE - Page 39 2. Installation Mounting the shelves and the battery cells Caution. Assembly of the bat tery cabinet must be carried out by cert ified personnel (standard EN 50091-1-2). Caution. The minimum clearance between the top of battery cells an d the next shelf is 150 millimeters.
34001813E N/AE - Page 40 2. Installation 2.18 Con trol co nnect ions for an ext ernal battery c abinet 1 - C onnect wires 1-2-3-4 on connector X R 1 (QF1 position and coil) in the ext ernal battery cabinet to connector XMB07 (6) (SELV) a nd wires 7-8-9-10 ( temper ature sensor) to connecto r XMD3 (22) (SELV) .
34001813EN/ AE - Page 41 2. Installation 2.19 Co nnectio n of an input isolat ing tra nsfor mer 2.20 Conne ction of an ou tput isola ting trans form er A - Connection of an input transformer for common normal and Bypass AC source. B - Connection of a Bypass AC input transform er for separate normal and Bypass AC sourc es.
34001813E N/AE - Page 42 3. Operation 3.1 Shut ting do wn a s ingle UPS The UPS remains energised unless it is shut down. 3.2 Res tartin g a singl e UPS Check that switches Q4S (9) and Q5N (11) are closed. I f this is the case, continue with this procedure, otherwise refer to paragraph 4.
34001813EN/ AE - Page 43 3. Operation 3.3 Shutt ing down a parallel co nfigur ation 3.4 Res tart ing a para llel co nfigur ation Check that switches Q 4S (9) and Q5N (11) are closed. If this i s the case, c ontinue with this procedure, otherwise refer to paragr aph 4.
34001813E N/AE - Page 44 3. Operation 3.5 O peration o f mimic -panel LEDs Single UPS sta rt sequence on Norma l AC input Single UPS start sequence on Bypass AC input Steps Actio n LED (39) LED (40) L.
34001813EN/ AE - Page 45 3. Operation 3.6 Oper ating mod es Normal ( double conversi on) mode This is the standard operating mode, set by default in the factory. Two possible cases: ECO mode (singl e UPS only) 1 - Normal AC source available: LED (31) is ON.
34001813E N/AE - Page 46 3. Operation 3.7 Lo ad on ba ttery power The load continues to be protected by t he UP S when the Normal AC s ource is not available. Power is supplied by t he battery. Trans fer to ba ttery p ower End of bat tery p ower 3.8 UPS persona lisat ion Access to the personal isation funct ions LED (32) is ON.
34001813EN/ AE - Page 47 3. Operation Operating mode Frequency Automa tic by pass Battery Function F actory setting Option s UPS operat ing mode NORMAL ECO UPS automat ic start Disabled Enabled Author.
34001813E N/AE - Page 48 3. Operation 3.9 Rel ay con tac ts (comm uni cation s ca rd) The indications 1.X become 2.X for a second identical card in the UPS. Contacts are of the NO (normally open) type. (1) The general alarm c an be tested by opening the battery circuit breaker.
34001813EN/ AE - Page 49 3. Operation 3.10 D isplay functi ons Battery measurements Welcome screen Main menu ? Press this key to return to the main menu Help key for information on the pictogram funct.
34001813E N/AE - Page 50 4. Maintenance 4.1 I dentifi catio n of alarm s Alarm conditions are identified by LEDs (31), (32), (33) and the buz zer. Detailed information on all alarms is supplied on the display. 1 - On the screen, select the alarm for which inf ormation is required.
34001813EN/ AE - Page 51 4. Maintenance 4.3 UPS isol ation Sing le UPS To isolate the UPS from the el ectrical power source and suppl y the load direct ly by the no rmal or B ypass AC source, follow the instructions below.
34001813E N/AE - Page 52 4. Maintenance If the load is supplied by the UPS with Byp a ss AC source present: Parall el UPS confi guration w ithout exter nal bypass ca binet Shut down and is olation of the first UPS unit: Shut down and is olation o f the second UPS unit: 1 - Press a button to exit sleep mode.
34001813EN/ AE - Page 53 4. Maintenance Parallel UPS configur ation with ex ternal byp ass cabinet Shut down and isolation of one UPS unit Shut down and isolation of all the UPS un it s: 1 - First c heck that the total capacity of t he remaining UPS units is sufficient to supply the connected load.
34001813E N/AE - Page 54 4. Maintenance 4.4 Re turn to the nor mal posi tion Single UPS Frequency converter 1 - Check that bypass s witch Q3BP (10) is ON and that all other switches are OFF. 2 - Set input switch Q4S (9) to ON. 3 - Set output switch Q5N (11) to ON.
34001813EN/ AE - Page 55 4. Maintenance Para llel UP S confi gurati on w ithout e xtern al byp ass ca binet Rest art the UPS unit for which switch Q3BP (10) is ON and the o ther swi tches are O FF . Rest art the UPS unit for which all switches a re set to OF F .
34001813E N/AE - Page 56 4. Maintenance Parall el UPS configuration w ith external bypas s cabinet 1 - Check that all switches on the UPS units are set to OFF. 2 - Set switch Q4S in the external bypass cabinet to ON. 3 - Set switc h Q4S (9) on each UPS unit to ON.
34001813EN/ AE - Page 57 4. Maintenance 4.5 Tr aining ce ntres To allow you to us e APC by Schneider E lectric products effectively and carry out bas ic maintenance, we offer a complete range of technical training cou rses in English and French.
34001813E N/AE - Page 58 5. Environment APC by Schneider Electric has implemented an environmental-protection policy. Products are developed according to an eco-design approach. Subst ances This product does not contai n CFCs, HCFCs or asbestos. Packing To improve waste treatment a nd facilitate re cycling, separate the various packing components.
34001813EN/ AE - Page 59 6. Available options Backfeed op tion This option opens the Bypass AC input or the Normal AC input if power fails. This option is mandatory to meet standard I EC 62040-1-2. If an external bac kfeed protection sy stem is us ed, it must c o mply with the requirements indicated in A nnex L of standar d IEC 62040-1-2.
34001813E N/AE - Page 60 7. Appendices 7.1 Tec hnica l sheet s Center o f gravity Tip an gle (to the rear) UPS pow er rating (kVA) H (mm) W (mm) D (mm) 20/30/40/60 kVA 950 350 360 80/100/120 kVA 950 350 360 UPS pow er rating (kVA) UPS on feet UPS on pall et 20/30/40/60 kVA 17.
34001813EN/ AE - Page 61 7. Appendices Electrical characte ristics Selection of protection de vices UPS short-ci rcuit current with in verter coupled and By-pass AC source out of tolerances: UPS unit .
34001813E N/AE - Page 62 7. Appendices Line current values Input / output characteristics Normal AC source / Bypass AC source Load ou tput Rated power of each UPS uni t Continuo us inpu t current at U=400V Input cur rent at U=400V overload = 1.25 In limited to 10 min.
34001813EN/ AE - Page 63 7. Appendices Maximum al lowable po wer for p arallel UPS un its Without external b ypass cabinet: With external bypass cabinet: + = 1 x Pn = 1 x Pn I O 3 s ? ~ I O 3 s ? ~ I .
34001813E N/AE - Page 64 7. Appendices The maximum allowable power for 4 parallel UPS units is limited to 4 x Pn. Restriction s to parallel operation (*) : exc ept in ECO m ode or bypa ss mode.
34001813EN/ AE - Page 65 7. Appendices General charact eristic s of MGE TM Galaxy TM 5000 UPSs (1)Losses are calculated for n-1%. UPS pow er in kVA 20 30 40 60 80 100 120 Normal AC inpu t Number of conduct ors 3 phases Reference voltage at Pn 380 V t o 443 V Reference frequency 45 Hz to 65 Hz THDI Typi cal ly 3 % at Pn Power factor >0.
34001813E N/AE - Page 66 7. Appendices General cha racterist ics of MGE TM Ga laxy TM 5000 UPSs (cont.) UPS comp onents UPS p ower in kVA 20 30 40 60 80 100 120 N o i s e l e v e l ( d B a ) 6 56 56 5.
34001813EN/ AE - Page 67 7. Appendices 7.2 Opti ons IP32 instal lati on Install the protection cover above the UPS. Install the spacers. The longer spacer s must be positioned toward the f ront of the UPS. Install the roof. Install the side deflectors.
3400181300/ AE 7. Appendices 7.3 G lossary Backup time Time that the connected loads can operate on battery power. Bypass AC source Source supplying the bypass line. The load can be transferred to the bypass line if an overload occurs on t he UPS out put, for maintenanc e or in the event of a ma lfunction.
Een belangrijk punt na aankoop van elk apparaat APC 5000 (of zelfs voordat je het koopt) is om de handleiding te lezen. Dit moeten wij doen vanwege een paar simpele redenen:
Als u nog geen APC 5000 heb gekocht dan nu is een goed moment om kennis te maken met de basisgegevens van het product. Eerst kijk dan naar de eerste pagina\'s van de handleiding, die je hierboven vindt. Je moet daar de belangrijkste technische gegevens APC 5000 vinden. Op dit manier kan je controleren of het apparaat aan jouw behoeften voldoet. Op de volgende pagina's van de handleiding APC 5000 leer je over alle kenmerken van het product en krijg je informatie over de werking. De informatie die je over APC 5000 krijgt, zal je zeker helpen om een besluit over de aankoop te nemen.
In een situatie waarin je al een beziter van APC 5000 bent, maar toch heb je de instructies niet gelezen, moet je het doen voor de hierboven beschreven redenen. Je zult dan weten of je goed de alle beschikbare functies heb gebruikt, en of je fouten heb gemaakt die het leven van de APC 5000 kunnen verkorten.
Maar de belangrijkste taak van de handleiding is om de gebruiker bij het oplossen van problemen te helpen met APC 5000 . Bijna altijd, zal je daar het vinden Troubleshooting met de meest voorkomende storingen en defecten #MANUAl# samen met de instructies over hun opplosinge. Zelfs als je zelf niet kan om het probleem op te lossen, zal de instructie je de weg wijzen naar verdere andere procedure, bijv. door contact met de klantenservice of het dichtstbijzijnde servicecentrum.